HVAC no heat call, Restaurant at 58°

แชร์
ฝัง
  • เผยแพร่เมื่อ 31 ธ.ค. 2024

ความคิดเห็น • 134

  • @cherish313
    @cherish313 3 ปีที่แล้ว +3

    Love your videos! I'm a design engineer (restaurants and supermarkets) and it's always cool to see the tech side of things. I often get calls to help with first level troubleshooting before the tech calls, so I enjoy seeing the typical checks and balances and maintenance misses that I don't have control of once the design has become a physical building. Keep up the good work!

  • @arthurcastillo8767
    @arthurcastillo8767 4 ปีที่แล้ว +6

    Dangggg Bro.! You did exactly what i would have done. Exactly.!! i really appreciate your videos. Especially when i see a pro like you doing the same set of diagnosing procedures i would have done. Have a Merry Christmas everybody.!!!

  • @samuelaranda4597
    @samuelaranda4597 4 ปีที่แล้ว +3

    As a formal York start up teck. I did that for years. That was the 1st thing we put when we do start up is all the hardware. Also we put final pressures on the inner panel with a start up date. They are good units. Just like everything else you need to maintain it. Good job brother

  • @justwork_hvac
    @justwork_hvac 4 ปีที่แล้ว +1

    Good stuff..thanks for sharing ..keep the videos coming..god bless

  • @samuellortie1647
    @samuellortie1647 4 ปีที่แล้ว +1

    bro you are hilarious. love the vids, you are entertaining, you know what you are talking about and i'm learning new stuff since i'am an apprentice. keep it up!

  • @CHOMAHOMA
    @CHOMAHOMA 2 ปีที่แล้ว

    That's very warm having it at 76. Good Job!!!

  • @James-vf5gs
    @James-vf5gs 4 ปีที่แล้ว +1

    You did it all fine bro, you did all the necessary checks and had the same outcome. You did in AC, what a good HVAC guy would have done on a walk in cooler. Got the answer, maybe just not a direct way. Only other thing I've done is check supply fan motor current with a pulley adjustment like that. And if the client approved, checked air volume and cross referenced manufacturers data. If it was low, than that would have explained the high temp split. Air isn't something that's commissioned properly here in Australia coz every customer wants more for less. Costs have to be cut somewhere. Well done mate, and merry Christmas!

    • @rookierefrigeration4357
      @rookierefrigeration4357  4 ปีที่แล้ว

      Thanks bro. And thank you for watching from Australia. I was there twice in 2003 and 2004. Darwin and Townsville

  • @jphvac5725
    @jphvac5725 4 ปีที่แล้ว +8

    Great job. Pro tip from hard lessons learned when messing with pulleys, always check amp draw of motor after. Most motors will work temporarily and then start shutting off due to high amps from belt riding on outside of pulley. Exhaust fans are most critical and I’ve had callback because of not checking amp draws.

  • @SamMason-t4z
    @SamMason-t4z ปีที่แล้ว

    Always check amo draw on the motor when adjusting belts or pulleys. Great work.

  • @OcRefrig
    @OcRefrig 4 ปีที่แล้ว +4

    Good vid rook ! I Would have done most everything the same. Those steel inducer nipples all ways get rusty & get blocked up / rust blockage. First place I always go when pressure switch does not close.
    I would of checked the evap motor amps. While adjusting shivs. You can get into trouble adjusting shivs and over amping the motor. Careful there.
    But , still a good vid.
    Oh , also I allways check 24 volt transformer taps. They are allways tapped wrong on new equiptment I find out here.

  • @randomrefrigeration4564
    @randomrefrigeration4564 4 ปีที่แล้ว +9

    Nah you did a good job
    Just make sure you set the amps when you replace those sheaves if the install book is still there checkout the air performance data page
    I did not see any air balance stickers on the units
    If it was balanced then it’s going to be off now because someone already moved that sheave but doubt it was balanced looked like OEM sheaves to me
    As for the the plugged orifice your probably ok being the units are so new. Older unit can have rust flaking off that induced draft assembly causing the clog
    You did the call your way and got the customer taken care
    Good job I’m not going to lie though I sure enjoyed watching you on the racks lol
    Thanks Rookie

  • @robertpoitras6809
    @robertpoitras6809 4 ปีที่แล้ว +6

    Those adjustables pulleys are only used for start-ups (i mean c.f.m. Calibration)once the good cfm is found, the solid pulley should be put on...diameter, shaft and width of the groove.Only then the belt will sit and last longer.

