But main difference between Differential protection and REF is differential will not detect the fault near neutral as voltage is low, for protecting this we use REF is used,
Ref is protected the sensitive fault only. If fault is near to winding only Ref protect. But u telling ,Current is very low ref will not protect and operate.how?
@@baranitech1026 why is it low current If the fault near to neutral? Where if it is near to neutral point resistance is too low and fault current will flow freely. The CT will also reads fault current.
VERY BEAUTIFULLY EXPLAINED THANKS A LOT
welcome
Neutral CT is available in bushing which is ahead of NGR. Does its will change the fundamental
same it will not have changes.
Many thanks.
You are welcome!
But main difference between Differential protection and REF is differential will not detect the fault near neutral as voltage is low, for protecting this we use REF is used,
Thank u
Welcome
Thanks
Welcome
Thank you
Thank you 🙏
Welcome!
Thanks you
Welcome
What is the use of stabilizing resistor & how to calculate the value , thank u ji
Will upload soon
Thank u
Then how to protect that 20 - 5% winding fault..?
we have different frequency inject method is there for protecting but mostly they will not use in Transformer
Ref is protected the sensitive fault only. If fault is near to winding only Ref protect. But u telling ,Current is very low ref will not protect and operate.how?
if the fault is very very near to neutral end then it can not protected so only its name restricted earth fault
@@baranitech1026 which function protect not protected area?
@@baranitech1026 why is it low current
If the fault near to neutral? Where if it is near to neutral point resistance is too low and fault current will flow freely. The CT will also reads fault current.
@@TH-cam-Creator81 but voltage will be very less
Tamil video pooduka sir please
i will make for you