How to Install Smoke and Carbon Monoxide Detectors | Ask This Old House

แชร์
ฝัง
  • เผยแพร่เมื่อ 22 มิ.ย. 2016
  • Scott Caron, master electrician for Ask This Old House, wires an old house with new smoke and carbon monoxide detectors.
    #ThisOldHouse #AskTOH
    SUBSCRIBE to This Old House: bit.ly/SubscribeThisOldHouse
    Steps for How to Install Smoke and Carbon Monoxide Detectors:
    1. Mark the location of each smoke detector on the ceiling.
    2. Use a drill and long, stiff wire to bore a small-diameter hole through the ceiling and into the attic.
    3. Go into the attic and check for obstructions around the small holes. If necessary, use a circular saw to cut open the attic floor.
    4. At each smoke detector location, use a drill and a 4-inch-diameter hole saw with dust shield to cut a hole through the ceiling for a round old-work electrical box.
    5. Run nonmetallic electrical cable from an existing outlet in the attic to each of the smoke detector locations.
    6. Cut the cable and pull it through an old-work electrical box. Push the box into the ceiling hole and tighten the screws to lock the box to the ceiling. Repeat for each ceiling hole.
    7. Screw the smoke detector's mounting plate to the box, then make the wire connections: black to black, white to white, red to orange.
    8. Gently tuck the wires into the box, then twist and lock the smoke detector onto the mounting plate.
    9. Install a combination smoke and carbon monoxide detector on each level of the home and within 10 feet of the bedrooms.
    10. Pull a new electrical cable down from the attic into the basement.
    11. In the basement, install a standard hardwired combination smoke and carbon monoxide detector, and a two-piece wireless smoke and carbon monoxide detector. Mount the battery-powered wireless half of the detector on the first-floor ceiling.
    12. Make the final wire connections in the attic, then test each detector to make sure all of them are operating properly.
    About This Old House TV:
    This Old House is the No. 1 multimedia home enthusiast brand, offering trusted information and expert advice through award-winning television, a highly regarded magazine, and an information-driven website. This Old House and Ask This Old House are produced by This Old House Ventures, LLC and are presented on PBS by WGBH Boston.
    Follow This Old House and Ask This Old House:
    Facebook: bit.ly/ThisOldHouseFB
    Twitter: bit.ly/ThisOldHouseTwitter
    bit.ly/AskTOHTwitter
    Pinterest: bit.ly/ThisOldHousePinterest
    Instagram: bit.ly/ThisOldHouseIG
    Tumblr: bit.ly/ThisOldHouseTumblr
    How to Install Smoke and Carbon Monoxide Detectors | Ask This Old House
    / thisoldhouse
  • แนวปฏิบัติและการใช้ชีวิต

ความคิดเห็น • 363

  • @Kuwandi
    @Kuwandi ปีที่แล้ว +5

    Superb EDITING credits to the This Old house , so much better than every one trying to show how to do it their way ⭐️⭐️✅

  • @RM-lv9ng
    @RM-lv9ng 3 ปีที่แล้ว +8

    There are so many new innovative smoke detectors, the ones installed in this video are dinosaurs.

    • @brandonwilson4281
      @brandonwilson4281 3 ปีที่แล้ว +1

      👙📲🍼💏🍼🚔🍼🌪️💓🍼🌪️

    • @brandonwilson4281
      @brandonwilson4281 2 ปีที่แล้ว

      🔥🌩️🍼😷💕❤️💩💩🛤️📱🔥🍼🇱🇷

    • @DanTDMJace
      @DanTDMJace 3 วันที่ผ่านมา

      He ones here are still pretty good (at least for the US, Europeans are leages ahead of us)

  • @user-Arthxeking777
    @user-Arthxeking777 3 ปีที่แล้ว +3

    needed this to reengineer the fire alarms in my house thank you for the wiring tips

  • @jeffjiao6781
    @jeffjiao6781 ปีที่แล้ว +1

    Thanks for the information Johnny

  • @sarafitzgerald8971
    @sarafitzgerald8971 ปีที่แล้ว +1

    Did you use a 4 inch hole saw to make the boxes to fit? I purchased the blue plastic connection boxes showing in your video.

  • @AndrewThronImprovements
    @AndrewThronImprovements 3 ปีที่แล้ว +2

    Good tips!

  • @abrahamvaro1637
    @abrahamvaro1637 5 ปีที่แล้ว

    very good video ,thanks.

