Nicely explained, Local electricians (wiremen) cries. Earthing, Double Neutral they have made mess. One neutral for all equipments. One UPS Phase output only. No separate wiring for Light Heavy (geyser, heater). No Earth wiring....even.
thanks very much for sharing your knowledge and experience sir, now a days i am continuously start to watch all ur videos sir, may god bless u happy and long life sir.
Good Job Sir Make Same video, *Sir Energy Meter Se Lekar Ghar Ke Laod Ke Bich Me Hum RCCB, MCB, ISOLATOR Ka Kya Sequence Hona Chahiye Is Par Ek Detail Video Banao*
Sir ups ke out put pe mcb (6amp)trip nahi hota jab hum short dete he lekin jab power aati he us waqt hum ups ke output pe short dete he to mcb 6amp trip hota he esa kiyon?sir i am waiting for your answer ?
Sir 3fase line + rccb + UPS inverter k connection btaya Isme mene Kiya thaa bt rccb bar2 trip ho jati h fir alag wiring krni padi aisa batay aap jisse iske andr hi wiring ho jay
सर आपको शिवरात्रि की बहुत-बहुत शुभकामनाएं. सर मेन सप्लाई और यूपीएस सप्लाई दोनों के लिए क्या एक 4 pole आरसीसीबी इस्तेमाल कर सकते हैं मेन सप्लाई और इनवर्टर सप्लाई में न्यूट्रल कॉमन है ??
Audio amplifier pam8403 me usb port lga kr power bank ka use na kakre Mobile charger se chla skte hai.. 5v 1m charger se.... mobile charger se chl jayega.. input, output k liye please reply
Thank you sir for sharing this information and please give me reply for the following, *The grid side main rccb is in off state or the neutral and grid power is in open state whther the inverter rccb will work or not? *i have been installed rccb protection in inverter as per your connection, but i have facing the above mentioned issue. *As per this connection the inverter rccb will works perfectly if the grid rccb and grid isolator is in ON condition.
For UPS out rccb to work, a current path through earth should complete due to leakage between line and earth due to some reason. But it depeds upon design of ups. In your case rccb of Ups output does not work if incomer is open. Then this should not be considered the problem. UPS might have been designed for no leakage current or very less leakage current path {similer to floating system}. There may be many ways to design some equipments. Actual reason can be find out by stuty of the diagram of equipment. However circuit diagram are not available for all the equipments.
@@GKAgrawal2 thank you sir for your quick and prompt reply... *shall i continue with this connection? i think this is not an big issue, am i right sir?
Is condition me grid ka rccb cut ho jata hai.... jab incomer chala jayega tab us condition me ups ke bad wali rccb trip hogi ....try karke dekh lijiye ...main dekh chuka hu karke ..ups ki rccb incomer n hone par kam karta hai...agar grid aa raha hai aur ups grid ko bypass kar raha h to us time grid wali rccb agar trip ho gaya to inverter ki line chalu ho jayegi ...aur jab tak phli rccb on nhi karoge to tab tak dusri nhi off hogi
Sir first me agar me 32Amp Mcb or Rccb laga liye uske bad ups k output me bi 32amp MCb or Rccb lagana padega Ya pper jitna mere light fan ka watt ha utna lagana padeka plz reply
@@prasenjitdebnath5466 haan, electrician ne neutral same hi rakha hai, servo laga hai uske bad inverter aur fir load. Jab mains rehta hai to inverter se bypass hokar connection rehta hai to usko neutral dena hoga aur fir inverter par jab load rehta hai to wo single wire wala hi kiya hua hai. Ab seperate kahan kare, thoda confusing part hai neutral seperate karna. Thoda iska bataye.
Sir what is the benefit of splitting 2MCBs for heavy and light loads? Why can't we use the same method with higher rated eg. 40A MCB--> 40A RCCB--> then split for heavy load and another wire for UPS inverter -->mcb--> rccb--> light loads.
Hello Namaskar Agarwal ji, I want to install Rccb (30ma) for safety reasons at my home but I m not able to do as my leakage current (overall from main grounding wire) is around 50-100ma . This keeps on increasing if I switch on geyzer (water heater) (by additional 100ma). How do I reduce this overall leakage current to less than 15ma Regards Hitesh
Sir , whenever lightening strikes somewhere near the inverter in our home gets damaged. If i connect a m.c.b to the input of the inverter, will it then protect the inverter from electric surges caused by lightening strike?
