Cooling Tower Setpoint For Chiller

แชร์
ฝัง
  • เผยแพร่เมื่อ 28 ก.ย. 2024

ความคิดเห็น • 42

  • @HVACTIME
    @HVACTIME  4 หลายเดือนก่อน +1

    chilleracademy.com/p/intro-to-chillers
    Get support today.

  • @mikee2923
    @mikee2923 3 ปีที่แล้ว +6

    Excellent explanation. You’re on top of your game. I live in the rust belt and this sounds like a good idea up this way since our temperatures usually cool off at night. I don’t do much chiller work anymore and when I did it was usually in large retail stores that mostly had water cooled screw chillers. The issue I mainly had was getting them started in the morning when the tower water had cooled off overnight when the chiller had shut down. They usually had tower bypass valves that would recirculate condenser water until it warmed up then would start pushing the water out to the tower as it warmed. However they rarely worked because the energy management company didn’t understand how these chillers operated. They usually only installed the condenser water temperature sensor on the outlet of the condenser to the tower and controlled the bypass valve and tower fan off this one sensor. I fought with them for a couple years trying to explain to them why I had to make rounds on an almost daily basis resetting the chiller at multiple locations due to this. They didn’t want to hear they were wrong. As you could probably guess they would see a high temperature on the condenser loop from their 1 sensor, turn on the tower fan and close off the bypass valve and dump a lot of cold water into the condenser which would cause it to fail on oil pressure. At 1 location I experimented and switched their strap on sensor to the water inlet which somewhat improved things by at least sensing the cold water from the tower sump would turn the fan off and begin to recirculate water again until the loop temperature stabilized. Couldn’t convince them to add a sensor to the tower sump to control the fan and relocate the sensor as I did to control the bypass from that. So I just continued to do my daily route to reset the chillers until we eventually lost the contract. It was easy money while it lasted. I pass by one of the stores I used to take care of often and rarely see the cooling tower fans running on a 90 degree day. I guess they showed me👍

  • @sergiodjf
    @sergiodjf 2 ปีที่แล้ว +1

    Great explanation & visual animations!💯👏 For lift control, you should control both condenser water temperature & water flow. All chillers have min & max flow and you can adjust those parameters for peak performance.

  • @neilvestervictor180
    @neilvestervictor180 3 ปีที่แล้ว +1

    great information

  • @greghawkins7317
    @greghawkins7317 3 ปีที่แล้ว

    The York ymc2 chillers can run inverted. Had our 800ton ymc2 running with a 45 degree leaving chilled water temp and a 42 degree entering condensing water temp.

  • @espinozajc64
    @espinozajc64 3 ปีที่แล้ว

    Excellent 👍

  • @nakiapringley5391
    @nakiapringley5391 ปีที่แล้ว

    Great video!
    Can those rule of thumbs set points be used on other air cooled chillers?
    Please keep videos coming as I am just getting into centripetal chillers.

  • @joshstevens9826
    @joshstevens9826 2 ปีที่แล้ว +7

    The tower sp at 80-85° is a decent rule of thumb. The true answer is the manufacturer spec. The carrier 19xrv, under low load situations in mild weather, are looking for 60-65° condenser water. Also the york mc2 likes low condenser water temps. Know your equipment before making changes.

  • @thomascrane8130
    @thomascrane8130 10 หลายเดือนก่อน

    What temperature outside should we not run a chiller? If it is used for cooling only? And what temp of the return air should it be before cooling enabled please

  • @northface484
    @northface484 3 หลายเดือนก่อน

    Thank you...Can you tell me what surge sounds like...I run a 900 ton York Chiller....And when we have a low load the Chiller makes a steady groaning noise for minutes at a time...Is this considered surge...???

    • @HVACTIME
      @HVACTIME  3 หลายเดือนก่อน

      A surge will be a high-pitched squeal with a bit of a swoosh, a low-end grumbling sound is considered a stall. We get into these kind of topics in my introduction to chiller's course at chilleracademy.com, there's a community group in there once enrolled you'll have access to where we can discuss these things in detail. I also have a course dedicated to York's YK centrifugal

    • @northface484
      @northface484 3 หลายเดือนก่อน

      @@HVACTIME Thank you...!!!

  • @Noypihvac
    @Noypihvac 3 ปีที่แล้ว

    Did you able experience chiller use geothermal cooling system?

    • @HVACTIME
      @HVACTIME  3 ปีที่แล้ว

      No

    • @Noypihvac
      @Noypihvac 3 ปีที่แล้ว +1

      @@HVACTIME here in the cayman island most centrifugal chiller plant runs thru geothermal cooling. 78f condenser inlet water temp york yk chiller. Some exixting plant are also converting from cooling tower to geothermal system..