  • @amodelanime2
    @amodelanime2 2 ปีที่แล้ว

    Awesome video thanks

  • @heroknaderi
    @heroknaderi 3 ปีที่แล้ว +1

    Great idea 💡

  • @mauricio6712
    @mauricio6712 8 ปีที่แล้ว +16

    I liked a lot , here in Brazil we do not have that device in the home...... very Good

  • @Tj-cq2nw
    @Tj-cq2nw ปีที่แล้ว

    I’m about to do this soon

  • @bignedu4871
    @bignedu4871 4 ปีที่แล้ว +1

    Thank you for this tutorial.

  • @thomaschristopher8593
    @thomaschristopher8593 2 ปีที่แล้ว +1

    great video. i was able to replace my two smoke detectors. thank you.

  • @lindahernandez2063
    @lindahernandez2063 ปีที่แล้ว

    I like how it catches the dust

  • @eclay432
    @eclay432 3 ปีที่แล้ว +24

    If code requires 2 sources of power to your detectors how do you get away with just a battery operated on the first floor?

    • @ronaldwoofer5024
      @ronaldwoofer5024 2 ปีที่แล้ว +1

      LMAO

    • @drnickriviera8270
      @drnickriviera8270 2 ปีที่แล้ว +3

      If smoke detectors are being installed in a home built prior to the hardwire code requirement than wireless smoke detectors with a non removable 10 year battery can be used. If a house is undergoing extensive renovation which would allow for the routing of hardwire power cables than the new detectors must be hardwired.

    • @mrsliva4156
      @mrsliva4156 2 ปีที่แล้ว

      Lllllllllllllllllllooooooooo

    • @LeroyZee
      @LeroyZee ปีที่แล้ว

      He put a second smoke detector in the basement.

    • @VOLTRONDEFENDER4440
      @VOLTRONDEFENDER4440 11 หลายเดือนก่อน

      @@LeroyZee for backup of smoke detector(late reply)

  • @matrewisdom6017
    @matrewisdom6017 3 ปีที่แล้ว +2

    Can I use normal 3cord x1.5mm flexible cableto wire smoke alarm

  • @amilcarduglasbenites583
    @amilcarduglasbenites583 8 ปีที่แล้ว +1

    que bien.practico.y eficas

  • @PeteBasel
    @PeteBasel 6 ปีที่แล้ว +8

    You said, on the upper floor, that the alarms needed two power sources according to code, then on the first floor you installed a battery only unit. I'm not an expert on the code but is that allowed? Also, you can use bridge units to join a wireless trigger unit to the wired ones.

    • @DaruDhillon
      @DaruDhillon 3 ปีที่แล้ว +1

      When renovating a home it is required to have all smoke and carbon monoxide detectors hardwired, interconnected with back-up batteries. Wireless is a good option, if you are not opening up walls.

    • @PeteBasel
      @PeteBasel 3 ปีที่แล้ว +1

      @jay fine Thanks, that makes sense. My first post here was 3 years ago!

  • @IAmNotAFunguy
    @IAmNotAFunguy 8 ปีที่แล้ว +58

    He never mentioned there are two kind of smoke alarms, ionization and photoelectric. Ionization is better for quickly flaming fires and photoelectric is better for slow smoldering fires, and most fire departments and building codes like them both in the house. The best is a 2-in-1 unit that has both types.

    • @jeremiahsimpkins5943
      @jeremiahsimpkins5943 7 ปีที่แล้ว +1

      IAmNotAFunguy yea he never mention them well I fell bad for this lady thank to Scott

    • @frank_texas7400
      @frank_texas7400 6 ปีที่แล้ว +5

      Now I heard that it burnt to the ground because of him not disclosing every kind of smoke detector there is

    • @NatSpecialOAthlete
      @NatSpecialOAthlete 5 ปีที่แล้ว +1

      this video will explain everything
      th-cam.com/video/714NB7CVrpA/w-d-xo.html

    • @brandonwilson4281
      @brandonwilson4281 3 ปีที่แล้ว

      🍼🚂🔫💰💡🔫👶👙🍼🤰🌪️💩📽️👙👶💰🔫🥋🤰👙🚂🚒❤️💡🍼👨‍👩‍👧🌩️💗🦃🙋🖤🔥📽️🌪️

    • @fartpluswetone8077
      @fartpluswetone8077 3 ปีที่แล้ว +1

      Most combination alarms are Carbon Monoxide and Ionization.

  • @parnika.agarwal
    @parnika.agarwal 3 ปีที่แล้ว +3

    How did you had the wireless smoke detector talking to the fire alarm system with the wires? Can you please tell which model numbers of the first alert were installed in this video?

