How to Connect NAMUR Sensors to an Intrinsic Safety Barrier

แชร์
ฝัง
  • เผยแพร่เมื่อ 16 พ.ย. 2024

ความคิดเห็น • 25

  • @hightechplatform1874
    @hightechplatform1874 หลายเดือนก่อน

    thx a lot for the video , it is great. i got a question that i have got the same configuration you have with NAMUR normally closed , and i would like to send a normally open logic signal to plc when target is detected , could you please share with me the way of doing this. many thx

    • @PepperlFuchsUSA
      @PepperlFuchsUSA  หลายเดือนก่อน

      Hello @hightechplatform1874, first you need to select the correct intrinsic safety barrier for your application. This would fall under our “Switch Amplifiers” on our website. We have many models to choose from. One deciding factor is the switching frequency.
      For switching applications with a frequency of 10 Hz or less, you can use a switch amplifier with a relay output. The most common is the KCD2-SR-EX1 for one channel or the KCD2-SR-EX2 for two channels.
      For switching applications with more than 10 Hz, you should choose a barrier with a transistor output. The most common would be the KCD2-SOT-EX1 for one channel or the KCD2-SOT-EX2 for two channels.
      All of the above models have DIP switches on the front panel of the barrier that allow the user to select an output mode based on the NAMUR input state. There is also a yellow status LED that illuminates when the output is in an “on” state. This provides a visual indication when the output is “on” based on the position of the DIP switches. For more information, please refer to the datasheet which can be downloaded from files.pepperl-fuchs.com/webcat/navi/productInfo/pds/70109406_eng.pdf?v=20240919144052.
      We hope this has answered your question.

  • @victoremmanuel711
    @victoremmanuel711 5 หลายเดือนก่อน

    Please tell me More about pepper+fuchs products
    If I can get a video regarding a proper explanation on its terminals functionality and how to troubleshoot it... Many Thanks 🙏

    • @PepperlFuchsUSA
      @PepperlFuchsUSA  5 หลายเดือนก่อน

      Hello Victoremmanuel711, we will look into your suggestion when creating our next video. If you have any questions you need answered now, you can fill out our Ask An Expert online form, and one of our tech specialists will reach out to you. www.pepperl-fuchs.com/usa/en/ask_an_expert_pa.htm

  • @MW-L.o.S-Essex
    @MW-L.o.S-Essex 4 หลายเดือนก่อน

    Hi - i require a galvanic barrier for a 24a DC fire alarm detection circuit AND a 24v DC Fire Alarm sounder circuit that uses reverse voltage monitoring. Is there a barrier for these types of uses?

    • @PepperlFuchsUSA
      @PepperlFuchsUSA  4 หลายเดือนก่อน +1

      @MW-L.o.S-Essex, thank you for your interest in Pepperl+Fuchs products. We're here to help. Our customer service agents and technical support specialists are ready to answer your questions and help you get the information you need.
      Please fill out our Ask an Expert form by clicking this link here:
      www.pepperl-fuchs.com/usa/en/ask_an_expert_pa.htm

  • @ravitejagujja
    @ravitejagujja ปีที่แล้ว

    Sir I need two Analog input (4-20mA) and respective two Analog Output (4-20mA). Which model Pepper Fusche should I select.

    • @PepperlFuchsUSA
      @PepperlFuchsUSA  ปีที่แล้ว

      Hi Raviteja, This is a 2-channel isolated barrier that can power a field transmitter, or accept a 4 ... 20 mA current source from the field, and pass that signal to the control side of the barrier.
      The datasheet can be found here:
      www.pepperl-fuchs.com/usa/en/classid_7.htm?view=productdetails&prodid=63975
      If you need further assistance, please contact our Ask an Expert by clicking here: www.pepperl-fuchs.com/usa/en/ask_an_expert_pa.htm

  • @Nalllllaaa5
    @Nalllllaaa5 3 ปีที่แล้ว +1

    Please explain about the KFD2-SOT2-Ex1.LB , how switching voltage is consumed by isolator ( 2vdc to low voltage pulses) while the input proximity is under continuous pulse sensing...

    • @PepperlFuchsUSA
      @PepperlFuchsUSA  3 ปีที่แล้ว +2

      Hello Nallendran, the KFD2-SOT2-Ex1.LB switch amplifier provides a constant excitation voltage of 8 VDC to power the NAMUR proximity switch. The NAMUR proximity switch varies the current in the loop to indicate position. The switch amplifier monitors the current in the loop to determine its output status. Please visit us at www.pepperl-fuchs.com/usa/en/ask_an_expert_fa.htm should you need further assistance. Thank you.