  • @Angelo-yj7bp
    @Angelo-yj7bp 3 หลายเดือนก่อน

    what happens if you set limits between 60 and 80 and you wet bulb is above 80 without adding the 5 degrees yet like it happens in south florida?

    • @HVACTIME
      @HVACTIME  3 หลายเดือนก่อน +1

      The maximum setpoint of 80f would be the maximum even when the temperature raises above 80f. Technically once you’re above 75f the setpoint stops increasing. The tower would keep its fans a maximum to try to keep up and maximize the water cooling at the high wet bulb.

  • @robertpeters9438
    @robertpeters9438 2 ปีที่แล้ว +1

    All the heat energy of the loop plus the power used by the chiller and tower must be rejected by the tower. The most efficient might be a giant coil, but completely impractical. So, we use enormous surface area in the droplets of a cooling tower to exchange heat with the added bonus of cooling from evaporation of part of the water. It is a tradeoff as to how big the pond or tower must be vs energy used in the spray and moving air through the field of the spray. Now, the chiller/compressor must raise the water temperature high enough that the water spray or waterfall can reject the total heat of the combined system. Many factors such as cost of electricity, cost of space for a pond, cost of maintenance on various system components all factor into the optimization of initial cost vs operational and maintenance costs.

  • @jarredallen
    @jarredallen 3 ปีที่แล้ว +2

    I have experienced many centrifugal chiller plant with fouled up condenser tube. I always advice my customers engineering and chiller plant operator to monitor condenser leaving temperature versus condenser saturation temperature. if the difference is greater than 10 fahrenheit, its time to punch the condenser tubes. and I also detest recycled water for cooling tower use.

    • @HVACTIME
      @HVACTIME  3 ปีที่แล้ว +1

      Approach will give you the most accurate/earliest determination of fouled tubes. And approach isnt as subjective to chiller load like differential is

  • @mwdub02
    @mwdub02 3 ปีที่แล้ว +2

    You’re the man!

  • @donsvideos1985
    @donsvideos1985 ปีที่แล้ว

    Thermal storage, how about 39deg f chillwater? Oh 134a gas

  • @olol3765
    @olol3765 ปีที่แล้ว

    20years ago received a new building and i tried to explain to engineer this issue he would admit, especially in GTA in April

  • @bobpetereson5177
    @bobpetereson5177 ปีที่แล้ว

    I'm curious as to what you would do if you had a York yk, and those OWT's are so high that you can't possibly have condenser water below 85 degrees. During the summer here in m.d., we commonly experience that with our yk's.. I'm not sure I've ever observed surging. (our cw setpoint is 44 degrees). I do however constantly see what appears to be surging in low load conditions this time of year in the morning. The chiller will be running around 24% and sound like a dying whale. I never see that hot gas bypass operate either. Very confused about this.

  • @billnipp2309
    @billnipp2309 ปีที่แล้ว

    60 degree tower water in the summer time??? good luck with that.

  • @alihatami4162
    @alihatami4162 ปีที่แล้ว

    In yk's we cant go under 7.5 barg condenser pressure because evaporator pressure drops and we must open hot gas.

  • @elderfarmstead
    @elderfarmstead 3 ปีที่แล้ว +1

    Great info! Thanks.

  • @ricardobmascardojr1608
    @ricardobmascardojr1608 2 ปีที่แล้ว

    What is the best or ideal energy efficient running 700tons York chiller. We have 3 700 tons chillers and 3 cooling towers but cold weather we only run one each, but hot weather two each. Thank you

  • @allanfolkes6019
    @allanfolkes6019 2 ปีที่แล้ว

    Because 80°c is like 26°c we have 2 York here so should the condenser water not cross 80 in C°/F°

  • @genegonzalez4713
    @genegonzalez4713 2 ปีที่แล้ว

    lift determines the actual work the chiller compressor is doing. the closer the approach the less energy consumption, and vice versa, remember that chiller efficiency is to produce a large amount of TR tons with the least amount of energy consumption

  • @santoscruz8
    @santoscruz8 10 หลายเดือนก่อน

    I want to say, thanks for your input and may God bless you and your families.

  • @hvac8826
    @hvac8826 4 หลายเดือนก่อน

    Worth information 🎉❤

  • @nakiapringley5391
    @nakiapringley5391 ปีที่แล้ว

    Great video brother 💯💯

  • @j.b9346
    @j.b9346 3 ปีที่แล้ว

    Thank you…great info

  • @stlbrian33
    @stlbrian33 2 ปีที่แล้ว

    Great video.

  • @simohvac9222
    @simohvac9222 3 ปีที่แล้ว

    very good info

  • @SoutheastHVAC
    @SoutheastHVAC 3 ปีที่แล้ว

    Thank you!

  • @allanfolkes6019
    @allanfolkes6019 2 ปีที่แล้ว

    Hi good day the temperatures your in reference to on this video is C° / F°