    • @nick4leader
      @nick4leader 3 ปีที่แล้ว +1

      I think the 2 in the basement are connected to each other and the wireless is connected to one of them

    • @kitty2ism633
      @kitty2ism633 2 ปีที่แล้ว +2

      It uses a wireless type signal to communicate with the one in the basement which will then connect to the second one and send the signal to the rest of the smoke alarms (i know as we have a similar model ours is the sc0500 i believe)

  • @10MohGG
    @10MohGG 4 ปีที่แล้ว +4

    I love how they make everything up

  • @gilzskillz
    @gilzskillz 2 ปีที่แล้ว

    changed my smoked to detectors for same new ones now one in the master bedroom does not sound with the others when testing

  • @pieceofcake2008
    @pieceofcake2008 8 ปีที่แล้ว +1

    Love the show. Always interesting seeing how it's done overseas.

  • @yzmoto80
    @yzmoto80 3 ปีที่แล้ว +6

    @1:30 : “Upp, there it is, right through my knee cap....No worries, I’m ok, I have another one !

  • @baliramdigitech
    @baliramdigitech 2 ปีที่แล้ว

    Nice Device

  • @bigvic1787
    @bigvic1787 2 ปีที่แล้ว

    I see how you wired the fire alarms but how did you wire it into the outlet in the Attic.? I noticed it's a 14-3 Romex so where did you connect the red for power was there a 14-3 already in there? What if it's a 14 -2 that's already existing there?

    • @thatbrownkid9783
      @thatbrownkid9783 ปีที่แล้ว

      I’m sure he pigtailed the hot & neutral from the back of the outlet and didn’t use the red wire

    • @lukekoesler3383
      @lukekoesler3383 3 หลายเดือนก่อน

      The 14/3 red wire is just needed for communication in between devices. It should not be tied into a power source. So a14/2 is your power supply.
      But in this video that means it's not talking to the lower floor devices unless he pulls a new interconnecting wire or uses a remote transmitter of some kind.

  • @roderickarnold1412
    @roderickarnold1412 2 ปีที่แล้ว +7

    Kevin almost just lost a kneecap.

  • @FireDetection101
    @FireDetection101 6 ปีที่แล้ว

    Might use this information when I get my own hardwired Smoke/CO alarms

  • @abbas5438
    @abbas5438 6 ปีที่แล้ว

    That's so informative

  • @garyvanrheenen181
    @garyvanrheenen181 11 หลายเดือนก่อน

    Do all the detectors need to be on the same power source? Can detectors on different floors have different power sources as long as they are all connected to a single red wire running from one the next?

    • @The09creeper
      @The09creeper 10 หลายเดือนก่อน

      They can have different power sources. As long as the interconnect wire is connected they’ll all sound

  • @johnkosheluk1041
    @johnkosheluk1041 3 ปีที่แล้ว

    Boy can't have it any easier then that running wires

  • @floxysfeed4448
    @floxysfeed4448 6 ปีที่แล้ว

    Pls can I get a technical report on this

  • @MODKILLER-od7pk
    @MODKILLER-od7pk 8 ปีที่แล้ว +6

    That's a nice house

    • @brandonwilson4281
      @brandonwilson4281 3 ปีที่แล้ว

      👙👩‍🚒🍼🚧👩‍🚒🍼👙🎸💡⚡🎙️📲🌜🎶💰🚒

  • @baliramdigitech
    @baliramdigitech 2 ปีที่แล้ว

    I also use that type of wiring

  • @seanlyons8053
    @seanlyons8053 5 ปีที่แล้ว

    What type of electrical wire did you use?

  • @samirrebel5473
    @samirrebel5473 ปีที่แล้ว

    Where does the end of the orange wire connect to

  • @Kansasavation
    @Kansasavation 3 ปีที่แล้ว +14

    Pot twist: The metal rod goes through Kevin

  • @koycdjartage2571
    @koycdjartage2571 3 ปีที่แล้ว +1

    Can i wire different brand ?
    I know I have to change the base ..

    • @guidedbygreen1480
      @guidedbygreen1480 3 ปีที่แล้ว +1

      It's preferred they are all same brand to ensure communication, but try it

  • @luigi2018
    @luigi2018 2 ปีที่แล้ว +3

    Imagine that metal rod would drill his knee 😂😂

    • @Jack-vo2sz
      @Jack-vo2sz 2 ปีที่แล้ว +1

      my exact thought "and now it goes straight thru his knee instead" 😂

  • @larrynone6354
    @larrynone6354 ปีที่แล้ว +1

    How many inches from the wall did you measure

  • @MrRubme
    @MrRubme ปีที่แล้ว +2

    The most unrealistic attic I’ve ever seen 😂

  • @POLOAZTECA
    @POLOAZTECA 2 ปีที่แล้ว

    For smoke detectors where exactly in a bedroom go?? Like what's a best location in a bedroom... How far away from vents or it doesn't matter?

