ความคิดเห็น •

  • @hackfreehvac
    @hackfreehvac 3 ปีที่แล้ว

    *Doing this same repair on a Trane*
    th-cam.com/video/3PGp8I4Mj1w/w-d-xo.html

  • @sammychow4467
    @sammychow4467 หลายเดือนก่อน +3

    Try this today and works good, before i cut it out & dip into the solvent and use use wire to clear the piston, save a lot of time. Thank you for sharing

    • @hackfreehvac
      @hackfreehvac หลายเดือนก่อน

      Glad to see it keeps doing the job 👍

  • @lil-m512
    @lil-m512 ปีที่แล้ว +1

    5 yrs later and I can say this man is a GOAT. preciate da vid, was having issues with evap and tried this b4 replacing and she is cooling !! BADASS 🔥

  • @bradleydicken5864
    @bradleydicken5864 6 ปีที่แล้ว +1

    Hey I just wanted to thank you for this video. It allowed me to save my customer by following your steps I did this and save the metering devices

  • @SETH0341
    @SETH0341 5 ปีที่แล้ว

    I would love to learn this trade in depth from a master like yourself. OUTSTANDING!!

  • @guitarhvac
    @guitarhvac 5 ปีที่แล้ว +2

    Awesome trick to know! Thanks for taking the time and effort to make this video.

  • @manueltorrez3843
    @manueltorrez3843 ปีที่แล้ว +1

    I followed your steps and was able to clear both circuits that were clogged and back in good operation. Thanks for the help man!

  • @Gears.and.Gadgets
    @Gears.and.Gadgets 5 ปีที่แล้ว +2

    Nice work
    I will have to remember that one. Thanks for sharing.

  • @vizcarra1981jose
    @vizcarra1981jose 3 ปีที่แล้ว +2

    Thanks for this video. I have been running into a couple of units with the same issue. I’m going to have to try this out.

  • @Nateone626
    @Nateone626 4 ปีที่แล้ว

    Hey bro thanks to your video it got me out of a bind! The header or coil won’t be available until nov and I seen this video and it helped me out this morning. She’s back up and running! New sub dude!!

  • @coreyjohnson6528
    @coreyjohnson6528 5 ปีที่แล้ว +1

    Had a tech fix a leak on one of these guys, got the job done, turned it on and it pumped itself down real quick. The next day I watched this video, did exactly what you said and she runs like a champ for now. Thank you for this sir

  • @alekmartinez3109
    @alekmartinez3109 4 ปีที่แล้ว +1

    Thanks for kicking that knowledge dude you're legit..

  • @TheCarterHour
    @TheCarterHour 6 ปีที่แล้ว

    Your videos are awesome. Doing it the right way!

  • @utubepro7742
    @utubepro7742 6 ปีที่แล้ว

    Awesome video
    I done this before with taking refrigerant out
    But that’s the greatest way

  • @dandaman2226
    @dandaman2226 6 ปีที่แล้ว

    Nice repair brother. I had one of these last year where we replaced the coil... as it was under warranty

  • @israelguillen7840
    @israelguillen7840 ปีที่แล้ว +1

    You are a true Master. Thanks You for the vídeo.

  • @marquezfamily3524
    @marquezfamily3524 6 ปีที่แล้ว

    Great video! Thank you for the tip. I am sure I will run into this one day.

  • @tracykronenberg6977
    @tracykronenberg6977 6 ปีที่แล้ว +4

    Nice trick. I have to remember that. Found some plugged up ones in scottsdale a few times.

  • @trentthompson5734
    @trentthompson5734 ปีที่แล้ว

    I literally just ran into this today. Didnt know you could do this. Im gonna think about this all night lol

  • @jjbotch2081
    @jjbotch2081 4 ปีที่แล้ว

    Beautiful job!

  • @markbeiser
    @markbeiser 5 ปีที่แล้ว

    I found a 3 year old carrier heat pump package unit with that problem last week, only someone else had over charged the crap out of it and told them it had a leak.
    I recovered 24 pounds of 410A that had an 18 pound factory charge...
    On a hope and prayer I changed the filter drier in hope that that was it, but no dice. It isn't quite plugged enough to freeze the coil, so I threw some AC renew in it to see what happens.
    I'm not confident in the AC Renew, so I'm pretty sure I'm going to be giving this method a try on the unit this week. ;)

  • @argenismoreno8838
    @argenismoreno8838 3 ปีที่แล้ว

    I need to do a similar job this week, thank you for this video.

