Differential Pressure Transmitter wiring setup and communication by HART 475 (Rosemount 3051)

แชร์
ฝัง
  • เผยแพร่เมื่อ 5 ต.ค. 2024
  • Instrumentation: This short video is to show how to connect the Differential Pressure Transmitter to power supply, multi-meter and HART communicator 475.

ความคิดเห็น • 37

  • @jonathanaldovino3869
    @jonathanaldovino3869 3 ปีที่แล้ว +1

    Boss more videos please. I Always watching your videos. Its very useful and educational. 100%

    • @armaiboi
      @armaiboi  3 ปีที่แล้ว

      okay boss pag may opportunity makakuha ng video. Thanks for watching boss

  • @niloyu105
    @niloyu105 3 ปีที่แล้ว +1

    Watching here Al Khafji Saudi Arabia from Philippines

    • @armaiboi
      @armaiboi  3 ปีที่แล้ว

      Thanks kabayan

    • @niloyu105
      @niloyu105 3 ปีที่แล้ว +1

      Nakuuu Kabayan sinabi kona eh? Boses palang... Kabayan may inaaplayan ako Ngayon DITO sa Saudi pinapa research SAKIN yang HART papano gumamit Ang Company Gas Detector ION Science Ang instrument na gina-gamit install nila.? Baka puwede maka hingi, tulong idea about pag gamit ng HART? At ano posiblidad na puwede ma encounter? Salamat advance Kabayan... Location mo Nilo Mustacho Yu ang messenger ko Kabayan...

    • @armaiboi
      @armaiboi  3 ปีที่แล้ว

      kabayan, kahit anong instrument pa yan basta HART capable halos pareho lang ang principle sa pag gamit nyan. meron din sa manual ng mismong instrument kung paano e navigate ang menu. basta makikta mo lang sa HART communicator ang menu and submenus. kung meron kang specific na Maker sa instrument na gamit nila try natin e download ang manual sa online para matignan natin.

  • @yagoubbouzned7397
    @yagoubbouzned7397 ปีที่แล้ว

    thank you my friend . for explication me from ALGERIA . and you ?

  • @InstrumentCalibration
    @InstrumentCalibration 2 ปีที่แล้ว +1

    Great video

    • @armaiboi
      @armaiboi  ปีที่แล้ว +1

      thanks for watching

  • @dispositivosautomatizados
    @dispositivosautomatizados 2 ปีที่แล้ว

    ❤❤❤❤❤❤❤❤❤❤ apaixonado por automação ❤ 🇧🇷🇧🇷🇧🇷

  • @balamurugansr5928
    @balamurugansr5928 ปีที่แล้ว +1

    Can you explain back to the panel smart tx (24v dc) , how to connect series and what type resistance using?

    • @armaiboi
      @armaiboi  ปีที่แล้ว

      brother, that is a loop resistance purposely for HART communication. typically the value is 230 ohms or 250 ohms. that is in series to your power supply. typical a carbon type resistor

  • @CalmTom
    @CalmTom 5 หลายเดือนก่อน

    one probe from the multimeter is connected to "Test" and the secon? To + or - ?

  • @abychasperindie5979
    @abychasperindie5979 3 ปีที่แล้ว +1

    Its amazing

  • @rnztraxxazz4943
    @rnztraxxazz4943 3 ปีที่แล้ว +1

    Aaah okkk keep it up 👍🔥

  • @amieacul_2492
    @amieacul_2492 3 ปีที่แล้ว +1

    what is the fitting use

  • @hamzahnasirudin8036
    @hamzahnasirudin8036 3 ปีที่แล้ว +2

    Sir how if my transmittrr measured LRV and URV good at 4.00 mA amd 20mA but at 50%,75%,25% value its not linear.. i mean when ot should be 12mA it shows 11,45 mA... i've did zero trim,d/a trim,and scaled like what u did.. but ist still shows the same thing..

    • @armaiboi
      @armaiboi  3 ปีที่แล้ว

      thank you for watching the video bro. With regards to your concern, can you share the result of your 5-point calibration verification? Moreover, is your transmitter a new one or in service? what type of transmitter is it?

    • @hamzahnasirudin8036
      @hamzahnasirudin8036 3 ปีที่แล้ว

      @@armaiboi 4 ma= 0 bar ma up= 3.99
      8 ma = bar 0.15 ma up= 7.76
      12 ma bar 0.31 ma up= 11.97
      16 ma = bar 0.46 ma up= 15.34
      20 ma = 0.62 ma up= 19.98
      Dp transmitter rosemount 3501

    • @armaiboi
      @armaiboi  3 ปีที่แล้ว +1

      there are several factors that caused of linearity error. Like if there is trapped water inside the transmitter capsule. This water is due to wet impulse lines. So, purge the water first prior to check the calibration. I observed some transmitters especially the low range, the LRV and URV have changed slightly. Check the LRV and URV. Another factor is the reliability of the reference gauge, check zero drift. I suggest use the unit of mbar instead of bar to make your reference more accurate.

    • @hamzahnasirudin8036
      @hamzahnasirudin8036 3 ปีที่แล้ว

      @@armaiboi okeee thankyou sir

  • @noelfaithfulkari2857
    @noelfaithfulkari2857 2 ปีที่แล้ว +1

    Thanks alot

    • @armaiboi
      @armaiboi  2 ปีที่แล้ว

      you're welcome. thanks for watching..

    • @noelfaithfulkari2857
      @noelfaithfulkari2857 2 ปีที่แล้ว +1

      @@armaiboi could you do videos for valve's

    • @armaiboi
      @armaiboi  2 ปีที่แล้ว +1

      Yes, i will, once i'll get the chance to be back in the field.

  • @meetpriya2812
    @meetpriya2812 3 ปีที่แล้ว

    Thanks bro

  • @praful7789
    @praful7789 3 ปีที่แล้ว

    good job

  • @armandobanda5198
    @armandobanda5198 3 ปีที่แล้ว +1

    En español no podrian tranmitir un video de calibracion o configuracion

    • @armaiboi
      @armaiboi  3 ปีที่แล้ว

      Gracias for watching amego. Though I couldn't fully understand your comment and have tried to go to google translate😊

  • @Cak_Karim
    @Cak_Karim 3 ปีที่แล้ว

    👍👍

  • @akemiasuhara2986
    @akemiasuhara2986 2 ปีที่แล้ว

    Hye, can you help me how to connect hart to digital pressure gauge... I want to change from analog system to digital system in hydraulic process..

    • @armaiboi
      @armaiboi  2 ปีที่แล้ว

      hello. is your digital pressure gauge hart capable?

  • @neyaz1
    @neyaz1 3 ปีที่แล้ว

    how to install DD file in 475 communicator

  • @kantopashi
    @kantopashi ปีที่แล้ว

    ok

  • @oceannamarie1474
    @oceannamarie1474 2 ปีที่แล้ว

    l

  • @pinoycalibrationmaster
    @pinoycalibrationmaster ปีที่แล้ว +1

    Salamat sa tutorial video mo, new subscriber here padalaw din po saking tyanel salamat po

    • @armaiboi
      @armaiboi  ปีที่แล้ว

      done kabayan