  • @rahulduttsharma1955
    @rahulduttsharma1955 5 ปีที่แล้ว +2

    Please make one video about current and voltage changes on NO,NC Namur Inductive sensors

  • @syedmohsinsaeed857
    @syedmohsinsaeed857 5 ปีที่แล้ว +2

    what are the other types of barriers and where we use them ?

    • @PepperlFuchsUSA
      @PepperlFuchsUSA  5 ปีที่แล้ว +2

      Hi Syed,
      All of our Switch Amplifiers can accept a NAMUR sensor or dry contact input. Our most common Switch Amplifier is our KFD2-SR2-EX*. It comes as either a single or dual channel model. And it accepts both NAMUR sensors and dry contact inputs. This type of barrier is part of our K-System portfolio, which are galvanic isolators. However we have a second line of I.S. barriers, our Z-system. These are not galvanic isolators, they are Zener barriers. These are passive devices, but still meet the I.S. requirements for connecting a NAMUR sensor or dry contact. Zener barriers do require a dedicated I.S. ground per NEC sec. 504. Out most common for these are our Z728 (single channel) and Z787 (dual channel).

  • @soloado5084
    @soloado5084 2 ปีที่แล้ว

    Trying finding out how KLB 2.30 lightning barrier is installed on a DIN rail . But , I cannot find it .

    • @PepperlFuchsUSA
      @PepperlFuchsUSA  2 ปีที่แล้ว

      Hi there Solo Ado, please download the Manual Surge Protection Barriers (SPB Handbook) by clicking the link www.pepperl-fuchs.com/usa/en/classid_383.htm?view=productdetails&prodid=219#documents. On page 46, section 9.5 you will find information on the installation of the KLB 2.30 on a DIN rail. If you need further assistance please contact our Ask An Expert www.pepperl-fuchs.com/usa/en/ask_an_expert_pa.htm. Thank you.

  • @gavsraw7812
    @gavsraw7812 6 ปีที่แล้ว +1

    Could we use potential free contacts at inputs in place inductive sensors?

    • @PepperlFuchsUSA
      @PepperlFuchsUSA  5 ปีที่แล้ว

      Hi,
      You can use dry contact inputs. All models of our Switch Amplifiers can accept this. Our most common Switch Amplifier is our KFD2-SR2-EX*. It comes as either a single or dual channel model. And it accepts both NAMUR sensors and dry contact inputs.

  • @eliasboutana3680
    @eliasboutana3680 ปีที่แล้ว

    how does the intrinsic module connect with the automation and how does the automaton act? give an example in the event of a flame how it will act?? if there are several photocell sensors. how to connect with the automaton

    • @PepperlFuchsUSA
      @PepperlFuchsUSA  11 หลายเดือนก่อน

      @eliasboutana3680, we're here to help. Our customer service agents and technical support specialists are ready to answer your questions and help you get the information you need.
      Please fill out our Ask an Expert form by clicking this link here: www.pepperl-fuchs.com/usa/en/ask_an_expert_fa.htm

  • @MrSidra2009
    @MrSidra2009 2 ปีที่แล้ว

    can i connect two or three device on same barrier

    • @PepperlFuchsUSA
      @PepperlFuchsUSA  2 ปีที่แล้ว

      Hello Osama Essa yes you can. We have a 4-channel barrier, the KFD2-SRA-Ex4, on our website where you can also find the data sheets www.pepperl-fuchs.com/usa/en/classid_6.htm?view=productdetails&prodid=35550. If you should have further questions, please don’t hesitate to contact us by filling out our Ask an Expert form at www.pepperl-fuchs.com/usa/en/ask_an_expert_pa.htm.

  • @diaadesoki5418
    @diaadesoki5418 5 ปีที่แล้ว

    hi
    i need a manual for KHD2-SS1/Ex2
    i searched for it but i can't find it

    • @PepperlFuchsUSA
      @PepperlFuchsUSA  5 ปีที่แล้ว +1

      Hi Diaa, what is the best email address to send the manual pdf to?

  • @isaacsepulveda8411
    @isaacsepulveda8411 6 ปีที่แล้ว +2

    Hello,
    you know I have problems with the exit states, in some occasions it is enabled both exits (open and closed state in the case of valve), I would like you to indicate some possibilities of such failure.

    • @PepperlFuchsUSA
      @PepperlFuchsUSA  6 ปีที่แล้ว

      Hi Isaac, we will look into your suggestion when creating our next video. If you have any questions you need answered now, you can fill out our Ask An Expert online form and one of our tech specialists will reach out to you. www.pepperl-fuchs.com/usa/en/ask_an_expert_pa.htm