    • @hackfreehvac
      @hackfreehvac 3 ปีที่แล้ว +1

      Comment back and let us know if it worked.

  • @mpmbeshara2017
    @mpmbeshara2017 ปีที่แล้ว

    Thank you for sharing this

  • @rayshaya9931
    @rayshaya9931 2 ปีที่แล้ว +1

    I learned from your video and did a job about the video and it worked great! I also didn’t use flush.

    • @hackfreehvac
      @hackfreehvac 2 ปีที่แล้ว

      Awesome.
      I only used the flush one time. Yet it worked every time so far.

  • @hedilbertomoraza7304
    @hedilbertomoraza7304 6 ปีที่แล้ว +1

    Good repair!

  • @anthonyrodriguez243
    @anthonyrodriguez243 6 ปีที่แล้ว

    Great video learned something new thanks

  • @HVACinSC
    @HVACinSC 6 ปีที่แล้ว +2

    Great video! Got a few of these systems at a local church I’m gonna try this on over the summer. Keep up the great content brother!

  • @NorCal-refrigeration
    @NorCal-refrigeration 6 ปีที่แล้ว +1

    Awesome video 👍👍

  • @ChrisEdwardsRestoration
    @ChrisEdwardsRestoration 5 ปีที่แล้ว

    at least your honest, most techs will not want to do the work on that mess and would just replace it. kudo's

  • @jeremyvoshage2410
    @jeremyvoshage2410 6 ปีที่แล้ว +2

    Saved that customer a new evap coil. Well done. I always prefer to not add any additives so I just cut out the header and sweat in a TXV kit on units with plugged orifices.

    • @CraigDohner
      @CraigDohner 5 ปีที่แล้ว

      Yeah, I heard him talk about that before. I think he leaves it up to the customer if he mentions it. The conversion being the higher priced option. But being he's had such high success rate, it's probably appealing to the customer

  • @jonsaircond8520
    @jonsaircond8520 5 ปีที่แล้ว +1

    Awesome video!!!

  • @jaymz0074
    @jaymz0074 8 หลายเดือนก่อน

    Great video

  • @julioortega559
    @julioortega559 19 วันที่ผ่านมา +1

    I just did this today. I isolated the coils purged the oil and flushed with Rx11 them then I heated up and blew them out with nitro. I replaced the compressor and charged it with R417c (hot-shot2) after a deep vacuum.

    • @hackfreehvac
      @hackfreehvac 15 วันที่ผ่านมา

      Did you get normal pressures and splits afterwards?
      So far this worked each time I attempted it.

  • @derrickbabinsky6064
    @derrickbabinsky6064 3 ปีที่แล้ว

    Well done!

  • @jddr.jkindle9708
    @jddr.jkindle9708 6 ปีที่แล้ว +4

    Great job!
    Would like to see your RX11 Flush and Nitrogen experiment results.

  • @islamkloub4491
    @islamkloub4491 3 ปีที่แล้ว

    Dude awesome job

  • @stevesilianoff693
    @stevesilianoff693 ปีที่แล้ว +2

    I have replaced headers before. If you cut the tubes with tin snips and unsweat each orifice individually, it is not all that bad..
    Always replace the Filter-drier with Sporlan solid core type. Obviously use nitrogen while brazing to keep new orifices clean.

    • @hackfreehvac
      @hackfreehvac 11 หลายเดือนก่อน

      Yup, I've done that. With snips as well. The only real way of extracting the individual tunes out of the evap tube bell ends without destroying it 👍
      That is the official repair method.
      Just got to hope a manifold assembly is in stock.
      As for Sporlan filters... check out a video of Sporlan vs Emerson th-cam.com/video/5OtmSbBAmCY/w-d-xo.html
      My coworker seen the demo in person. You could tap on a sporlan while it runs and it allows debris to escape

  • @hookedup9424
    @hookedup9424 10 หลายเดือนก่อน

    I need to do this this week. Wish me luck. Thanks for the video.