Sir, the rating of alternator is given in kVA, but in hydroelectric stations capacity rated in kw or in Mw where the 3 phase AC is generated by the alternator, why? Please clarify.
If only one wire is connected at the output of ups, then the rccb cab cannot be connected. You must connect 2 wires at the output of ups to make rccb work. In such case, you can connect rccb at the load side, which has 2 wires.
Lekin sir, inverter ki safety instructions mai ku lika hota hai ki " Kindly ensure that ELCB/RCCB is not connected at either input or output in inverter? Pls answer.
I have a problem with a similar connection in my 3 phase wiring. When ELCB is introduced, the main ELCB does not get on. I think it is a problem with double neutral. How can I resolve this issue?.
Sir... Luminous 3.5 kva model me piche 4 cable nikalta hain input-output k lie. 1 phase output huta hain. Aur Input k lie 3 cable... Phase, Neutral, Earthing. So RCCB / RCBO me Neutral kaha se le jai... ?? plZ help.
But sir es video mei jo aapne UPS ka connection show Kiya hai, isme sabhi light & fan points inverter se connect ho gaya hai, but generally hum kuch points ko hi inverter ka connection dete hai and baki sab ko main line ke phase se connected rakhte hai. And also most of cases mei inverter se single phase wire nikalti hai & neutral comman hoti hai (inverter output plug se neutral wire nahi nikalte hai). Sir please tell how to do RCCB connection with inverter in that case ?
Sahi kaha, 1 wire hota hai but yeh galat tarika hai. Mainey apne ghar mey dono wire lagvaye hai. Mainey wiring se pahiley hi electrician ko bataya ki 2 wire lagana hai. Agar 1 hi lagao ge then, mujhe tumse kaam nahi karana. Dono wire lagane chahiye. Heater load etc inverter se nahi lagata, yeh video me explain kiya hai.
@@GKAgrawal2 But sir kya aapke tarike se connection karne par sabhi fans, lightbulbs & small socket ke points inverter se connect nahi ho jaege? Agar hame sirf kuch hi points ko inverter par chalana ho tab uss case mei kaise connection kare inverter ka with RCCB ? Only this is main confusion for me & many other people.
नमस्कार सरजी वायरीग पहले से किया हुआ है अन्दर ग्राउण्ड उसमे आरसीसीबी लगाना है और इनभटर मेन बोड से नही देकर बीच मे तीसरे रुम से देना है घर का सभी लोड तो कितनी आरसीसीबी लगाए एक या दो और कहाँ पर लगाए जीसमे बोड का इण्डीकेटर लाइट पर रहेगा
@@GKAgrawal2 जी सर आपने जो बताया है वैसे वायरिंग करने पर ही आरसीसीबी काम करेगा लेकिन हमें इनवर्टर प्वाइंट के लिए अलग से neutral देना होगा जिससे वायर एक्स्ट्रा लगेगा
Watch UPS inverter, RCCB MCB connection for the home.
Also, join channel at Membership th-cam.com/channels/O31rZS4_EDYJ8CGXiRZdxg.htmljoin
bahut hi asan bhasha me bahut asan tarika se apne bahut badhiya samjhaye....❤❤
🎉🎉🎉🎉 thanks sir ji ...bohot Acha samajhaya apne
आपके समझाने का तरीका को जबरदस्त है सर 🙏❤️
aap ko meraa baar bar Namskar sir ji🇮🇳🇮🇳🙏🙏🙏🙏🙏🙏🙏🙏🙏🙏
Aapka samjhane ka tarika aur digram best hi thanks you sir uploading video for this topic
Nicely explained,
Local electricians (wiremen) cries.
Earthing, Double Neutral they have made mess.
One neutral for all equipments.
One UPS Phase output only.
No separate wiring for Light Heavy (geyser, heater).
No Earth wiring....even.
Nicely explained
Simple and superb instructions
Thank you
Sir your videos are very knowledgeable and useful. Thank you
Very useful information sir ji
you are great sir ji
धन्यवाद 🙏🙏
Thankyou sir nicely explained
Very good knowledge
अप्रतीम बहुत अच्छा और अलग
Great Sir ,🙏🙏
Nice n informative video sir.
Excellent 👌
You Are Brilliant Sir
Thank you sir. very nicely explained.
Great video sir! Thank you.