    • @gangisspawn1
      @gangisspawn1 2 ปีที่แล้ว +1

      On the ceiling in front of the door. Sometimes one on both sides of the door for extra safety(apartment code).

    • @POLOAZTECA
      @POLOAZTECA 2 ปีที่แล้ว

      @@gangisspawn1 Thanks

  • @mdahshan9936
    @mdahshan9936 5 ปีที่แล้ว

    Superb

  • @kevingordon669
    @kevingordon669 2 ปีที่แล้ว

    Loop you tape into itself, it makes for easy removal, I've heard it call the buddy tab idk just don't get fired

  • @ayanhussain6798
    @ayanhussain6798 6 ปีที่แล้ว +1

    @ThisOldHouse if you mute a detector in one room will if mute all of the others?

    • @10MohGG
      @10MohGG 4 ปีที่แล้ว

      Ayan Hussain no

    • @brandonwilson4281
      @brandonwilson4281 3 ปีที่แล้ว +2

      🍼🔫💡🚧✏️⚡👙

  • @OwYouMoron
    @OwYouMoron 6 ปีที่แล้ว +13

    Imperial Walker spotted at 0:54

  • @gravisan
    @gravisan 2 ปีที่แล้ว +1

    Would be good to know what cables they used? maybe it's 14/3?

    • @lyndoncreps4218
      @lyndoncreps4218 2 ปีที่แล้ว +1

      14/3 is ideal for smoke detectors.

  • @mohamadboodhoo
    @mohamadboodhoo 3 ปีที่แล้ว

    Hi I have noticed the smoke alarm beeping,I have disconnected it from the wire but I noticed the beeping has moved to the ceiling light and its continuously beeping every 5-10 sec 24/7.Any solutions please?
    Thanks

    • @gangisspawn1
      @gangisspawn1 2 ปีที่แล้ว

      Battery needs changing... if you can't figured that out then hire a handyman for ALL issues in the future.

    • @oldtwinsna8347
      @oldtwinsna8347 2 ปีที่แล้ว

      Just find an exact replacement for it if you've done the battery change and it still does it . These have maximum lifespans and some will beep at that point, or they just crap out over time. The same model will fit the existing mount and so it can be swapped out in like 1 minute time.

  • @atkgrl
    @atkgrl 6 ปีที่แล้ว +5

    Great plastic shield, Where can I buy one.

    • @alec4672
      @alec4672 6 ปีที่แล้ว +3

      PlayGirl It's just your standard cheep plastic bowl from the kitchen section with a small hole in the bottom.

    • @atkgrl
      @atkgrl 6 ปีที่แล้ว +2

      Alec Ver Bunker it's a great idea and could be sold as a tool.

    • @alec4672
      @alec4672 6 ปีที่แล้ว +4

      PlayGirl they do sell it as a tool but for much more then it's worth. I use a plastic salad bowl and it works just as well.

    • @brandonwilson4281
      @brandonwilson4281 3 ปีที่แล้ว

      🍼🖤💡⚡🌩️🌩️🍼🔫🥋💰🍼👨‍👦‍👦🍼🔥🚒

  • @generally_good_guy
    @generally_good_guy 4 ปีที่แล้ว +1

    This was a great video. Unfortunately I need to do a hardwired install in the location you put wireless. Any advice on running the cables?

    • @aurvaroy6670
      @aurvaroy6670 3 ปีที่แล้ว

      I'm pretty sure you take the same steps Scott took (run romex from a nearby power source to each location) without having access to an attic. There are plenty of videos showing you how to do that

  • @saud702
    @saud702 8 ปีที่แล้ว +2

    عمل رائع

  • @kickdrum1185
    @kickdrum1185 3 ปีที่แล้ว +1

    Will 12/2 wire work or 12/3. I noticed he had red wire?

    • @aurvaroy6670
      @aurvaroy6670 3 ปีที่แล้ว

      12/3 for alarms with a red interconnect wire and 12/2 for alarms without that extra wire

  • @Dggb2345
    @Dggb2345 3 ปีที่แล้ว +3

    Dude, saw comment about on knees before watching...Lmfao. Laurel & Hardy level potential.

    • @brandonwilson4281
      @brandonwilson4281 3 ปีที่แล้ว +1

      🍼🌪️🔫👙💏🤰🌛🔥👙🕑🚂🍼💡⛈️🔥

    • @brandonwilson4281
      @brandonwilson4281 3 ปีที่แล้ว +1

      ⚡📲🚧🇲🇾💰💑❤️🚒🍼🎸🔊🎤☎️👙📲💰🚒🍼❤️

  • @anafigueroa2463
    @anafigueroa2463 7 ปีที่แล้ว +10

    wonder cost of labor I have to install 6 in my house, and I prefer to be wired

  • @nevrbdwnruby7484
    @nevrbdwnruby7484 6 ปีที่แล้ว +4

    Sending the wires to these devices is cumbersome but there is no way out of it... Great for remodel work but I don't recommend if it was going to be inspected it will be a no pass.. Why? All devices need a dedicated circuit and they all need to be hardwired... That's what happened to me in LA...