    • @rookierefrigeration4357
      @rookierefrigeration4357  4 ปีที่แล้ว +1

      Agreed

    • @georgebrabec7138
      @georgebrabec7138 4 ปีที่แล้ว +3

      And how many times have we seen that swap actually done.
      you did good, sir !

    • @xraybravo7180
      @xraybravo7180 4 ปีที่แล้ว +1

      Wouldn't be nice if them mf also tag the unit cfm and pulley adjustment on there for future.

    • @throttlebottle5906
      @throttlebottle5906 4 ปีที่แล้ว

      nobody does that

  • @shoot3r1134
    @shoot3r1134 4 ปีที่แล้ว +3

    Learning a lot! Us new techs need all the help we can get!

  • @prestigemechanical1145
    @prestigemechanical1145 4 ปีที่แล้ว +1

    Clock the gas meter for the input. Also set the high fire to 3.25 and check your combustion. FYI that blower wheel is dirty it on only takes 1/8 of an inch of build up to affect air flow across the heat exchanger.

  • @lakeshvac
    @lakeshvac 4 ปีที่แล้ว +3

    Great to see videos from. You again

  • @theCybershot123
    @theCybershot123 4 ปีที่แล้ว +1

    I was told the adjustable pulley is there to get correct air flow. And if belt has been over tightened then that pulley wears faster than the fan pulley. Check fan motor amps to name plate.

  • @andrewwarfield6223
    @andrewwarfield6223 4 ปีที่แล้ว +1

    Gotta walk that line called NTE! I totally get it homie! Glad to see ya back

    • @djastram
      @djastram 4 ปีที่แล้ว +1

      Do we need the NTE people? Is that all they do is ask if I went over the NTE? I never know what the NTE is. How can I get a job being a NTE person? :)

  • @gas_man1565
    @gas_man1565 4 ปีที่แล้ว +3

    Most of the times when a service call comes in, i always check if the maintenance has been done, 75% of the time its usually a belt and or filters the issue. first things i do are, check belts and filters and then check codes.

  • @awesomebillfromdawsonville8715
    @awesomebillfromdawsonville8715 4 ปีที่แล้ว +3

    A lot of the newer valves are 1.2-1.3" wc low fire and 3.2" wc high fire if temperature rise is to high and air flow is good can help with high limit trips.

  • @deathlokmk1
    @deathlokmk1 4 ปีที่แล้ว +2

    First thing you check is the filters when it starts tripping on high limit.

  • @throttlebottle5906
    @throttlebottle5906 4 ปีที่แล้ว +2

    the wing-wang's may have half the vent fins/dampers inside partial closed inside the building or they may have vibrated closed depending on the type. I think most chipotle have exposed ducts and them multi-fin registers, which can easily get banged mostly shut cleaning

  • @mason122122goodman
    @mason122122goodman 4 ปีที่แล้ว +2

    I always adjust my gas pressure per temperature rise if airflow adjustments are accurate. Typically 3.0-4.0 is my limit for high stage.

  • @lilpbass
    @lilpbass 4 ปีที่แล้ว +1

    I just had to do this same stuff to the same York rtu here in Indiana. We always leave spare belts for pms.

  • @BYENZER
    @BYENZER 4 ปีที่แล้ว +1

    You crack me up!! I like your style! Great job dude! AND your SPIDERMAN 'SPIDEY SENSES', about a possible bad startup, were A.O.K.!! No handles = ABSOLUTE FAIR ASSUMPTION about a possible bad startup/install. SPIDEY SENSES!!! When the hair on the back of your neck, begins to standup, not always, but usually, it means, something ain't right!! LISTEN TO EM! SPIDEYS!!!

