ON/OFF MODE OF PID UT35A OF YOKOGAWA

แชร์
ฝัง
  • เผยแพร่เมื่อ 11 ม.ค. 2025

ความคิดเห็น •

  • @rajasekhar-po5hs
    @rajasekhar-po5hs 4 หลายเดือนก่อน

    U r video 's more help me sir. Tq

  • @mdkhokonahamed1686
    @mdkhokonahamed1686 3 หลายเดือนก่อน +1

    Hi sir pressure sensor relation vedeo &cilbetion vedeo tutorial upload- yokogawa-ut55a

    • @ultimatesolution9935
      @ultimatesolution9935  3 หลายเดือนก่อน +1

      Hello dost
      Really UT55 not available.Really in my plant UT35A, selec PID 330, Yudian, and of radix has been used. But don't, worry I am trying trying to make your video.Really I have indent the UT55 but availability of video depend will depend on availability of indented UT55A .
      But according user manual of UT55A it is not so far differences.
      Although I am trying to fulfill your requirement.
      Thanks

    • @mdkhokonahamed1686
      @mdkhokonahamed1686 3 หลายเดือนก่อน

      Yokogawa-ut35a

    • @ultimatesolution9935
      @ultimatesolution9935  3 หลายเดือนก่อน +1

      ​@@mdkhokonahamed1686
      To control pressure in PID
      Mode
      Please setting are below
      For pressure transmitter
      Range: -1 to 16
      4-20 ma
      Set
      CNT: PID
      Input section setting
      INPUT:4-20 ma
      RH: 20
      RL : 4
      SDP : 1
      SH : -10
      SL : 160
      Output
      ot : 2 ( analog output put)
      Here pressure is controlled by using out like control valve or other like vfd etc.
      How we enter in programming there a video
      "Parameter setting for pressure, temperature level in PID mode. Please see that
      Note: Same parameter are for UT55A PID controller.
      If there be need of help, please comment.

    • @mdkhokonahamed1686
      @mdkhokonahamed1686 3 หลายเดือนก่อน

      @@ultimatesolution9935 thanks sir i m very happy

    • @mdkhokonahamed1686
      @mdkhokonahamed1686 2 หลายเดือนก่อน

      Sir Yokogawa-UT55A Controller was like a little graphics, a little graphics was more than a setting, the graphics and SSR Output Up Speed Graphics and SSR Voltiz has no settings

  • @rajasekhar-po5hs
    @rajasekhar-po5hs 2 หลายเดือนก่อน

    Sir ut 32 a pid control input jp2 ( rtd) out put 4to 20 milliamps used to i/ p converter samson posinitor steam prv used my company pasturazer purpose. So pid set point 90.pv going 98,99,100, degrees going again down 85,84,83,up/down come how to adjusted proposanal, integrated. Derivatived value or how to calibraction samson posinitor pls video sir

    • @ultimatesolution9935
      @ultimatesolution9935  2 หลายเดือนก่อน

      For this you have decrease offset value.Take attempt by decreasing the Proportional value keeping I& D constant.During this change you can make derivative zero/off.
      What is the effect of this change please comment

  • @rajasekhar-po5hs
    @rajasekhar-po5hs 4 หลายเดือนก่อน

    Pid back side connection relay connection witch one terminal given sir

    • @ultimatesolution9935
      @ultimatesolution9935  4 หลายเดือนก่อน

      Have you need of connections details???

    • @rajasekhar-po5hs
      @rajasekhar-po5hs 4 หลายเดือนก่อน

      Yes sir. My plant is the same pid available. U r video 's total i'am seeing good sir. ot 0.03 voltage select. Hys 0.2 na but witch common number & witch wire no pls tell me sir

    • @rajasekhar-po5hs
      @rajasekhar-po5hs 4 หลายเดือนก่อน

      207.208 4 to 20 milli amps out put. I think u r connect relay connected 103 common 102 NO correct na

    • @ultimatesolution9935
      @ultimatesolution9935  4 หลายเดือนก่อน

      Really in this video, operating mode(CNT) is ON/OFF mode and out put is selected Relay output (ot=0.03)
      Hys is used for ON below set point and off above set point.103 is common and 102 NO,and 101 is NC as you said. New video will be uploaded in 1-2 days which make you clear more.

    • @rajasekhar-po5hs
      @rajasekhar-po5hs 4 หลายเดือนก่อน

      Tq correct tq.for replay sir👍