    • @hackfreehvac
      @hackfreehvac 10 หลายเดือนก่อน

      Post the results

    • @hookedup9424
      @hookedup9424 10 หลายเดือนก่อน

      @@hackfreehvac it didn't work very well but it helped. So I told the customer and we just ordered the TXV conversion kit which is nice because it will fix both circuit one and two

    • @hackfreehvac
      @hackfreehvac 10 หลายเดือนก่อน

      @hookedup9424 If it's straight cool the conversion is easy.
      I have videos of that too. Older ones so look back a ways.
      Heat pumps don't convert.

    • @hookedup9424
      @hookedup9424 10 หลายเดือนก่อน

      @@hackfreehvac yeah it's a gas pack. I'm hoping it goes smoothly. It's been a pain in the ass and made me feel like I don't know what the hell I'm doing

    • @hackfreehvac
      @hackfreehvac 10 หลายเดือนก่อน

      @@hookedup9424
      Here is a video of me doing that 8 years ago 👍
      th-cam.com/video/6r-GAx8f3-0/w-d-xo.htmlsi=VfJBFPR2YInFdscG

  • @mikie2501
    @mikie2501 5 ปีที่แล้ว

    Awesome brother! I love your swedge tools, oh, and that freakin' display setup!! Niiice :)

    • @SombraLocs
      @SombraLocs 4 ปีที่แล้ว

      Are you still making videos?

  • @janibashamolla
    @janibashamolla 5 ปีที่แล้ว

    Good knowledge for us

  • @jamminwrenches860
    @jamminwrenches860 3 ปีที่แล้ว +1

    Brilliant fix. The copper glitter from spin swedge went down both pipes though. I hope it dosent cause a restriction. Spin swedge up to keep debris out.

    • @ianicus123
      @ianicus123 3 ปีที่แล้ว

      That tool does not remove copper, I usually use a little oil to help it work even better.

  • @jerryfrigeration
    @jerryfrigeration ปีที่แล้ว

    that was awesome..... subscribing!

  • @edlauren9434
    @edlauren9434 2 ปีที่แล้ว

    I think that I will try your method on Bryant 10 ton RTU next week.

  • @codyd3456
    @codyd3456 4 ปีที่แล้ว

    Life Saver ! !
    Restriction killed Compressor, Of course Carrier didn’t have it in stock 🤦‍♂️.

  • @arthouston7361
    @arthouston7361 5 ปีที่แล้ว

    A few months ago, I did this with a straight cool/gas heat Carrier, and the stuff found its way back into the orifices after I had blown them out. I ended up replacing the header and orifices.

    • @joeanderson6187
      @joeanderson6187 3 ปีที่แล้ว

      This is a bandaid fix at best.

    • @arthouston7361
      @arthouston7361 3 ปีที่แล้ว

      @@joeanderson6187 I have decided to stop doing orifice replacements, because half of the time there is still a problem in the evap, and the better part of a day is wasted.If I saw a more consistent outcome, i would be clearing the orifices, but after so many partial outcomes, I just write them up.

  • @HughesManHVAC
    @HughesManHVAC 6 ปีที่แล้ว

    Nice video

  • @DWAYNE2ism
    @DWAYNE2ism 5 ปีที่แล้ว

    hey great video

  • @actechformallyyomama746
    @actechformallyyomama746 4 ปีที่แล้ว +3

    I’ve seen many times if you loose a condenser motor and the head pressure gets high those flowraters clog up. I’ve never tried the nitrogen purge while heating the pistons with heat. I wonder have you tried this with the unit running? I wonder if it would work. Oh and it’s shellac from the windings of the compressor running hot.

  • @mychoclabwinston
    @mychoclabwinston 5 ปีที่แล้ว

    Nice vid

  • @randomrefrigeration4564
    @randomrefrigeration4564 5 ปีที่แล้ว +2

    I have done this with 3 carrier units without using rx11 and have had 100% success. The key is isolating the short orrfice tubes as you did. Great video but this will not work on a Goodman because nothing works on a Goodman except a trane curb adapter lol

  • @patrickbowers1
    @patrickbowers1 4 ปีที่แล้ว +1

    where do you get the swedgie for the drill???