  • @jfoley1968jf
    @jfoley1968jf 4 ปีที่แล้ว

    Great job with a full check out.
    Merry Christmas 🎅

  • @ronaldclark8187
    @ronaldclark8187 4 ปีที่แล้ว +1

    Good call.
    Gas pressure and temp rise for sure.
    I use the field peice SDMN6 for gas pressure, static and vacuum switch testing.

  • @jeffreykubiak5126
    @jeffreykubiak5126 4 ปีที่แล้ว +1

    Good call on checking temp rise. Adjust pulley Amp motor . Check return air . Make sure Static pressure ok. Had a unit like that call back. Didn't check static returns were closed down. Rookie your specialty is Super markets.We all have strong points and not so strong. How does it go? Boyongg!🤣Feliz Navida!

  • @JackalJEB
    @JackalJEB 4 ปีที่แล้ว +1

    Might be just the old belt or the camera angle but they seemed off center slightly. I had a few jobs were the belts were only slightly miss aligned that caused them to wear out. Love the videos.

  • @hvac01453
    @hvac01453 4 ปีที่แล้ว +3

    I’ve worked in New England many many years, on a no heat call, keep it simple.... people don’t do maintenance commercial or otherwise as much as they should. It’s the first thing cut on my he budget. So first thing should always be filters and belts. Then NRG....elec, oil, gas, propane... b4 you go on the roof, speak to the manager and get an idea from their perspective and what they have done. Check the stat, is it on, switch the fan to on, if it starts, you have both power and a good transformer. Can you see or feel airflow?... now go on he roof.

  • @gameforfree2833
    @gameforfree2833 4 ปีที่แล้ว

    Good shit bro... l9ve the video. And your process of troubleshooting.

  • @markpayne6803
    @markpayne6803 4 ปีที่แล้ว +4

    At 9:48 approximately you checked the pressure switch to see if it was closing also could you have checked the amp draw on your inducer motor also just a suggestion

  • @picklerix6162
    @picklerix6162 4 ปีที่แล้ว +7

    It looks like they have the wrong size filters in those RTU’s.

  • @Robyrich2377
    @Robyrich2377 4 ปีที่แล้ว +1

    The belt and the pulley is one of the first things that you should’ve checked is in the start up sequence of operation.

  • @ivanconawayiv6707
    @ivanconawayiv6707 4 ปีที่แล้ว +2

    Nice video, now the important part when can we expect yalls next podcast man? I miss you guys.
    Semper Fi Brother!

  • @nickcampbell8096
    @nickcampbell8096 4 ปีที่แล้ว +1

    Good vid, those pulleys were shot. Checking supply air temperature right there can be deceiving. Not 100% sure on those units but your probably reading right next to the heat exchanger. I wonder what supply temp would have been at registers. And yes it would have been a pain in the ass to check. Good to have you back rookie!

    • @rookierefrigeration4357
      @rookierefrigeration4357  4 ปีที่แล้ว

      Agreed 100%. Thanks

    • @throttlebottle5906
      @throttlebottle5906 4 ปีที่แล้ว

      think of where the limit switches are and their trip temps. if there's lack of flow the air will cool down too much in duct and supply registers could be low enough to give false sense of overhead. manufacture probably states to check in the test holes or specifies where exactly to test :)

    • @nickcampbell8096
      @nickcampbell8096 4 ปีที่แล้ว

      Yea, I guess your right. Air flow issues can be a pain, especially if ductwork is jacked.

  • @andrewgilbreath1331
    @andrewgilbreath1331 4 ปีที่แล้ว +1

    Only thing I would have done differently is made sure that belt was square in the pulleys on the first unit you adjusted looked like it was riding hard on the left side. That will take out bearings and damage your shive fast to.

    • @rookierefrigeration4357
      @rookierefrigeration4357  4 ปีที่แล้ว

      Looked like it was. But it was straight. I saw that on the video too.

