Hola buenos días, soy estudiante de medgas, y trabajo en un shop , mi pregunta es porque estoy batallando tanto para ensamblar las “t” que puedo hacer para hacerlo más rápido sin contaminarlos?
Good question, waste gas is a vacuum9 and not a supply or cylinder based. It is a special pump that is frequently found in the CUP- central utility plant.
@@mikecanales3905 the WAGD could be tied into the vacuum pump, provided the dedicated WAGD piping ties into the vacuum piping 5' from the inlets. Assuming N2O is being used in a Category 1 space, and used as an anesthetic.
@@edwardmcbrearty5712 yes, all true. You are talking at an ASSE 6030 level. This is a 100 level intro class. In regards to the micro bulk/in house reserve, drawing is more illustrative than design compliant. Point well taken. Thanks.
Hola buenos días, soy estudiante de medgas, y trabajo en un shop , mi pregunta es porque estoy batallando tanto para ensamblar las “t” que puedo hacer para hacerlo más rápido sin contaminarlos?
Your diagram has N20, but no WAGD. Is this an oversight or is it code compliant. Like your micro bulk with an inhouse reserve?
Good question, waste gas is a vacuum9 and not a supply or cylinder based. It is a special pump that is frequently found in the CUP- central utility plant.
@@mikecanales3905 the WAGD could be tied into the vacuum pump, provided the dedicated WAGD piping ties into the vacuum piping 5' from the inlets. Assuming N2O is being used in a Category 1 space, and used as an anesthetic.
@@edwardmcbrearty5712 yes, all true. You are talking at an ASSE 6030 level. This is a 100 level intro class. In regards to the micro bulk/in house reserve, drawing is more illustrative than design compliant. Point well taken. Thanks.
@@mikecanales3905 I appreciate the replies, Mike. Thank you. I thought I was losing my mind. And guilty, in regards to the 6030 mindset.