  • @jlwhitt77
    @jlwhitt77 5 ปีที่แล้ว

    Where did you get your swedge tools at? Those are awesome.

  • @lancerudy9934
    @lancerudy9934 4 ปีที่แล้ว +1

    Does that swage make any dirt in the system?

  • @robertschwiesow1593
    @robertschwiesow1593 3 ปีที่แล้ว

    wOULD have BEEN NICE TO SEE BEFORE PRESSURES ALONG WITH THE AFTER !

    • @hackfreehvac
      @hackfreehvac 3 ปีที่แล้ว

      Search the videos.
      There should be some others.
      There should be one of a Trane that was really bad. Same fix. Multi orifice header design.

  • @SombraLocs
    @SombraLocs 4 ปีที่แล้ว +1

    What kind of Subcooling and Superheat were you getting with those plugged orifices?

  • @justdissin7340
    @justdissin7340 4 ปีที่แล้ว

    What is the procedures for a split system?

  • @bennysanchez96
    @bennysanchez96 ปีที่แล้ว

    We’re those tubes freezing up before your repair when you were testing the system?

  • @HelixtheCAT01
    @HelixtheCAT01 ปีที่แล้ว

    I just recently replaced a bad compressor in a carrier HP RTU from 2002. I unknowingly removed the check valves with the strainers and installed (2) filter driers where the old strainers were. I thought the strainers were filter driers. I added refrigerant back into the system and now it’s running low suction. I’m assuming I need to install new check valves and remove (1) of the driers? Any pointers would be appreciated as I have never worked on these particular units before.

    • @hackfreehvac
      @hackfreehvac ปีที่แล้ว

      You can use a filter drier in place of a strainer. But you will need the check valves.
      Also if the system had a restricted multi orifice manifold assembly before the old compressor died then you'll still have that restriction after

  • @jroqraymond6342
    @jroqraymond6342 3 ปีที่แล้ว

    Dude I want to thank you for your advice on this ,my name is jack Raymond Watson Jr and I showed my video on Facebook if you would watch and comment would be awesome ,I wasn't as discriptive as you but it worked

  • @coolezum
    @coolezum 5 ปีที่แล้ว

    If the Header that contains the metering devices is available at parts house. might be good to replace header. Good job, by the way! Peace

    • @markbeiser
      @markbeiser 5 ปีที่แล้ว

      Usually 2-3 weeks to get one, and an absolute PITA to replace on some models, especially the 14 SEER heat pump package units.

  • @danpmatz
    @danpmatz 5 ปีที่แล้ว

    What psi of nitrogen? 75?

  • @victorguerra9232
    @victorguerra9232 6 ปีที่แล้ว

    Do put,maybe wd40,,so it can spin faster,,,just asking or would it do more damage than good??

  • @anders882
    @anders882 4 ปีที่แล้ว +4

    "Looks factory!"

  • @braintumor943
    @braintumor943 2 ปีที่แล้ว +1

    First you don’t have to change the whole coil, you can just change the orfice header, and if this doesn’t work, damn it’s a lot of wasted time and a dryer down the drain, but you did teach me something with the heating up the orfices

    • @hackfreehvac
      @hackfreehvac 2 ปีที่แล้ว

      Yeah you can buy an orifice kit and cut the old one out and piece together the kit.
      I've just been able to clear them out.
      On straight cool in just convert to TXV with feeders

    • @braintumor943
      @braintumor943 2 ปีที่แล้ว

      hackfreehvac I’ve done dozens of conversions, kits and building own distributor, they work on tranes great but not so much on the carriers, it’s a toss up on them I believe it’s because the valve has to be in heat, like this old Lennox that were built that way

    • @braintumor943
      @braintumor943 2 ปีที่แล้ว

      Orfice kits are not that hard, carriers you have to pull while coil, 4 hour job

    • @hackfreehvac
      @hackfreehvac 2 ปีที่แล้ว

      @@braintumor943 I've done it on Trane and Carrier but on straight cool.
      The heat pumps have check valves to change flow/purpose of part of each coil depending on heading or cooling mode.