  • @curioushvacguy6876
    @curioushvacguy6876 4 ปีที่แล้ว +1

    awesome hat bro- you guys selling merch? I could probably google it and figure it out, lol

  • @EverythingHVACR
    @EverythingHVACR 4 ปีที่แล้ว +1

    Great video! Gonna have to change that name to rookie hvac guy, lol. I'm sure you did but better check your blower amps when adjusting the pulley.

  • @VitalYFZ
    @VitalYFZ 4 ปีที่แล้ว +1

    Spare belts should always be left in every unit. Not because of a damaged pulley, its so anyone can change that belt on the fly that comes along next. All vent hoods should be the same. You charge for two belts and leave one if you need to.

    • @rookierefrigeration4357
      @rookierefrigeration4357  4 ปีที่แล้ว

      Most of our customers DO NOT allow that. Almost all of them don’t.

  • @Ted_E_Bear
    @Ted_E_Bear 4 ปีที่แล้ว +2

    Another awesome video !

  • @JorgeRodriguez-wc6th
    @JorgeRodriguez-wc6th 4 ปีที่แล้ว

    I used to work on a lot of their refrigeration equipment and HVAC

  • @manuelherreros4609
    @manuelherreros4609 4 ปีที่แล้ว +2

    Great video bro. Keep up the good work 👌

  • @hugomoreno9312
    @hugomoreno9312 2 ปีที่แล้ว +1

    The man’s a wizard

  • @j.d.6221
    @j.d.6221 4 ปีที่แล้ว +1

    Got to love a nice multi level NTE increase process lol

  • @TexasStateMechanical
    @TexasStateMechanical 4 ปีที่แล้ว +1

    maybe check if there is enough return air for system(check external static pressure against data plate)looks like max static is 1.5 inwc put a manometer were your temp probes were and make sure you not above 1.5 inwc external static if you are above 1.5 inwc (between return and supply air).it could be a duct sizing issue, maybe check economizer functionality as well. just some thoughts. That’s if everything was checked out(like you did )and it was still popping the high limit.

  • @joshstevens9826
    @joshstevens9826 4 ปีที่แล้ว

    New guys, if u abjust a sheave make sure u check amps on the motor. Tighten the sheave equals higher amps, open the sheave equals low amps. Check the motor data plate

    • @larrydurkee5741
      @larrydurkee5741 3 ปีที่แล้ว

      Agreed. You should never adjust the sheave without checking the motor amp draw. Could come back and bite you in the butt if you don’t. Great videos keep up, the good work.

  • @joehead1294
    @joehead1294 4 ปีที่แล้ว +1

    Is that normal for the adjustable side of the pulley to be on the motor side? How's those uei pocket thermo's?

  • @SeersantLoom
    @SeersantLoom 4 ปีที่แล้ว

    8:40-8:46 - looks like the pulleys are not lined up. Possibly explains why left half of pulley shows more wear.

  • @hobbymadness
    @hobbymadness 4 ปีที่แล้ว +2

    Great vid!!! But not seeing you clean the flame sensor is driving my ocd nuts but i understand NTE's they drive my ocd nuts too. .:( ... .

    • @rookierefrigeration4357
      @rookierefrigeration4357  4 ปีที่แล้ว +1

      Lol. I thought about that. Lol

    • @gas_man1565
      @gas_man1565 4 ปีที่แล้ว +1

      you inspect it, first then you clean it, use steel wool and please dont use sand paper!

    • @hobbymadness
      @hobbymadness 4 ปีที่แล้ว

      @@gas_man1565 Simply can not change my ways!!! Never even heard of any tech running into issues from it. Although i do understand the theory behind not doing it.

  • @richardkirts7298
    @richardkirts7298 4 ปีที่แล้ว +1

    I use nothing but bc and ax belts. They last longer and save 10 to 20 %

  • @gregbowman3598
    @gregbowman3598 4 ปีที่แล้ว +2

    Good video 👍

  • @matthewgregory8218
    @matthewgregory8218 4 ปีที่แล้ว

    Arn,t those return vents?