    • @leonardholt5311
      @leonardholt5311 4 ปีที่แล้ว

      NevrBDwn Ruby does not need to be on a dedicated circuit.

  • @shahilrabbani5973
    @shahilrabbani5973 6 ปีที่แล้ว +1

    Good

  • @jahidahmed-dg8qr
    @jahidahmed-dg8qr 6 ปีที่แล้ว

    nice

  • @gamebreaker5518
    @gamebreaker5518 3 หลายเดือนก่อน

    why wasn;t the second screw in the first box he wired screwed down?

  • @GalaXy808
    @GalaXy808 8 ปีที่แล้ว

    Wow very nice job,is that a new type of smoke detectors the other one?

  • @gavilanjuarez1053
    @gavilanjuarez1053 6 ปีที่แล้ว +2

    Hey I have question how connect the smoke detector to the breaker box

    • @lmd6204
      @lmd6204 5 ปีที่แล้ว +2

      It is connected to the outlet in the attic which is already connected to the breaker box.

    • @Nick-bh1fy
      @Nick-bh1fy 4 ปีที่แล้ว +1

      gavilan juarez it’s straight 120 line voltage

    • @brandonwilson4281
      @brandonwilson4281 3 ปีที่แล้ว

      🔥🍼🤡💷🔥🇺🇸💡💏🍼🇺🇲🇺🇲

    • @brandonwilson4281
      @brandonwilson4281 3 ปีที่แล้ว

      @@lmd6204 🔥

  • @Pr0gr3ss
    @Pr0gr3ss 3 ปีที่แล้ว

    Is it required to shut off power in the house while attaching those colored 3 wires?

    • @hoivothi1997
      @hoivothi1997 3 ปีที่แล้ว

      Wdt

    • @hoivothi1997
      @hoivothi1997 3 ปีที่แล้ว

      .

    • @hoivothi1997
      @hoivothi1997 3 ปีที่แล้ว

      .

    • @hoivothi1997
      @hoivothi1997 3 ปีที่แล้ว

      ..?..

    • @oldtwinsna8347
      @oldtwinsna8347 2 ปีที่แล้ว

      Definitely turn it off. Only after you got it wired in and have a modular connector for future replacement would you not need to turn power off (works light plugging in socket).

  • @mrseanpride6449
    @mrseanpride6449 3 ปีที่แล้ว +1

    What was the second one for? To get him out of trouble? Are the cops after him?

    • @fatherelijah1763
      @fatherelijah1763 3 ปีที่แล้ว

      😁😁you just made me spill my coffee

  • @fredkachongo3183
    @fredkachongo3183 7 ปีที่แล้ว +1

    very educative

  • @CaptainBill22
    @CaptainBill22 8 ปีที่แล้ว +10

    Correct me if I'm wrong, but the last I heard the NEC says that smoke detectors should be on a separate circuit. I get that you guys did this so it's more user friendly, but the job should be done to code for today.

    • @nofingway1
      @nofingway1 7 ปีที่แล้ว +4

      codes change depending of the country/state.

    • @jc5536
      @jc5536 7 ปีที่แล้ว +2

      If the NEC states it should be on its own circuit ( individual branch circuit ) I would be interested in that chapter and section or if it's an amendment to NFPA 70 written into law and approved in a specific state or commonwealth. I'm almost inclined to point towards NFPA 72 if that even exists.

    • @Sparky-ce9yy
      @Sparky-ce9yy 6 ปีที่แล้ว +2

      Sigvulcanas you are correct. Hard wire smoke detectors must be on one circuit and are NOT allowed to be GFCI or AFCI protected.

    • @ronaldbeal
      @ronaldbeal 6 ปีที่แล้ว +4

      WRONG!!! NEC section 210.12 requires 120v smoke alarms to be on Arc Fault circuits.
      They should be interconnected and on one circuit. There is debate on weather they should be alone on a circuit, or be on a shared circuit. NEC, NFPA, and IRC do not weigh in on the matter. Some state and local AHJ have made a determination one way or another, and they have the final say. The fire prevention community is leaning toward being on a shared circuit, so that if the breaker is tripped, the occupants will be more likely to notice it, whereas if the alarms are by themself, someone might turn off the breaker to silence a false alarm, and then never turn them back on.

