Diesel Generator fuel consumption | Diesel consumption of DG

แชร์
ฝัง
  • เผยแพร่เมื่อ 19 พ.ค. 2023
  • In this video, we will learn to calculate per hour fuel consumption of diesel generator (10kVA to 1000KVA) at various load level i.e. 100%, 75%, 50%, & 40%. An obvious question when looking at buying a diesel generator is, how much fuel do they consume? Generator has a fixed RPM so we can work out how much fuel they will use across various load levels approximately? Actual usage may vary due to a number of factors so specific calculation method of the fuel consumption of diesel genset from capacity 10kVA to 1000kVA as under;
    Most generator manufacturers use G/kWh as parameters, which mean how many grams (G) of oil the Genset consumes per kilowatt per hour? & then change unit to liters (L) to know that you are an hour Fuel consumption costs.
    Generally, the fuel consumption of diesel genset is calculated according to 0.2-0.26kg/kWh. One liter of diesel is about 0.84-0.86 kg. Then 1KW per hour is 0.2-0.26kg divided by 0.84 = 0.238 liters-0.3 liters, multiplied by kilowatts equals to fuel consumption per hour.
    So Genset consumes 0.26 Litres of diesel per kWh produced considering frictional losses & other factors.
    .
    .
    .
    #dg
    #engine
    #dieselengine
    #dieselgenerator
    #generator
    #dgset
    #gcet

ความคิดเห็น • 54

  • @junaidsultan8687
    @junaidsultan8687 ปีที่แล้ว +1

    Very informative and also verified through IOT fuel monitoring solution.❤ Keep it up Sir❤

  • @zeeshan9888
    @zeeshan9888 ปีที่แล้ว +1

    Thanks sir g

  • @SahilKhan-in4gd
    @SahilKhan-in4gd 6 หลายเดือนก่อน +1

    Nice information thanks 🙏🙏🙏

  • @muzaffarshabir5937
    @muzaffarshabir5937 ปีที่แล้ว +2

    Nice, very informative..

  • @muhammadtauqeer8717
    @muhammadtauqeer8717 ปีที่แล้ว

    V informative

  • @djtarunverma6743
    @djtarunverma6743 11 หลายเดือนก่อน +1

    Bahut achhi jankari diye ho sir ..ye formula to Google me bhi nai milega 😊

    • @mechanicalengineeringpract140
      @mechanicalengineeringpract140  11 หลายเดือนก่อน

      Thanks my dear, kindly share with your Friends
      Pls also watch oil change frequency of diesel generator

    • @mechanicalengineeringpract140
      @mechanicalengineeringpract140  11 หลายเดือนก่อน

      Oil change link is
      th-cam.com/video/noLhkpM-m2s/w-d-xo.html&feature=share9

    • @mechanicalengineeringpract140
      @mechanicalengineeringpract140  10 หลายเดือนก่อน

      th-cam.com/video/YOSazz-bUwQ/w-d-xo.htmlsi=turwULRsUC94GPWp
      Kindly watch this newly uploaded video on bearing basics may be helpful for you
      Best regards

  • @djsjsjjsbsbsbdbdb5970
    @djsjsjjsbsbsbdbdb5970 8 หลายเดือนก่อน +1

    Thanks

  • @jyotirmoyghosh95
    @jyotirmoyghosh95 11 หลายเดือนก่อน +2

    Dhanabad

    • @mechanicalengineeringpract140
      @mechanicalengineeringpract140  10 หลายเดือนก่อน

      th-cam.com/video/YOSazz-bUwQ/w-d-xo.htmlsi=turwULRsUC94GPWp
      Kindly watch this newly uploaded video on bearing basics may be helpful for you
      Best regards

  • @sheshnathsingh9465
    @sheshnathsingh9465 2 หลายเดือนก่อน +1

    HEMM engine ka bhi banao

  • @shanugaur8218
    @shanugaur8218 3 หลายเดือนก่อน +1

    Q1 Is this conversion factor of 0.26 ltr Per unit applicable to all Kinds of DG Sets ( Greaves , Ashok Leyland , Cummins )
    Q2 How did you arrive at this conversion factor of 0.26 ltr/Unit.

