Omron CP1H PLC System Hardware

แชร์
ฝัง
  • เผยแพร่เมื่อ 22 ส.ค. 2024

ความคิดเห็น • 7

  • @ugurzal860
    @ugurzal860 5 ปีที่แล้ว +1

    Hi i need to help
    When we creat new channel in cp1e da modul(cpw1a), we write 8099.
    I know mean of 99 but why we write 80(1000 0000)?

    • @ACCautomation
      @ACCautomation  5 ปีที่แล้ว +1

      Hi Ugur,
      The first bit of the word is the sign. This means that you are writing -99. I would check the setup of the analog card if you do not want to use the negatives.
      industrial.omron.ca/en/media/CP1E_Hardware_UsersManual_en_201601_W479-E1-09_tcm824-108755.pdf
      Here is the manual. Look under the Analog Input Signal Ranges.
      Regards,
      Garry

    • @ugurzal860
      @ugurzal860 5 ปีที่แล้ว +1

      Garry Shortt
      Thanks Garry 🙏🙏

  • @auster3122
    @auster3122 3 ปีที่แล้ว +1

    Hello. I set Constant Cycle Time to 500ms. Then PLC lost all contact with PC and i can't change it back to normal. Is there any way for a hardware factory reset of PLC?

    • @ACCautomation
      @ACCautomation  3 ปีที่แล้ว +2

      Hi Auster,
      I would try the following:
      Open CX-Programmer and connect to PLC using Auto Online.
      Place PLC in Stop mode.
      Clear PLC Memory. "PLC" --> "Clear All Memory Areas" --> "Initialize".
      Regards,
      Garry

  • @bendylee860
    @bendylee860 5 ปีที่แล้ว +1

    Can i have this sample program?
    Thanks.

    • @ACCautomation
      @ACCautomation  5 ปีที่แล้ว +1

      You can get the information on the website at:
      accautomation.ca/omron-cp1h-system-hardware/
      Regards,
      Garry