How to do ACB breaker settings | Overload | Short circuit | Earth fault | Instantaneous fault

แชร์
ฝัง
  • เผยแพร่เมื่อ 9 พ.ค. 2020
  • How to do major protection settings in Air circuit breaker like overload current setting, short circuit current setting, earth fault current setting, instantaneous current fault setting.
    Please watch the video completely and more about electrical engineering please subscribe to our youtube channel " Electrical Mastar"
    #ACBsetting #ACBprotectionsettings #Aircircuitbreakersetting #ACBrelaysetting #ACBmicrologicsetting

ความคิดเห็น • 34

  • @sheikabbas1207
    @sheikabbas1207 2 หลายเดือนก่อน

    Thank you very much for good explanation.

  • @owinookello9358
    @owinookello9358 2 ปีที่แล้ว +1

    i 💕 your teachings sir great

  • @vinzers1311
    @vinzers1311 2 ปีที่แล้ว

    Very Informative and detail video. ACB's are usually recommended on 800A - 6300A.

  • @rameshtripathy5978
    @rameshtripathy5978 2 ปีที่แล้ว

    Nice description & definitely helpful to commissioning engineers & maintenance technicians !

  • @africantales124
    @africantales124 2 ปีที่แล้ว

    Nice video. Very explicit.
    Please talk on shunt trip and under voltage release coil.

  • @KKumar-sk2kd
    @KKumar-sk2kd 3 ปีที่แล้ว

    Good explaining thank you sir

  • @sohailjanjua123
    @sohailjanjua123 ปีที่แล้ว

    Hi, I like your video. Thanks

  • @majifscreation
    @majifscreation 4 ปีที่แล้ว

    👌

  • @prakashksp2918
    @prakashksp2918 ปีที่แล้ว

    Good explain sir

  • @shankargoudapp9472
    @shankargoudapp9472 3 ปีที่แล้ว +1

    Hi sir super teaching thank you 👍

  • @gopalakrishnanc.p4415
    @gopalakrishnanc.p4415 ปีที่แล้ว

    Excellent

  • @pavankumar-ey3bw
    @pavankumar-ey3bw 3 ปีที่แล้ว

    Good sir

  • @TIGREinVOLO
    @TIGREinVOLO 2 ปีที่แล้ว

    Good video

  • @azuram6261
    @azuram6261 2 ปีที่แล้ว

    Thanks

  • @Sourav8692
    @Sourav8692 3 หลายเดือนก่อน

    Ii and Isd can be kept switched on simultaneously?

  • @ismailajarju8222
    @ismailajarju8222 2 ปีที่แล้ว

    thanks

  • @abomohamedalrubee5287
    @abomohamedalrubee5287 3 ปีที่แล้ว

    Hi there, thank you for video. the tg began from A to J what this mean?

  • @siddeshaj552
    @siddeshaj552 3 ปีที่แล้ว

    Please upload working principle of oltc

  • @anbarasansss1673
    @anbarasansss1673 2 ปีที่แล้ว

    How to setting in Ir value amps micrologic 6.0.A

  • @Sourav8692
    @Sourav8692 3 หลายเดือนก่อน

    Why I2t on and I2t off term has come for alarm ??

  • @thklran6400
    @thklran6400 ปีที่แล้ว

    Hi sir, please help, i have trouble at my site, we install transformer 20kv/0,69kv LV side going to ACB siemens 3wl 2000A, load 1 motor 250kw, with DOL starter, the problem indication ground fault in ACB ON status (alarm) during motor start, after 3 second motor run, alarm ground fault is missing, if the setting Ground fault adjust min to max , acb will be trip , ground fault adjust to off, motor normal running, indication ground ON only < 2 seconds

  • @pavankumar-ey3bw
    @pavankumar-ey3bw 3 ปีที่แล้ว

    Hai give me some information. Dip switchs is 1 2 3 4 but setting value is 3 numbers available. In Abb ACB breaker relay setting

  • @arvindchauhan-mi2rh
    @arvindchauhan-mi2rh 2 ปีที่แล้ว

    From which point it will give to external breaker command for tripping.

  • @mohammadafroz4611
    @mohammadafroz4611 3 ปีที่แล้ว

    Sir,
    In Abb relays for HT panel how to know what current is dangerous when earth fault occurs while charging the transformer...as the settings 0.3 In where In is 100. But when earth fault occurs how to know what current is dangerous and what is not so that we can charge again.

  • @benignojeciel7252
    @benignojeciel7252 3 ปีที่แล้ว

    Hi Pare, can u help me, sace tmax7 is tripping without load how can i fix it and set it to rated current 1200amps, nominal current is 1600 amps. Thanks Pare for helping me.

    • @electricalmastar
      @electricalmastar  3 ปีที่แล้ว

      Hi pare, thanks for your comments and could you tell me when it was Tripp what are the relay been activated

  • @bejoyfrancis5598
    @bejoyfrancis5598 2 ปีที่แล้ว

    Hi IG values of the breaker differs based on rating. Which was not explained

  • @basavarajus9383
    @basavarajus9383 4 ปีที่แล้ว +2

    What is instantaneous current fault in ACB

    • @electricalmastar
      @electricalmastar  4 ปีที่แล้ว +1

      Instantaneous fault means phase to phase fault will occur it produce large current that time ACB will trip immediately without time delay

  • @vamshiganapavarapu7885
    @vamshiganapavarapu7885 ปีที่แล้ว

    Earth fault
    A to J means

  • @prakashksp2918
    @prakashksp2918 ปีที่แล้ว

    How to select the relay settings
    L.over load
    Flc*0.80 or 0.85
    S. Short circuit
    Flc* 2times or 3times
    Instantaneous current
    Flc*4 times or 6 times
    G ground
    Flc*0.10 or 0.15
    Sir but
    Short circuit current
    2 time or 3 times sent pandra thu epdi sir enna formula
    Instantaneous current
    4 times or 6 times set in what formula

  • @akhildogra7017
    @akhildogra7017 2 ปีที่แล้ว

    Sir.
    My breaker capacity is 800amps all breaker setting is ok but still my breaker tripped at 300amps of load