  • @wonderhomie2011
    @wonderhomie2011 4 ปีที่แล้ว +2

    Lack of maintence call or job security call. I don’t like how the filters flop around inside the filter rack.

    • @rookierefrigeration4357
      @rookierefrigeration4357  4 ปีที่แล้ว +1

      I saw that too.

    • @BYENZER
      @BYENZER 4 ปีที่แล้ว +1

      @@rookierefrigeration4357 Supposed to be 4" thick filters, i think.

    • @jphvac5725
      @jphvac5725 4 ปีที่แล้ว +1

      They have a metal rail the sit in and can pull it out, automatically opening those hinges covers. Dislike that style York unit, prefer my carrier simplicity.

    • @FrostBlueFire
      @FrostBlueFire 4 ปีที่แล้ว +1

      @@BYENZER York is trash, end of story, they require 2 inch filters, they just make the access too big, it's not a good design.

    • @throttlebottle5906
      @throttlebottle5906 4 ปีที่แล้ว

      it will pull them flat against rack face as soon as it fires up the blower

  • @samx9024
    @samx9024 4 ปีที่แล้ว +1

    IVR, service channel on national accounts. Everything quoted and approved exceeding the NTE. It is a pain sometimes.

  • @Audaz_Firme
    @Audaz_Firme 4 ปีที่แล้ว +1

    Whats up with the podcast no new episode since the sporlan?

  • @tamershata4640
    @tamershata4640 4 ปีที่แล้ว +1

    Do you need an assistant intern with news at work?

  • @IslandbreezeMechanical
    @IslandbreezeMechanical 4 ปีที่แล้ว +2

    Nice work. You can only do so much with an NTE.

  • @wd8557
    @wd8557 3 ปีที่แล้ว

    I always buy two belt's and leave a spare one period I suggest you start doing the same. Belt's are a part that can go bad just like anything else.

  • @sknight0391
    @sknight0391 4 ปีที่แล้ว +2

    I would have checked gas pressure too.
    😎👍

  • @throttlebottle5906
    @throttlebottle5906 4 ปีที่แล้ว +1

    massive temp split, slipping belt lack of airflow (filters BAH who needs to change them!) followed by gas pressure too high lol

  • @gatoguevara71
    @gatoguevara71 4 ปีที่แล้ว +2

    Great vid 👌

  • @armandorodriguez6447
    @armandorodriguez6447 4 ปีที่แล้ว +1

    Good job broski.....come work for a national commercial co.....

  • @FrostBlueFire
    @FrostBlueFire 4 ปีที่แล้ว +1

    Yorks are sketchy as hell to work on, crappy design, absolute garbage units to touch. Filter locations are weird, and repairing them sucks. You did great though bro, for someone who mainly does RACK and refrigeration, you do better than half these techs so far lol. Checking far, it's good. I don't know everything and I'm always willing to learn and teach what I know. Other than the amps, always check, you did a great job. Typically people will leave either a new or used belt as an emergency, just incase one pops, you have a spare to hold them over. One of my first things to check is filters and belts when i have limit switches opening lol. Keep it awesome dude!

    • @rookierefrigeration4357
      @rookierefrigeration4357  4 ปีที่แล้ว +2

      Thanks alot bro. And yup. York’s are kinda low quality😂

    • @leonbogon148
      @leonbogon148 4 ปีที่แล้ว

      Never had certain tools like a manometer--Wasalways rushed in my service ,got shit going and moved on to next call........ nobody gave a shite except me--I still dream/nightmare of certain stores where I could have remedied the problem if I was given 2-3 days alone......Still wish I could go back and r eapair engineering problem--At @ the time I left the Co. -You might as well talk to a brick wall rather than a supervisor...........Peace-

    • @markpayne6803
      @markpayne6803 4 ปีที่แล้ว +1

      In some cases we leave an extra belt because we have a maintenance contract so if we have a bad belt when supply houses are closed it's the least we can do instead of wasting time chasing one did I explain that with some sense

  • @publicmail2
    @publicmail2 4 ปีที่แล้ว +14

    At least amp the motor so you dont burn it up or have it off on over current.

