RSLogix 5000 Analog Input Programming | Wiring Scaling Tutorial for PLC Analog Input Signal Example

แชร์
ฝัง
  • เผยแพร่เมื่อ 27 ธ.ค. 2024

ความคิดเห็น • 28

  • @Manjinder_Pawar
    @Manjinder_Pawar 3 ปีที่แล้ว

    Vlad you are doing great work ... best wishes to you

  • @ahmedabdulkareem6481
    @ahmedabdulkareem6481 4 ปีที่แล้ว +3

    I think the reason why for the fluctuation is your output is from an HMI which means has a processor and frequency, the input module of the AB has a scan frequency too, so both processors will meet sometimes in a point where no output from the HMI while the input is scanning, better to use a true analog like a battery with a resistor for things like this, better to use current to begin with to get better value at longer cables, thanks for the video buddy

  • @amreshadwikvirtual
    @amreshadwikvirtual 2 หลายเดือนก่อน

    Exlnt explanation👍

  • @muhammadatif1696
    @muhammadatif1696 5 ปีที่แล้ว +3

    Splendid!
    Do make the video for the Analog Output Signal.
    Thanks!

  • @electrichorror6642
    @electrichorror6642 5 ปีที่แล้ว

    good vid. Like it how you debugged it and found the issue some people would have solved it and not showed it

  • @FollowerofYahuwah
    @FollowerofYahuwah 4 ปีที่แล้ว +1

    What is the name of the video that covers the hmi and the analog programming you touched on a little. I want to figure out how to do the hmi analog control and how to create the ladder logic for it. Why does it seem NO ONE really covers the actual breakdown of the ladder logic for those of us who are new? Everyone touches on it back never fully goes into it including examples of how to write and use the logic.

  • @improviser100
    @improviser100 3 ปีที่แล้ว +3

    By the way, the catalog number for the expansions are also on the inside of the cover. Bottom corner.

  • @sahand944
    @sahand944 5 หลายเดือนก่อน

    very helpful. thanks

  • @CADELZOGMR
    @CADELZOGMR 5 ปีที่แล้ว +1

    Thanks, buddy. You helped me a lot.

  • @rachidajewher8649
    @rachidajewher8649 4 ปีที่แล้ว

    do you know how i'm gonna scale the analog signal coming from a preamp to an adc in audio ? do you know any analog brand for this

  • @amreshadwikvirtual
    @amreshadwikvirtual 3 ปีที่แล้ว

    I want know how to change the range or scale of a particular AI in RS logix5000. Could u plz help me on that?

  • @PLCProgrammingCourses
    @PLCProgrammingCourses 4 ปีที่แล้ว

    Very useful stuff 😊

  • @LololeoLolo
    @LololeoLolo 3 ปีที่แล้ว

    can i add a analog module to a compactlogix 5069 on ONLINE MODE without going off with the plc ???

    • @SolisPLC
      @SolisPLC  3 ปีที่แล้ว

      No, you can't add modules online.

    • @SolisPLC
      @SolisPLC  3 ปีที่แล้ว

      Although Rockwell does allow you to add external devices online. It may be possible... I'd have to check.

    • @LololeoLolo
      @LololeoLolo 3 ปีที่แล้ว

      @@SolisPLC i have an entire water treatment plant operation running under a compact logic 5069 ( with their respective module ) I’m gonna have to shut down the plant to install a new analog if8 module ?

    • @SolisPLC
      @SolisPLC  3 ปีที่แล้ว +3

      @@LololeoLolo by the NEC (electrical code), you need to shut down the panel to perform any modifications even at low voltages. Regardless of what can be done with the module, this isn't something that should ever be done live... For equipment and personnel protection.

  • @megrobelly
    @megrobelly ปีที่แล้ว

    what hmi is that?

  • @naop86
    @naop86 4 ปีที่แล้ว

    Very useful thank u!!

  • @repro-rt6lu
    @repro-rt6lu 3 ปีที่แล้ว

    How are u able to change to a real #?

  • @plcplc3138
    @plcplc3138 4 ปีที่แล้ว

    Cool videos, brilat brain!

  • @benc8030
    @benc8030 5 ปีที่แล้ว

    Hi Vlad, Can you please made a video of selecting job thru an array of database with many attributes

  • @rahulmaharnor9000
    @rahulmaharnor9000 4 ปีที่แล้ว

    do more videos on Communication protocol in AB

  • @selvaganeshs4145
    @selvaganeshs4145 5 ปีที่แล้ว

    Kindly make video for analog output also

  • @ZohaibJahan
    @ZohaibJahan 5 ปีที่แล้ว

    Any other way of scaling Analog values apart from CPT?

    • @Davedwin
      @Davedwin 3 ปีที่แล้ว

      I know you posted this a year ago, but ... For my Analog mA signals, the designers of our logic created some Analog Conversion function blocks. We put the RAW input into a function block (using values from the chart seen here). I then send that converted value to another FB that converts that to the value for the instrument (psi, gpm, deg, etc.).

    • @GuidoCarmona
      @GuidoCarmona 4 หลายเดือนก่อน

      yes, with SCP AddOn Instruction.