Lot of Electrical youtube channels are there, But your contents are exclusively substation and it's equipments oriented in tamil. No one is doing particularly like yours with neat practical explanation. Congrats keep going on to educate us through new contents 👏😊
Differential protection ka or vera va? Pilot cable differential protection la b/w la fault varum pothu both the breaker trip aga pilot cable use pandron
The allowable leakage current for a vacuum circuit breaker during a vacuum bottle test typically depends on the manufacturer's specifications and industry standards. It's crucial to refer to the specific technical documentation provided by the manufacturer or relevant standards Normally it will be micro amps
Thank you for your valuable Question Sir We can apply AC or DC voltage no issue When compare to AC voltage DC injection will give accurate result Also AC v can do our aim to measure Dielectric strength
மிகவும் தெளிவான விளக்கம் நண்பரே. எளிமையாக புரிந்தது. நன்றி.
அருமை 👏👏👏👏
I don’t understand tamil but understood your concept. ❤
Lot of Electrical youtube channels are there, But your contents are exclusively substation and it's equipments oriented in tamil. No one is doing particularly like yours with neat practical explanation.
Congrats keep going on to educate us through new contents 👏😊
Really Thanks Mr.Mohamed Askar
No words to say
Keep support you will get Good videos
God bless u bro u r a good teacher
விளக்கம் அருமை.
Excellent work bro need to upload more videos hv and lv testing❤
இந்த மாதிரி தெளிவா யாரும் சொன்னதே இல்லை . மற்ற vcb ACB testing பற்றியும் வீடியோ போடுங்க
❤
Your videos are realy awesome with clear explanation and advice❤
❤
very good information sir keep doing more videos
Thank you for your valuable supports
Good explanation, thank you
Thank you so much sir. You are doing great job.
Really Thank you
Brother
Acb full preventive maintenance podunga bro
Explain speak very good anna
Please keep support
Super sir... Thank you
Please do video for control panel high voltage test with procedures as soon as possible
Sure
Nice explanation brother... Keep doing
Thanks sir good explain
Thank you sir
Excellent
thank u sir
Thank you Brother
Good
Vara level 👍 sir,
Thank you brother
Put video on Air Circuit Breaker & it's Test
Sure
Keep supporting
Thank you sir
Super bro ❤❤❤🎉🎉🎉
Hi sir intha test ku calculation epudi pananum means injected kv epudi calculate pananum
Thanks Sir thelivana vilakkam. relay testing eppo arambika poringa...
Relay testing Daily Yeduthuttu thaan brother but video yedukka mudiyala
@@Engineering-in-tamil sir pilot wire connection konjam sollunga.
Differential protection ka or vera va?
Pilot cable differential protection la b/w la fault varum pothu both the breaker trip aga pilot cable use pandron
@@Engineering-in-tamil differential protection than sir. Idhu ct secondary cable thana S1 S2 , ila na . Indha panel relaykum adutha panel relaykum Naduvil pogum cable la sir
@@Engineering-in-tamil enga panel la ferrule number T5 ,T6. Potu iruku. Idhu than sir.idhu S1 S2 va nu theriya la..
Thanks
Sir nan wire man.. ennaku pilot wire connection konjam sollunga sir.neenga sonnega. Relay pinnadi connection pannum bothu puriya matuthu
No problem
9787433094
Entha number Ku WhatsApp msg pannuga clear ah voice msg la soldren
What is the allowable leakage current sir ??
The allowable leakage current for a vacuum circuit breaker during a vacuum bottle test typically depends on the manufacturer's specifications and industry standards. It's crucial to refer to the specific technical documentation provided by the manufacturer or relevant standards
Normally it will be micro amps
What shall be the test voltage in DC for 6.6kV & 11kV Vacuum Circuit Breaker?
Common ah
We will give 2 times of Operating voltage
How to know how much voltage will be apply and in case we are applying ac what will happen
(Vcb ideal charge) nu soranga apadiba enna sir
Why you are applying DC volt to an AC breaker?
Thank you for your valuable Question Sir
We can apply AC or DC voltage no issue
When compare to AC voltage DC injection will give accurate result
Also AC v can do
our aim to measure Dielectric strength
❤
Sir, here we set micro Amps to 300, what is the criteria for selecting this value? And is it based on the Kv rating of breaker?
Breaker manufacturer recommendations
Generally we are taking reference value 300microAmps
Thank you for valuable comments
Sir unga contact no plz i want know resting