Very clear explanation is given.
Thanks for the comment.
Very simple trick
Thank you Sir for making this very simple.
Thanks chacha
Thanks dada ji
Good.
Naaaamaaaskaar.... 🙏
Inkamar hai ghar ka
Ghodu
excellent sir
thanks very much for sharing your knowledge and experience sir, now a days i am continuously start to watch all ur videos sir, may god bless u happy and long life sir.
Sir thank you...
Please sir make videos on digital electronics...
Thanku
Good
Sir, please, discuss elaborately on SPD for home.
Good Job Sir Make Same video,
*Sir Energy Meter Se Lekar Ghar Ke Laod Ke Bich Me Hum RCCB, MCB, ISOLATOR Ka Kya Sequence Hona Chahiye Is Par Ek Detail Video Banao*
❤😮 good sir
Thanks for making informative video. I had asked you about this in past.
Sir ups ke out put pe mcb (6amp)trip nahi hota jab hum short dete he lekin jab power aati he us waqt hum ups ke output pe short dete he to mcb 6amp trip hota he esa kiyon?sir i am waiting for your answer ?
Thank you sir
Very impressive sir., But there are some other methods also.
Sir Rccb single phase k bhe aate hain kya plz describe.thanks
Good chacha
Sir three phase mein rccb connection kaise krein please ek video is par bhi banaye thank u
Thanks sir 👌👌👌
Three phase rccb bhi to use Kar sakte hai. R me line ka, Yme UPS ka, Y me power load ka connection Kar sakte hei and tinoka neutral common hota.
No
Doing great! I also post electronics explanation videos
Thanks sir
Sir agar kolar yaa ac ferg chalane ho to ups se thodi chalegi vo to darekt chalegi
3KVA Stabilizer MCB & RCCB ke bich v connection bataye sir❓
@GKAgrawal2 But inverter uses a common neutral, inverters are wired to provide a single wire ( phase only) as the output
You can connect separate wire. In my house I connected separate N wire for input and output.
Sir 3fase line + rccb + UPS inverter k connection btaya
Isme mene Kiya thaa bt rccb bar2 trip ho jati h fir alag wiring krni padi aisa batay aap jisse iske andr hi wiring ho jay
Janab hum ups ki out put p single pole mcb aur rcd conect kr skty hain rcd work kryga single pole mcb k sath.
Yes. Line will be through MCB and Neutral will be direct from Mains to RCCB.
Thanks for your video.
I have one question. Before UPS and after UPS the RCCB and MCB current rating value will be same or differ.
youll be better of having RCCB and MCB after UPS if everything get supplied from UPS
सर आपको शिवरात्रि की बहुत-बहुत शुभकामनाएं. सर मेन सप्लाई और यूपीएस सप्लाई दोनों के लिए क्या एक 4 pole आरसीसीबी इस्तेमाल कर सकते हैं मेन सप्लाई और इनवर्टर सप्लाई में न्यूट्रल कॉमन है ??
Very nice video sir,
Sir agar ham sirf rccb lagaye aur mcb na lagaye to kya hoga
Line aur neutral key beech short hone per protection nahi milegaa.
@@GKAgrawal2sir RCCB short circuit me kam nahi karta ?
Mera video MCB RCCB difference dekho
Audio amplifier pam8403 me usb port lga kr power bank ka use na kakre Mobile charger se chla skte hai.. 5v 1m charger se.... mobile charger se chl jayega.. input, output k liye please reply
Tnx sir
Nice information sir. But my question is in normal tecnitians for inverter they give only phase wire, for neutral they took common already installed.
At the output of my home UPS, all yhe 3 points earth neutral and phase are there. May be , some cheap type may give only phade as you said.
Kya hum ups output me RCCB ki jageh DP MCB laga sakte h?
MCB , RCCB kaa Kam nahi karta hai.
House wiring ka vdo bano geser or heater ke connection aur ups bypass wiring ke sath agar ups faulty ho jata hai to practical
7:57 sir 2 q lgane the 1 m kam sahi s chal rha jab? aise to kafi sari mcb lgengi to kya har mcb k aage ak separate rccb denge?
Thank you sir for sharing this information and please give me reply for the following,
*The grid side main rccb is in off state or the neutral and grid power is in open state whther the inverter rccb will work or not?
*i have been installed rccb protection in inverter as per your connection, but i have facing the above mentioned issue.