    • @ronaldbeal
      @ronaldbeal 6 ปีที่แล้ว +5

      International Code Council Electrical Code (ICCEC) :Section 1202.5 states: "Smoke detectors required by the International Building Code and installed within dwelling units shall not be connected as the only load on a branch circuit. Such detectors shall be supplied by branch circuits having lighting loads consisting of lighting outlets in habitable spaces."

  • @bluesteel5841
    @bluesteel5841 3 ปีที่แล้ว +1

    Because carbon monoxide is slightly lighter than air and also because it may be found with warm, rising air, detectors should be placed on a wall about 5 feet above the floor

    • @DanTDMJace
      @DanTDMJace 2 ปีที่แล้ว

      No, they should be on the ceiling.

    • @The09creeper
      @The09creeper 10 หลายเดือนก่อน

      I would love to see some one actually put a co alarm 5 feet above the ground but no one does it because of aesthetic reasons

  • @priceandpride
    @priceandpride 3 ปีที่แล้ว

    Is it possible to get them all to chirp at the same time?

  • @rajabalaji8918
    @rajabalaji8918 3 ปีที่แล้ว

    We need for this my company

  • @alexxxx334
    @alexxxx334 7 ปีที่แล้ว +4

    ho yes

  • @PBunyanOx
    @PBunyanOx ปีที่แล้ว

    Kevin!!! 🏡

  • @Kuwandi
    @Kuwandi ปีที่แล้ว

    Thanks to this old house addiction 34 yrs ago I bought an old house - lol - it’s a bit older now …lol?

  • @djtippler8259
    @djtippler8259 5 ปีที่แล้ว

    What kind of wire that you use in smoke detector ?

  • @johnkosheluk1041
    @johnkosheluk1041 3 ปีที่แล้ว

    What good is that if thay are not home

  • @_imran_4205
    @_imran_4205 7 ปีที่แล้ว +1

    Plz upload ull episode of this video

  • @_imran_4205
    @_imran_4205 7 ปีที่แล้ว +1

    full episode not availiable in this link

  • @ManleyDestine
    @ManleyDestine 2 ปีที่แล้ว +1

    Aren't fire alarm systems supposed to be on a dedicated circuit?

    • @easyroc75
      @easyroc75 2 ปีที่แล้ว +1

      Some places require a dedicated circuit. He said if someone turned the circuit breaker to the dedicated circuit, no one would know. However, I think the alarm with a battery backup would beep if the AC power is turned off.

    • @ManleyDestine
      @ManleyDestine 2 ปีที่แล้ว

      @@easyroc75 Yes, though the system is supposed to have redundancy. Supposed everyone is awa for a weekend and that circuit trips and battery power goes out within the 24 hour limit or 48 depending on how much juice is in it? Come back don't realize that cicuit is off because it's on a circuit not being used and boom, fire while your family is sleeping.

  • @safekid101firesafetyandexi8
    @safekid101firesafetyandexi8 7 ปีที่แล้ว +4

    I wanted to know that .

  • @stardelta9508
    @stardelta9508 6 ปีที่แล้ว +1

    Wow, i know your code is different from scotland, but why no earth sleeving?? It just makes sense. Any US sparky would learn alot if they worked over here for a few days.

    • @AMD1
      @AMD1 4 ปีที่แล้ว +1

      It's not necessary to have the ground/earh covered since it's not a normal current carrying conductor, and usually bonded to the back of a metal box. North American codes say that the ground/earth must be identified with green insulation, green with a yellow stripe, or bare coper. I believe Australia also has a bare ground/earth conductor in their NM cable/twin and earth.

  • @spencerg3303
    @spencerg3303 2 ปีที่แล้ว +2

    It’s so terrifying to hear a robot voice at night saying warning Carbon Monoxide, especially since it echos the entire house, but I’d rather live than die from Carbon Monoxide

  • @johnathankelley7151
    @johnathankelley7151 4 ปีที่แล้ว +1

    Was there a battery in the wireless one he installed? I didn't see one.

    • @ethanmacias7287
      @ethanmacias7287 4 ปีที่แล้ว

      At 6:12 that's the battery and wireless one he installed

  • @alexandersalarms5380
    @alexandersalarms5380 4 ปีที่แล้ว +22

    7:07 he is using too much smoke, one spray is enough. you will damage it.

    • @Slektus
      @Slektus 3 ปีที่แล้ว +3

      Ikr

    • @razorcool5011
      @razorcool5011 3 ปีที่แล้ว

      Spray

    • @alexandersalarms5380
      @alexandersalarms5380 3 ปีที่แล้ว

      @Anthony Lee The smoke alarm...

