Both the KP35 and KP36 are equipped with SPDT (Single Pole Double Throw) contacts, which means they can switch between two circuits. The contacts can handle low voltage DC circuits, including 24V DC. This means they can open or close a circuit carrying a 24V DC signal. Given their contact rating for DC, they are suitable for controlling a 24V DC signal within their specified load limits. The Danfoss KP35 and KP36 pressure switches can indeed be used to give a signal to a 24V DC circuit, provided the current through the contacts is within the switch's specified ratings.
I have this switch in my pressure booster pump frequently it’s terminal meltdown when pump on and terminal remain in contact for sometime it melt and stuck joint together so it doesn’t stop and pump remain on. Any suggestions why I am having this. I have replaced 2 switches but problem remain same.
Hy Chichano Lotha, The Danfoss KP35 and KP36 Wiring connection diagrams are explained in detail in the technical datasheet and we request you to reach our technical expertise for further queries. Thank you!
I have this switch in my pressure booster pump frequently it’s terminal meltdown when pump on and terminal remain in contact for sometime it melt and stuck joint together so it doesn’t stop and pump remain on. Any suggestions why I am having this. I have replaced 2 switches but problem remain same. Let me know the Customer care number for this Danfoss KP35.....
@@InstrukartHoldings********Answer for this issue ******* I have this switch in my pressure booster pump frequently it’s terminal meltdown when pump on and terminal remain in contact for sometime it melt and stuck joint together so it doesn’t stop and pump remain on. Any suggestions why I am having this. I have replaced 2 switches but problem remain same*******
It is well explained , keep it up .
nice explanation👍👍👍
ma'am can it give single to 24 v DC
Both the KP35 and KP36 are equipped with SPDT (Single Pole Double Throw) contacts, which means they can switch between two circuits.
The contacts can handle low voltage DC circuits, including 24V DC. This means they can open or close a circuit carrying a 24V DC signal.
Given their contact rating for DC, they are suitable for controlling a 24V DC signal within their specified load limits.
The Danfoss KP35 and KP36 pressure switches can indeed be used to give a signal to a 24V DC circuit, provided the current through the contacts is within the switch's specified ratings.
Awesome lecture
Thanks and welcome
Can i use it on water line?
Please tell me is there any difference between them? I want to use it with havells hbtm2 pressure pump which comes with kp35.
The difference between the KP35 & KP36 is pressure connection size & regulation range
I have this switch in my pressure booster pump frequently it’s terminal meltdown when pump on and terminal remain in contact for sometime it melt and stuck joint together so it doesn’t stop and pump remain on. Any suggestions why I am having this. I have replaced 2 switches but problem remain same.
Use contactor of required amperage of motor along with this pressure switch.
Nice
Thanks
Hello Madam...... Could you please send me the diagram or video of danfoss pressure switch wiring connection in detail
Hy Chichano Lotha,
The Danfoss KP35 and KP36 Wiring connection diagrams are explained in detail in the technical datasheet and we request you to reach our technical expertise for further queries.
Thank you!
I have this switch in my pressure booster pump frequently it’s terminal meltdown when pump on and terminal remain in contact for sometime it melt and stuck joint together so it doesn’t stop and pump remain on. Any suggestions why I am having this. I have replaced 2 switches but problem remain same.
Let me know the Customer care number for this Danfoss KP35.....
Too much current , Install an appropriate sized contactor instead.
What its actual purpose
At certain pressure these are used as Switches to ON\OFF
@@InstrukartHoldings********Answer for this issue ******* I have this switch in my pressure booster pump frequently it’s terminal meltdown when pump on and terminal remain in contact for sometime it melt and stuck joint together so it doesn’t stop and pump remain on. Any suggestions why I am having this. I have replaced 2 switches but problem remain same*******
How to connect KP 36 pressure switch in to PLC.