    • @braintumor943
      @braintumor943 2 ปีที่แล้ว

      hackfreehvac you right, we don’t get a lot of heat pumps, although we do get dehum in drug warehouses, labs, clean rooms, etc
      On a side note, kind of threw dud under the bus didn’t ya, haha

  • @aldomartinez7698
    @aldomartinez7698 4 ปีที่แล้ว +3

    I'm about to try this I have about 20 carrier rtu about 15 years old and most of them with restrictions will see how it goes

    • @hackfreehvac
      @hackfreehvac 4 ปีที่แล้ว +1

      Make sure you come back and let us know how it went.

    • @tobyoverton_hvacr
      @tobyoverton_hvacr 3 ปีที่แล้ว +1

      Been a few months, how’d it go?

  • @agudolaespada3302
    @agudolaespada3302 2 ปีที่แล้ว

    Great results and still 11 people didn't like the video. And I'm sure the tenant was glad there was no need for a change out

  • @bmorekairful
    @bmorekairful 4 ปีที่แล้ว

    How do you know that's where your restriction is? Does it frost up there? And you had low suction pressure, high superheat?

    • @hackfreehvac
      @hackfreehvac 4 ปีที่แล้ว

      No drop across the strainer/check valve.
      And you do often see frost after the metering device.
      Low suction pressure and high superheat.
      I often add a pinch of refrigerant to see if it corrects as these are sometimes hard to tell the difference when the restriction is subtle.
      If the subcooling starts to climb with the extra refer than it is definitely restricted.

  • @ianicus123
    @ianicus123 3 ปีที่แล้ว +1

    Yep done this befor

  • @HealthInfo
    @HealthInfo 6 ปีที่แล้ว

    What were the symptoms the unit was displaying before you cleared the restriction?

    • @hackfreehvac
      @hackfreehvac 5 ปีที่แล้ว

      Restriction.
      High superheat, low suction, low temp split. etc

  • @richardwoeckener7936
    @richardwoeckener7936 5 ปีที่แล้ว

    Kool.... nice job!

  • @bormorzx
    @bormorzx 4 ปีที่แล้ว

    Great video. How u do the vacuum on that rtu.. it’s no damage the compressor??

  • @eastcounty4605
    @eastcounty4605 3 ปีที่แล้ว

    I have a bryant package unit that i cannot find the metering device
    The unit is a heat pump r22 system. Tech support is no help because they wont call back. Cannot even find the manual on line. It's crazy. Unit model # 549BPX40000AK. Any help will be appreciated.

  • @Kman-hw9pf
    @Kman-hw9pf 3 ปีที่แล้ว

    Does that drill bit swager tool not leave shavings in the pipe?

    • @hackfreehvac
      @hackfreehvac 3 ปีที่แล้ว

      It's NOT a drill bit.
      It uses friction to heat the pipe then the pipe is able to be stretched to the shape of the spinning tool. The tool is made to do this.
      I do give a shot of nitro through the pipe just in case.

  • @OcRefrig
    @OcRefrig 6 ปีที่แล้ว

    Awesome Video ! Very cool Hackfree. Does it only Happen on Heat Pumps ? Yea, that Poe Oil Does not Like Heat. it seems to turn to white concrete , . i see it on cap tube systems all the time if Peope don't keep thier Commercial Refrigerator Condenser Clean. i would be interested to see what the Oil in the compressor on that unit Looks Like, ,If it Plugs up again i'd Do a Oil change on the Compressor. Awesome Video ! Thanks for Posting ! i Have not Ran into this yet.
    Thanks also for the cool Swage usage tip. i'm Gonna Get me some of those . i have seen those before but, i did not think they would work very well. on the big 7/8 one u might want to use some wd-40 and it might go Easier. take er easy.

    • @hackfreehvac
      @hackfreehvac 6 ปีที่แล้ว

      I think I've fixed some on the gas packs too.

  • @carlososborne2866
    @carlososborne2866 4 ปีที่แล้ว

    cool

  • @jeffscanlan3554
    @jeffscanlan3554 5 ปีที่แล้ว +1

    The problem with this is that it is only a temporary fix and someone will be back again because you have not got the wax completely out and like someone else said the oil was more than likely over heating to cause this.

