Hello Sir. I really love the tutorial an made one on my own. However I get this message 'function refused by CPU'. I tried digging up and found that I need to turn off the OPTIMIZED ACCESS BLOCK, ACCESS LEVEL should be FULL and DB should be GLOBAL which I did. But I still get the same error. Is there any firmware version that needs to be followed? Thanks in advance. :) :)
Hi!, thank you for the comment, and I'm sorry to read that not work, I'm not sure if firmware version could be the problem, but I will check, did you enable the "PUT/GET communication" 26:58, regards
@@RodolfoTiburcio had to reboot the PLC. Finally got the output I needed. Anyways, this tutorial is very helpful. Hopefully you can upload a few more videos😊😊😊
Excelente Ejemplo. Funciona Muy Bien Con Un PLC Fisico. Muchas Gracias.
Hello sir.. what this is will be same if I use S7-300 PLC ?
hello sir. how can i import Snap7 for Visual Studio?, tks
Hello Sir. I really love the tutorial an made one on my own. However I get this message 'function refused by CPU'. I tried digging up and found that I need to turn off the OPTIMIZED ACCESS BLOCK, ACCESS LEVEL should be FULL and DB should be GLOBAL which I did. But I still get the same error. Is there any firmware version that needs to be followed? Thanks in advance. :) :)
Hi!, thank you for the comment, and I'm sorry to read that not work, I'm not sure if firmware version could be the problem, but I will check, did you enable the "PUT/GET communication" 26:58, regards
@@RodolfoTiburcio had to reboot the PLC. Finally got the output I needed. Anyways, this tutorial is very helpful. Hopefully you can upload a few more videos😊😊😊