You are simply the best! Thank you for your contribution to knowledge. By the way, I'm trying to learn relay protection schematics and circuit breaker trip and control diagrams. Do you have a video about them? I look forward to your response.
@@romeroengineering Reverse power protection is only for generators when the steam stop valves shut off, can you tell me why there will be reverse power in equipment other than generators?
In ETAP i found overpower and under Power in Reverse Power setting. For reverse setting in what i should fill for example setting is 4% from Pm (kW). In Overpower or Underpower?
Hi! Please keep watching, this is explained at minute 11:00 in the video, where the quantity is changed to -WATTS so that it is real power in the reverse direction
Learn more with our online courses here: www.romeroengineering.co/courses
Can you give instructions on how to use phase overcurrent protection? Thanks in advance!
You are simply the best!
Thank you for your contribution to knowledge. By the way, I'm trying to learn relay protection schematics and circuit breaker trip and control diagrams. Do you have a video about them? I look forward to your response.
Thanks! We don't have videos on those topics yet, but we'll consider them for future videos
@@romeroengineering Reverse power protection is only for generators when the steam stop valves shut off, can you tell me why there will be reverse power in equipment other than generators?
Very good. Thanks 👍
In ETAP i found overpower and under Power in Reverse Power setting. For reverse setting in what i should fill for example setting is 4% from Pm (kW). In Overpower or Underpower?
You calculated in W but setting in VA ?
Hi! Please keep watching, this is explained at minute 11:00 in the video, where the quantity is changed to -WATTS so that it is real power in the reverse direction
Thank you!
You're welcome!