    • @CraigDohner
      @CraigDohner 5 ปีที่แล้ว +1

      Sure, but to get them back up and running can be a great win. Then you tell them you're going to need to come back and do that work. Job security. Most customers like the option of getting their equipment back up and running with little cost. Then perhaps with incremental improvements making it look like it didn't cost so much. So it depends on what the customer wants to do sometimes. You make recommendations that keeps you coming back if you like doing that. But being he's had such success performing this task, the simplicity in it, and the lack of parts needed to perform the task, it's a cheap option to get the customer up running. Additionally, in inline filter replacement will buy even more time. A cost most customers are willing to fork out. But again, with the thought of returning. So dude, he just got them running at a fraction of the cost of another (rejected) quote. All the while landing a repeat customer for saving them money.
      But seriously though, do you actually believe this is the kind of guy that had not considered everything you've just stated? Clearly, the contaminated oil issue is the obvious. But with the success rate being 100%, I'd think he knows what he's doing. So your comment is definitely odd. What tech performing such a task wouldn't know that?

  • @lilweezy110
    @lilweezy110 2 ปีที่แล้ว

    to make swage easier i usually heat it up a bit and then swage have never had any issues.

    • @hackfreehvac
      @hackfreehvac 2 ปีที่แล้ว +1

      That's what I do when I swage larger sizes such as 7/8

  • @mohammedsyedali8438
    @mohammedsyedali8438 7 หลายเดือนก่อน

    ❤how much pressure nitrogen. When we flash the system

    • @hackfreehvac
      @hackfreehvac 7 หลายเดือนก่อน

      When clearing the orifices I blow as fast as it will go. Short hard blasts. You see the smoke from the oil/wax come out for a second then it clears up.
      Just have the pipe around the orifice almost cherry red hot (but don't melt the copper) then blast it. Do the same on each parallel orifice.

  • @edwinjewell5359
    @edwinjewell5359 4 ปีที่แล้ว

    Can nitogen/heat/ and air mixture
    create a kaboom.

    • @hackfreehvac
      @hackfreehvac 4 ปีที่แล้ว

      Dry Nitrogen is fairly inert.
      It displaces the atmosphere so no oxygen in the system.

  • @ritchieortiz5610
    @ritchieortiz5610 5 ปีที่แล้ว

    Do you clear out the lines with nitrogen after you used that spinning swage?

    • @hackfreehvac
      @hackfreehvac 5 ปีที่แล้ว +1

      I often blow them out anytime I think something might get in there.
      Although the spinning swage doesn't really make any shavings at all. It makes the copper malleable by heating it up and then just stretches it.
      There is no cutting effect etc.

    • @cravenmoorehead6219
      @cravenmoorehead6219 5 ปีที่แล้ว

      @@hackfreehvac what's the brand of that swedge tool or where can I get one? That looks sweet , especially not leaving anything in the line.

    • @hackfreehvac
      @hackfreehvac 5 ปีที่แล้ว

      @@cravenmoorehead6219
      The brand I use is called Spin Swage
      spintools.com/swage/

  • @hvac01453
    @hvac01453 3 ปีที่แล้ว

    have you ever tried the AC Renew on them?

    • @hackfreehvac
      @hackfreehvac 3 ปีที่แล้ว

      That is a synthetic oil. I don't think it will remove the debris which are generally caused by nuked compressor oil. LOL
      AC Renew does seem to help with TXV's though by helping the needle move smoothly. Reversing Valves too.

  • @BoomhauerWorldwide
    @BoomhauerWorldwide 6 ปีที่แล้ว

    I always replace the header. Sometimes I swap to TXV.
    Carrier RTU'S sure keep us busy with repairs don't they? I call Carrier for quotes about everyday, probably have to call Trane and Lennox once a week.

    • @hackfreehvac
      @hackfreehvac 6 ปีที่แล้ว +2

      I often swap to TXV on the straight cool units but most units here are heat pumps and due to the check valves in the coil manifolds to re purpose sections of the coils differently for heat versus cool it is not an option to change to a TXV.