    • @brandonwilson4281
      @brandonwilson4281 3 ปีที่แล้ว +1

      🍼🚓🧠🛫🛩️♥️🚑♥️🍼😍🏈🎂💺🎃🧤🔦💡💵🛍️🕯️🙋🚴⛹️🏋️💆🙇👩‍🚒👩‍👩‍👧🌩️🍼🎂🚔🎤📹💡👙🗄️🕞💜🎦🕣🇱🇷🇺🇾💰📲🔴🔵🔊😡😤😠💰📞📲

    • @alexandersalarms5380
      @alexandersalarms5380 3 ปีที่แล้ว

      @@brandonwilson4281 shut up

  • @matth8200
    @matth8200 2 ปีที่แล้ว

    I've always heard that carbon monoxide detectors should be low to the ground, since carbon monoxide sinks. Is this wrong?

    • @TheSgtDabbs
      @TheSgtDabbs ปีที่แล้ว

      It doesn't really matter what height they are at, CO spreads pretty evenly throughout a given area.

  • @dene8989
    @dene8989 3 ปีที่แล้ว

    If battery is moved but powered by wire, will it always chirp?

    • @6string327
      @6string327 3 ปีที่แล้ว

      yes, the battery is only if the power goes out. If it's also hard wired your good.

    • @oldtwinsna8347
      @oldtwinsna8347 2 ปีที่แล้ว

      there's usually voltage monitoring for the backup battery so if it gets old the battery can invoke the chirping to start.

  • @Kirby7601
    @Kirby7601 3 ปีที่แล้ว +1

    Can of smoke is better than the test button

  • @OfficialNewAndImproved305
    @OfficialNewAndImproved305 2 ปีที่แล้ว +1

    I had professionals install 5 of those and it wasn't cheap

    • @cantlean4440
      @cantlean4440 2 ปีที่แล้ว +1

      I'm curious how much it was. I am guessing $80 per unit plus labor and materials. Maybe around $900?

  • @Self_Supremacy
    @Self_Supremacy 5 ปีที่แล้ว +2

    There is jo way i could have been in that attic while he was drilling those rods without screaming " oh god my knee, you drilled it through my knee".

  • @Nine-Signs
    @Nine-Signs 7 ปีที่แล้ว +2

    Bugger the smoke detectors, what were those red terminal caps you were twisting wires together with?
    Ive done electrics for a long time in the UK and have never seen such things before.
    would save time over solder and shrink wrap that's for sure.

    • @nofingway1
      @nofingway1 7 ปีที่แล้ว +2

      en.wikipedia.org/wiki/Twist-on_wire_connector
      super cheap in any hardware store.

    • @nofingway1
      @nofingway1 7 ปีที่แล้ว +2

      www.homedepot.com/p/Wire-Connector-Assortment-25-Pack-775128/202894260

    • @Nine-Signs
      @Nine-Signs 7 ปีที่แล้ว

      thank you :)

    • @jenkins6421
      @jenkins6421 7 ปีที่แล้ว +1

      ArmyOfAll just remember its 110v in the us compared to 220 over there

    • @zakadamson6059
      @zakadamson6059 6 ปีที่แล้ว

      James Jennings not being cocky but letting u know its 240~250 volts. So soldering is a musg

  • @gurmindersingh1424
    @gurmindersingh1424 6 ปีที่แล้ว +3

    My washer is broken and I want a new washer thanks.

  • @omegalpha777
    @omegalpha777 8 ปีที่แล้ว +9

    Quick Question, if a person is hearing impaired and is living alone, how can she/he knows if a fire is starting?

    • @jackdoble2
      @jackdoble2 8 ปีที่แล้ว +12

      They make smoke detectors with strobes, perfect for someone that is hearing impaired.

    • @rdcstyle6612
      @rdcstyle6612 7 ปีที่แล้ว +7

      +bobloblaws911 those vibrator alerts are very handy usually they install them between then individuals private parts for max alertness and stimulation

    • @muscleman569
      @muscleman569 7 ปีที่แล้ว +5

      THEN THEYRE FUUUUCKED!!!!!!!!!!!!!@!!%

    • @atkgrl
      @atkgrl 6 ปีที่แล้ว +1

      Jack where can you buy them?

    • @davidredpath4781
      @davidredpath4781 6 ปีที่แล้ว

      Mark R they make horn strobes for that situation

  • @grantmiller6147
    @grantmiller6147 3 ปีที่แล้ว

    2:20 why did it look like an arc cutting the saw?

    • @Nick-bh1fy
      @Nick-bh1fy 3 ปีที่แล้ว

      Most likely friction from the metal wholesaw against the wood but definitely not an electrical arc

  • @masteryoda7583
    @masteryoda7583 2 ปีที่แล้ว

    So if my cooking sets off my detector how do I turn it off?

