How to Sync a Honeywell Power Supply with Another Panel (Fire-Lite, Notifier, and More!)

แชร์
ฝัง
  • เผยแพร่เมื่อ 29 ก.ย. 2024
  • Do you like these demonstrations? Let me know below!
    WEBSITE: www.thefirepan...
    FORUMS: forums.thefire...
    WIKI: wiki.thefirepa...
    DISCORD: / discord
    INSTAGRAM: / thefirepanel
    THREADS: www.threads.ne...
    FACEBOOK: / thefirepanelllc
    TIKTOK: / thefirepanel

ความคิดเห็น • 23

  • @_SeanSmart
    @_SeanSmart 5 ปีที่แล้ว

    Nice Demonstration!! Keep Them Coming

  • @frankiefrank4853
    @frankiefrank4853 3 ปีที่แล้ว

    Thanks man

  • @botl8179
    @botl8179 5 ปีที่แล้ว +3

    What’s that dollar sign thingy😂 1:25

  • @AZ762SHOOTER
    @AZ762SHOOTER 11 หลายเดือนก่อน

    I'm having a similar problem on a notifier nfw2-100. We have 3 fcps24s8 power supplies in slave. Still can't get it to sync up. Everything is set to system sensor, there's also the eol resistor in place. Could it be the only a simple jumper causing it?

    • @TheFirePanel
      @TheFirePanel  9 หลายเดือนก่อน

      Sorry I didn’t see this when you originally commented. Did you ever find the solution? I’d have to see pictures of the setup to get some insight

    • @AZ762SHOOTER
      @AZ762SHOOTER 9 หลายเดือนก่อน

      @@TheFirePanel I did. Turns out a contractor got in the program and changed a few things when they added some devices. Also the panel was looking for a control module when they added a relay module for a big ass fan in the warehouse. FACP had a few problems because of them. A simple auto program and a quick change in the programming for the NAC clears it right up. Now our engineering department wants to add more devices to the system. Looking forward to fixing what the next contractor messes up.

  • @FireTech7
    @FireTech7 5 ปีที่แล้ว

    Where is this at?

  • @shaynewaite5329
    @shaynewaite5329 5 ปีที่แล้ว

    there’s no cables going into the onboard dialler

  • @bob5074
    @bob5074 5 ปีที่แล้ว +2

    To properly supervise the FCPS-24S6 you should run one side of your end of line resistor up through the common and normally closed of the aux relay TB5.

    • @BackyardWeightlifting
      @BackyardWeightlifting ปีที่แล้ว

      Alternatively, set a monitor module to monitor that same set of contacts. As long as your system has enough addresses left of course, but for sure I've had it with trying to look for power supplies in obscure closets that no one aware of.

  • @brianthetowerguy979
    @brianthetowerguy979 4 ปีที่แล้ว

    Fire department will not allow auto silence ? Per the international fire code can't sound over 1 hour. That is why the panels max sounding time is 1 hour in the auto silence feature

  • @FireAlert
    @FireAlert 5 ปีที่แล้ว

    cool i have one of those Power Supply's!

  • @ElectronicsHikingandJesusTalk
    @ElectronicsHikingandJesusTalk 5 ปีที่แล้ว

    Nice! That was a cool demo!

  • @alarmandsirenguy
    @alarmandsirenguy 5 ปีที่แล้ว

    Awesome Video

  • @evanbart4109
    @evanbart4109 5 ปีที่แล้ว

    Great video 😀👍👍

  • @christopherbluhm
    @christopherbluhm 5 ปีที่แล้ว

    Why would you put the system on test when nothing is connected to the dialers?

    • @christopherbluhm
      @christopherbluhm 5 ปีที่แล้ว

      Zachary Fleck AES wireless?

    • @christopherbluhm
      @christopherbluhm 5 ปีที่แล้ว

      Zachary Fleck Oh. Okay.

    • @vrryan6
      @vrryan6 3 ปีที่แล้ว

      relay probably

    • @joeycaridi3030
      @joeycaridi3030 2 ปีที่แล้ว

      @@christopherbluhm ​The dialer is built in into the control panel's circuit board as Fire-Lite panels have the dialer built in into the panel that can be programmed through the panel's programming and have the dialer connected to the monitoring company's wireless device

  • @BousaiGuy
    @BousaiGuy 5 ปีที่แล้ว

    Did you happen to mean _turning on_ audible silence? I liked the demo!