*As per this connection the inverter rccb will works perfectly if the grid rccb and grid isolator is in ON condition.
For UPS out rccb to work, a current path through earth should complete due to leakage between line and earth due to some reason. But it depeds upon design of ups.
In your case rccb of Ups output does not work if incomer is open. Then this should not be considered the problem. UPS might have been designed for no leakage current or very less leakage current path {similer to floating system}.
There may be many ways to design some equipments. Actual reason can be find out by stuty of the diagram of equipment. However circuit diagram are not available for all the equipments.
@@GKAgrawal2 thank you sir for your quick and prompt reply...
*shall i continue with this connection?
i think this is not an big issue, am i right sir?
Hello Sir inverter me DC current hota h to usme rccb kya kaam krega agar DC RCCB hota h to please uska name btaye
Bijuli se inverter bosne ke liye kiya logana porta hai sir....
07:50 sir kanjusi kaisi yhan to 1 hi lgega. or inverter ki output m dusra.
Is condition me grid ka rccb cut ho jata hai.... jab incomer chala jayega tab us condition me ups ke bad wali rccb trip hogi ....try karke dekh lijiye ...main dekh chuka hu karke ..ups ki rccb incomer n hone par kam karta hai...agar grid aa raha hai aur ups grid ko bypass kar raha h to us time grid wali rccb agar trip ho gaya to inverter ki line chalu ho jayegi ...aur jab tak phli rccb on nhi karoge to tab tak dusri nhi off hogi
Sir first me agar me 32Amp Mcb or Rccb laga liye uske bad ups k output me bi 32amp MCb or Rccb lagana padega
Ya pper jitna mere light fan ka watt ha utna lagana padeka plz reply
no.. ups ke baad vala 32a ka lagane ki jarurt nai. agar ups ki supply 3 bed rooms se he to 16amp ka kafi hai.
Sir normally home inverter ka input and output neutral are common
haan aaj connection kiya aur yeh condition thi rccb connection main, sari combination try ki but rccb trip hi ho rahi thi inverter par.
@@nitinkumar29 muja lagta ha up na rccb ka input neutral and output neutral suprat nahe keya ha
@@prasenjitdebnath5466 haan, electrician ne neutral same hi rakha hai, servo laga hai uske bad inverter aur fir load. Jab mains rehta hai to inverter se bypass hokar connection rehta hai to usko neutral dena hoga aur fir inverter par jab load rehta hai to wo single wire wala hi kiya hua hai. Ab seperate kahan kare, thoda confusing part hai neutral seperate karna. Thoda iska bataye.
Jo rccb sa neutral Loga input or output ka leya oh rccb ka output sa lo rccb ka input sa kucve motlo
Sir what is the benefit of splitting 2MCBs for heavy and light loads? Why can't we use the same method with higher rated eg. 40A MCB--> 40A RCCB--> then split for heavy load and another wire for UPS inverter -->mcb--> rccb--> light loads.
Hello Namaskar Agarwal ji, I want to install Rccb (30ma) for safety reasons at my home but I m not able to do as my leakage current (overall from main grounding wire) is around 50-100ma . This keeps on increasing if I switch on geyzer (water heater) (by additional 100ma).
How do I reduce this overall leakage current to less than 15ma
Regards Hitesh
Hello Sir agar solar usu karege to conection me koi change hoga kya
Sir , whenever lightening strikes somewhere near the inverter in our home gets damaged. If i connect a m.c.b to the input of the inverter, will it then protect the inverter from electric surges caused by lightening strike?
Watch my video on MOV varistor. MCB does not provide protection from lightning impulse.
नमस्कार🙏🙏🙏
Sir, the rating of alternator is given in kVA, but in hydroelectric stations capacity rated in kw or in Mw where the 3 phase AC is generated by the alternator, why? Please clarify.
Please upload a video on automatic voltage regulators.
Sir mare office ma ups cneckting karna hai sytem or preter
If we use RCCB why using mccb in ups out pot
Sir i have a question invertor output has a single wire phase how we can connect rccb pls help.
If only one wire is connected at the output of ups, then the rccb cab cannot be connected.
You must connect 2 wires at the output of ups to make rccb work.
In such case, you can connect rccb at the load side, which has 2 wires.
Lekin sir, inverter ki safety instructions mai ku lika hota hai ki " Kindly ensure that ELCB/RCCB is not connected at either input or output in inverter? Pls answer.