  • @52bighead
    @52bighead 6 ปีที่แล้ว

    Who makes the swage tool?

    • @hackfreehvac
      @hackfreehvac 6 ปีที่แล้ว

      There are a few brands making them.
      Search "Spinning Swage"

  • @damarcojackson1005
    @damarcojackson1005 5 ปีที่แล้ว

    Nice brotha ...lol😆!

  • @juanreveles3866
    @juanreveles3866 2 ปีที่แล้ว

    what were your pressures

    • @hackfreehvac
      @hackfreehvac 2 ปีที่แล้ว

      This was too long ago to remember that.

  • @bobbyatman273
    @bobbyatman273 3 ปีที่แล้ว

    Question; doesn't all that drilling introduce shavings into the system? Clearly does, now what?

    • @hackfreehvac
      @hackfreehvac 3 ปีที่แล้ว +1

      Did you think that was a drill bit?
      That is a specialized "swage" tool that is mase for this purpose. It is tapered and uses friction to heat the copper until the tapered swage tool spins down into it, creating a female fitting.
      There really isn't debris from this process.
      And the nitro can blow it out. And so far never had one single one of these come back to me restricted.
      These repairs are also already an option for the customer to get an old unit working as opposed to buying a new unit or waiting to get the entire header assembly.
      It is understood that it is a fix to get a little more life out of it. But again. Haven't had to go back on one single one yet for any restriction.

    • @bobbyatman273
      @bobbyatman273 3 ปีที่แล้ว

      @@hackfreehvac Thank you for explanation! Hey I'm not the only dummie around 🙃

  • @chriscordasco5449
    @chriscordasco5449 5 ปีที่แล้ว

    have you ever converted it to a txv ?

    • @hackfreehvac
      @hackfreehvac 5 ปีที่แล้ว +2

      When it's a straight cool I do convert them to txv.
      But on heatpumps it's difficult because the coils have multiple check valves to repurpose sections of each coil whether it's in heating or cooling mode.
      For example... in condenser coil mode the hot gas goes through multiple parallel connected circuits then comes out onto a manifold and then a single 3/8" line then goes back into the bottom section of the same coil for a few more passes before leaving as liquid to the other coil.
      That complexity prevents changing to a TXV.
      But straight cool units are a more typical design.
      Here's a video of converting a straight cool carrier to txv
      th-cam.com/video/6r-GAx8f3-0/w-d-xo.html

  • @OlGoodJoe
    @OlGoodJoe 2 ปีที่แล้ว

    I like what you did but 123lb suction? You got to have a bad low side valve in that unit.

    • @hackfreehvac
      @hackfreehvac 2 ปีที่แล้ว

      123 PSI is too high? LOL
      Normal 410 suction can be 110 to 150 easy depending on current return air load.
      Every 1 degree of increased evap coil temp adds several PSI of suction pressure.
      i.e. a 40 degree coil = 118 PSI
      41 = 121
      42 = 123
      43 = 125
      44 = 128
      45 = 130
      46 = 133
      47 = 135
      48 = 138
      49 = 140
      50 = 143
      An 80 degree return air temp can EASILY give you a 140 PSI suction pressure.
      123 is really good suction pressure.
      Low suction / high compression ratio is what kills compressors.
      When I did these repairs I informed the person that the compressor MAY already have taken a hit from the previous operation and that time will tell.

  • @shadowbanned69
    @shadowbanned69 4 ปีที่แล้ว

    I have a late question....the strainers on those 10 tonners. Are the check valves in those strainers?
    I have the same unit but mine is 96 and r22. But there has never been a filter dryer change or a strainer change. Ive cleared the accurators 2 years ago and it needs it again. But I've seen the fd installed at the condenser inlets and at the old strainer locations. I just dont want to install them in the wrong spot..
    Im asking you cause....well your the one hvac channel I enjoy the most....and your work ethic is exactly like mine...dealing with fucktards and idiot techs on a daily....is a job all in itself...lol 😆 I'm fixing a bunch of ass backwards shite...from a company who'd rather wait till it breaks royally and charge more instead of doing proper preventative maintenance...