    • @rookierefrigeration4357
      @rookierefrigeration4357  4 ปีที่แล้ว +3

      That’s true. I didn’t do that. Good call

    • @charlesmurphy1510
      @charlesmurphy1510 4 ปีที่แล้ว +1

      Yes, you are correct, adjusting the pulley open or closed effects current in the motor.

  • @gerardorodriguez-uf9rx
    @gerardorodriguez-uf9rx 4 ปีที่แล้ว +1

    You’re not supposed to tighten the pulleys. You’re gonna over amp the motors. The tighter the pulley the more amps. The looser the pulley draws less amps on the motor. FYI.

    • @rookierefrigeration4357
      @rookierefrigeration4357  4 ปีที่แล้ว

      Yes. I agree. So should I not adjust it and leave the unit down?

    • @xraybravo7180
      @xraybravo7180 4 ปีที่แล้ว +1

      But you need to adjusted the airflow though. That's why they are adjustable

    • @jphvac5725
      @jphvac5725 4 ปีที่แล้ว

      @@xraybravo7180 airflow should be correct after just tightening belt, without moving pulley. First bad pulley I’d had turned in maybe half turn and double check amps. Been burned couple times by motors shutting off due to not checking amps after trying to get them by until new pulleys came in.

    • @FrostBlueFire
      @FrostBlueFire 4 ปีที่แล้ว +3

      @@rookierefrigeration4357 Typically a new belt will hold them over until they replace the pulleys. What I do, replace the belt, quote a motor, drive pulley, and a new belt. What you did was fine, just check the amps to be sure you're not going over, and mark the old positioning when you install the new pulleys, so you don't have to play the test and balance game. Sometimes to hold over the customer, you gotta cut things close, and if they fail to act in time, it's on them, especially if given warning.

    • @grindstone5368
      @grindstone5368 4 ปีที่แล้ว +1

      We all do things to get the customers running. Main thing is getting that current measured and knowing exactly where that pulley was set originally so you get the new one correct. Restaurant air balance is never perfect just because of the environment. Always remember though temporary becomes permanent Great video 👍

  • @alansotelo6472
    @alansotelo6472 7 หลายเดือนก่อน

    God bless you bro

  • @TexasStateMechanical
    @TexasStateMechanical 4 ปีที่แล้ว +1

    good job buddy

  • @001tracker001
    @001tracker001 ปีที่แล้ว

    Wait til u get a York Johnson Controls handled with a vfd.

  • @ntsecrets
    @ntsecrets 4 ปีที่แล้ว +2

    Hope you got a free burrito out of it

  • @gingerstrand6153
    @gingerstrand6153 4 ปีที่แล้ว +1

    You be you👍

  • @JorgeRodriguez-wc6th
    @JorgeRodriguez-wc6th 4 ปีที่แล้ว +2

    Lol I just quit a company that Services chipotle

  • @ryanellinger103
    @ryanellinger103 4 ปีที่แล้ว +1

    You still with coolsys/ source or no?

  • @xw3200
    @xw3200 4 ปีที่แล้ว +1

    That job should be done in 3 minutes.

  • @rocker8692
    @rocker8692 12 วันที่ผ่านมา

    Will other techs laugh at me for being a beginner at 50 years old?

  • @throttlebottle5906
    @throttlebottle5906 4 ปีที่แล้ว +1

    hey this isn't refrigeration! =P

  • @steveblake8766
    @steveblake8766 4 ปีที่แล้ว +1

    #306 thumbs up

  • @WisdomInTheWoods
    @WisdomInTheWoods 3 ปีที่แล้ว

    Boyaayayang😆

  • @gerardorodriguez-uf9rx
    @gerardorodriguez-uf9rx 4 ปีที่แล้ว +1

    Good video though.

  • @0ohoaxo0
    @0ohoaxo0 4 ปีที่แล้ว +1

    Just stay away from those nasty chipotle burritos and youre good

  • @juliochavezunacosa4147
    @juliochavezunacosa4147 4 ปีที่แล้ว +1

    Ok change your name to Rookie HVAC