I have a problem with a similar connection in my 3 phase wiring. When ELCB is introduced, the main ELCB does not get on. I think it is a problem with double neutral. How can I resolve this issue?.
you seend to draw and show how is your connection is done.
सर rccb के स्विच साइड में फेज वायर जोड़े या न्यूट्रल वायर बताइये।।
Mera video MCB input output connection dekho.
@@GKAgrawal2 जी सर
Sir... Luminous 3.5 kva model me piche 4 cable nikalta hain input-output k lie. 1 phase output huta hain. Aur Input k lie 3 cable... Phase, Neutral, Earthing.
So RCCB / RCBO me Neutral kaha se le jai... ?? plZ help.
Sir train se related interview questions pr videos bnaye
Sir jis case me ups ke output se neutral nhi lete us case me kya kare?
Sir ji, electric welding machanism kya hota he. is per ek detailed video banaye
Thanks
Local electrician cries 😭
Single wire invertor connection me kya karen
Sir solar off-grid inverter k liye connection diagram bhi bataye.
Sir please tell us how to calculate current carrying capacity of acsr 50mm2 on 11 kv side and 33 kv side.
Ek rccb ka parice aapko pata hai sirf ek rccb lagta baaki singal pol mcb lagana chahiye srkit waire ke liye
How to conncet RCCB for UPS with only power out and no nuetral terminal (Luminous Cruze)?
But sir es video mei jo aapne UPS ka connection show Kiya hai, isme sabhi light & fan points inverter se connect ho gaya hai, but generally hum kuch points ko hi inverter ka connection dete hai and baki sab ko main line ke phase se connected rakhte hai. And also most of cases mei inverter se single phase wire nikalti hai & neutral comman hoti hai (inverter output plug se neutral wire nahi nikalte hai).
Sir please tell how to do RCCB connection with inverter in that case ?
Sahi kaha, 1 wire hota hai but yeh galat tarika hai. Mainey apne ghar mey dono wire lagvaye hai. Mainey wiring se pahiley hi electrician ko bataya ki 2 wire lagana hai. Agar 1 hi lagao ge then, mujhe tumse kaam nahi karana.
Dono wire lagane chahiye.
Heater load etc inverter se nahi lagata, yeh video me explain kiya hai.
@@GKAgrawal2 But sir kya aapke tarike se connection karne par sabhi fans, lightbulbs & small socket ke points inverter se connect nahi ho jaege? Agar hame sirf kuch hi points ko inverter par chalana ho tab uss case mei kaise connection kare inverter ka with RCCB ?
Only this is main confusion for me & many other people.
Very good question
Please answer sir
Kuch hi poknts chalana hai tho wiring change karani padegi, ya khub sare wires open idhar udhar dekhenge.
3 rcb (3floor)sa 1 inveter connection kaisa karoga
Sir main ne UPS ke pahle or AC supply ke baad rccb lagaya hain to rccb trip ho rahi hain Kya problem honga
Ghar me 1rccb se single wire inverter connection kaise Kare single wire se load chalega
Inverter rccb kaise lagai jaati hai out put in face wire
नमस्कार सरजी वायरीग पहले से किया हुआ है अन्दर ग्राउण्ड उसमे आरसीसीबी लगाना है और इनभटर मेन बोड से नही देकर बीच मे तीसरे रुम से देना है घर का सभी लोड तो कितनी आरसीसीबी लगाए एक या दो और कहाँ पर लगाए जीसमे बोड का इण्डीकेटर लाइट पर रहेगा
Sir what is GAIN in Transistor and in opamp please please please answer thise question😭😭😭
एक घर मे दो रूम में दो इन्वर्टर लगे हो तो दोनों के लिए दो rccb लगाने पड़ेंगे क्या
दोनो जगह लगाना अधिक safe है ।
गुरुजी, आगर आप UPS खोल के देखेंगे तो अंदर neutral शॉर्ट हि होता है !
Yes, मगर आप वायरिंग वैसी करिए जैसे मैंने कहा आरसीसीबी काम करेगा
@@GKAgrawal2 जी सर आपने जो बताया है वैसे वायरिंग करने पर ही आरसीसीबी काम करेगा
लेकिन हमें इनवर्टर प्वाइंट के लिए अलग से neutral देना होगा जिससे वायर एक्स्ट्रा लगेगा