  • @christ2290
    @christ2290 4 ปีที่แล้ว

    Won't it just plug up again since the oil wasn't changed?

    • @hackfreehvac
      @hackfreehvac 4 ปีที่แล้ว +2

      The OEM units often only used a screen strainer ahead of the check valve and orifice header to the evap coil.
      I install a good liquid line drier.
      I have yet to go back and fix the same problem on any of these.

  • @obedb093
    @obedb093 2 ปีที่แล้ว

    would you recommend using ac renew?

    • @hackfreehvac
      @hackfreehvac 2 ปีที่แล้ว +1

      Not for this issue.
      The synthetic coil helps sticking reversing valves and TXV's but this issue is more from oil breakdown from comp heating etc..

    • @obedb093
      @obedb093 2 ปีที่แล้ว

      @@hackfreehvac thanks for replying, how much pressure did you use to purge it.

    • @hackfreehvac
      @hackfreehvac 2 ปีที่แล้ว +1

      @@obedb093 I blasted the nitro pretty high after I heated the orifice

    • @obedb093
      @obedb093 2 ปีที่แล้ว

      @@hackfreehvac thanks it worked.

    • @hackfreehvac
      @hackfreehvac 2 ปีที่แล้ว

      @@obedb093 That's awesome.

  • @johndoe-wt4ui
    @johndoe-wt4ui 5 ปีที่แล้ว

    I heard it’s the compressor that’s turning the oil into wax or sludge or whatever

  • @hvacjohnnie
    @hvacjohnnie 5 ปีที่แล้ว

    Nice Job! If I could Sub twice I would have.

  • @Andrew-xs4qy
    @Andrew-xs4qy 5 ปีที่แล้ว

    im here because my evap on a rtu is fronzen from the meter ->evap

  • @sergiodjf
    @sergiodjf 3 ปีที่แล้ว +1

    Do they even teach this at HVAC school? Otherwise you may have to replace the whole manifold 😬

    • @hackfreehvac
      @hackfreehvac 3 ปีที่แล้ว

      Typical repair is replacing the entire manifold header assembly.

  • @christiandaniel3738
    @christiandaniel3738 10 หลายเดือนก่อน

    Happens a lot when the condenser coils get dirty

  • @mikepict9011
    @mikepict9011 3 ปีที่แล้ว

    Oil to ashes ashes to smoke

  • @supermoto3453
    @supermoto3453 6 ปีที่แล้ว

    wow what was that reamer tool on your drill?

    • @hackfreehvac
      @hackfreehvac 5 ปีที่แล้ว

      It's called SpinSwadge.
      Once you get a set you will wonder why you ever had to use a coupler. LOL
      spintools.com/

  • @MEATZBMX
    @MEATZBMX 5 ปีที่แล้ว

    I usually just replace the header

    • @hackfreehvac
      @hackfreehvac 5 ปีที่แล้ว

      That's what I used to do.
      Many techs condemn the entire coil because replacing the header is a lot of work.
      Doing what I am doing here is actually pretty quick and easy

    • @MEATZBMX
      @MEATZBMX 5 ปีที่แล้ว

      @@hackfreehvac definately.. I'm going to try this next time.. not quite cooling season yet for us in CT haha

  • @clarkgwozdecki6782
    @clarkgwozdecki6782 2 ปีที่แล้ว

    Would bet money you will get a future leak on those tubes you heated. Would have atleast wrapped the solder joints close by with wet rags.

    • @hackfreehvac
      @hackfreehvac 2 ปีที่แล้ว +1

      DUDE! 😆😆😆
      *The entire point is to quickly heat up the pipe just to the point of glowing red in order to liquify the oil wax in the internal captive acutrol (pistons) in order to then clear them out with nitrogen*
      Using a wet rag would fight that entire process.
      Remember. This is a quick last ditch effort on older units as opposed to swapping out the entire acutrol header assembly. That is, IF an assembly is even available. The customer would be fully aware that there were no promises.
      So far the only leak I have ever had yet was when I cracked one and I saw it crack and then simply welded over it.
      So far every attempt has worked and I didn't have a repeat failure as of the last time I was doing service on them.