Over View of Transformer Relay Protection in 132/25 or 66/25 KV railway

แชร์
ฝัง
  • เผยแพร่เมื่อ 15 ก.ย. 2024
  • INK PLAYLIST : Railway Traction Substation
    www.youtube.co...
    About speaker: Atanu Biswas , Master of Engineering specialization in Power Electronics from IIEST Shibpur, Senior Section Engineeer Electrical ,Railway Electrification (RE)
    Differential Protection by Differentia Relay:
    Relay shall be of high speed type and operates in less than 0.04 s or 40ms
    Relay shall not operate at max through current fault
    and due to charging magnetization current
    Current setting 20% to 80%
    Adjustable bias setting at minimum operating current 20%,30% or 40%
    Depending upon tap changer
    This is connected through Inter tripping relay
    Earth leakage protection by Restricted Earth fault Relay :
    This is backup protection for internal earth fault
    It is very sensitive ,high speed realy
    It is provided separately on primary and secondary side
    Relay connected to separately mounted current transformer
    Relay is adjustable between 20-40% of 5Amp in eual step of 5%
    Of T10 Class , Operating time not exceeding 10ms
    This is connected through Inter tripping relay
    It is also a single pole non directional over current relay
    It works on IDMT(Inverse definite time lag) characteristics
    Primary and secondary side have separate Overcurrent IDMT relay
    There is a separate Instantaneous over current relay of T10 class
    Other protective devices
    Low oil level alarm
    Buchholz relay with alarm and trip contact
    Oil temperature indicator with alarm and trip contact
    Winding temp. indicator with alarm trip contact