    • @AMD1
      @AMD1 ปีที่แล้ว

      Use a shotgun

  • @mannythesavage2
    @mannythesavage2 3 ปีที่แล้ว

    I saw sparks at 2:20

  • @NatSpecialOAthlete
    @NatSpecialOAthlete 5 ปีที่แล้ว +1

    If you want even more information on this subject, see this video!
    th-cam.com/video/714NB7CVrpA/w-d-xo.html

  • @UnionPacificBigBoy-of8xy
    @UnionPacificBigBoy-of8xy 4 ปีที่แล้ว +3

    5:20 First Alert SC9120B

  • @jmachasm8976
    @jmachasm8976 3 ปีที่แล้ว +4

    You installed battery powered smoke detectors down stairs, There’s no place to wire a smoke detector downstairs

    • @brandonwilson4281
      @brandonwilson4281 3 ปีที่แล้ว +1

      🍼👙👩‍🚒💰😠😤🍼👙🌩️💡

  • @speway
    @speway 6 ปีที่แล้ว +1

    No Red FPLR Alarm Cable? Why?

    • @dunnitt
      @dunnitt 6 ปีที่แล้ว +1

      120 volt units . They are not connected to a alarm system

    • @fnhwk
      @fnhwk 4 ปีที่แล้ว

      It's a house, not a hospital.

  • @kevinnaylor5737
    @kevinnaylor5737 3 ปีที่แล้ว +3

    Pretty sure its supposed to be on its own power source. 15 amp arc fault breaker, 14-2 to the first and 14-3 in between others 🤷

    • @ryanwoods4691
      @ryanwoods4691 3 ปีที่แล้ว +5

      No, you are wrong. He said why they share circuits in the video. If the smoke detectors get shut off then you would want to know. So if your master bedroom lights are off, then you know your smoke alarms don't have power.

    • @easyroc75
      @easyroc75 2 ปีที่แล้ว

      @@ryanwoods4691 A smoke detector that has both AC/DC power will beep if the AC power is turned off. Correct?

    • @ryanwoods4691
      @ryanwoods4691 2 ปีที่แล้ว +1

      @@easyroc75 it depends on the model of detector.

  • @kllgrogto5838
    @kllgrogto5838 6 หลายเดือนก่อน

    It would've been easier to patch drywall than repair flooring 😂😂😂

  • @abelluz5698
    @abelluz5698 7 ปีที่แล้ว +1

    11-- how interconnected ?

    • @edduanchavez3346
      @edduanchavez3346 4 ปีที่แล้ว +1

      The red wire connects between the smoke detectors, this red wire is called the signal wire, as soon as one detects smoke it carries the signal to the rest

    • @abelluz5698
      @abelluz5698 4 ปีที่แล้ว

      Treasper Killa thanks, about wireless how take signal to the others?

  • @DCC--vq1ng
    @DCC--vq1ng 3 ปีที่แล้ว

    I think a commercial fire alarm system might be a good choice if you have enough money.The solution can be like this:
    1.unimode 2000 UDLS FACP in basement or garage
    2.fire lite LCD-40 annunciator in entryway
    3.some BG 12LX pull stations installed throughout house.
    4.spectr alert low frequency horn strobes in sleeping areas
    5.gentex horn strobes in living area(tone set to code 3 mechanical or whoop)

    • @alexandersalarms5380
      @alexandersalarms5380 3 ปีที่แล้ว +1

      You must be drunk because this is a house.. not a restaurant

    • @The09creeper
      @The09creeper 10 หลายเดือนก่อน

      A little too over powered. Tho if you want something like that then get a security panel and wire up a few fire zones

  • @bobbygecko
    @bobbygecko 6 ปีที่แล้ว +12

    she blinks way less when scott is taking to her than kevin... weird

    • @fatherelijah1763
      @fatherelijah1763 3 ปีที่แล้ว

      😁😁

    • @user-Arthxeking777
      @user-Arthxeking777 3 ปีที่แล้ว +1

      XD lmfao

    • @alexsahib5669
      @alexsahib5669 2 ปีที่แล้ว

      Blink rate tends to increase when people are thinking more or are feeling stressed

    • @brandonwilson4281
      @brandonwilson4281 2 ปีที่แล้ว

      🍼🧑‍🚒💖🍼💏💏🍼🧑‍🦲🍼🔪🔪👱‍♀️🍼🎂

    • @brandonwilson4281
      @brandonwilson4281 2 ปีที่แล้ว

      @@alexsahib5669 🍼👱‍♀️🎂🍼🥞🎂🍼🙄👨‍👩‍👧‍👧🎂🍼👱‍♀️👭👱‍♀️🔪💏