  • @AyanJani-ox6zc
    @AyanJani-ox6zc 4 วันที่ผ่านมา +1

    Sir 25 kv Ka generator hai .. rpm 20 par hai km Kaisy Hoga

    • @mechanicalengineeringpract140
      @mechanicalengineeringpract140  3 วันที่ผ่านมา

      20 rpm NAHI hota. DG normal RPM are 1500 and high upto 1800.
      It can control from AVR by resitting frequency at 50HZ if is is not adjusted to desire rpm, pls check governor functioning and also check fuel injection system thoroughly and calibrate if required. oil pump malfunctioning also shows this problem, check rotor chrome of pump as well
      Best Regards

  • @rajeshbariki8266
    @rajeshbariki8266 3 หลายเดือนก่อน +1

    Sir to convert kva to kw 0.8 stand for??

  • @CeyhunAbasov-lq8pr
    @CeyhunAbasov-lq8pr 2 หลายเดือนก่อน +1

    If I run a 20kva diesel generator at 0%, does it use more or less fuel?

    • @mechanicalengineeringpract140
      @mechanicalengineeringpract140  2 หลายเดือนก่อน

      It will be run in underload which is not recommended due to more torque required. Less 40% is underload consuming high fuel and more than 75% is overload, will also consume more fuel so safer range is 40% to 75% load on genset in term of efficient fuel consumption and also to avoid erosion in moving n mating parts of dg
      Best regards

  • @user-jw2ky9yc3e
    @user-jw2ky9yc3e 11 หลายเดือนก่อน +1

    Sir,koi v DG ho uska normal fuel consumption, 0.26 hi hota hai??

  • @rakeshdalai7005
    @rakeshdalai7005 3 หลายเดือนก่อน +1

    But bhai 1 unit ko kese 0 .26 diesel consumption higa malum nehne hua pls thoda expelain kejeye

    • @mechanicalengineeringpract140
      @mechanicalengineeringpract140  3 หลายเดือนก่อน

      It is conversation factor which is taking into consideration while assembling of any DG by oem manufacturer
      Best regards bhaiya

  • @sachingaikar1197
    @sachingaikar1197 ปีที่แล้ว +2

    Hi sir 0.26 per kwh per diesel use hota he lekin 0.26 he kya he or kahase liya

  • @BHAGWANGOYAL-nv6wl
    @BHAGWANGOYAL-nv6wl 3 หลายเดือนก่อน +1

    20% load par kitana consumer hoga

    • @mechanicalengineeringpract140
      @mechanicalengineeringpract140  3 หลายเดือนก่อน

      It is not recommended to use any Genset on 20% load. safer range is 40% to 75% connected load on Genset and fuel consumption will be calculated as described in video.
      At 20% load, generator will run on underload ,will produce more torque resulting more fuel consumption as per recommended factor of 0.26
      Best Regards

  • @g.gunanithi4354
    @g.gunanithi4354 5 หลายเดือนก่อน +1

    How come 0.26 Please let meknow sir.

    • @mechanicalengineeringpract140
      @mechanicalengineeringpract140  5 หลายเดือนก่อน

      It is factor which is used to calculate capacity of any DG while assembling by OEM manufacturer
      Best Regards

  • @debasisdas9667
    @debasisdas9667 3 หลายเดือนก่อน +2

    0-40% pe jyada fuel consumption kiun kartahe ?

    • @mechanicalengineeringpract140
      @mechanicalengineeringpract140  3 หลายเดือนก่อน

      Torque load is increased when we operate DG underload at less than 40%. In this case DG takes definitely high fuel than recommended
      Best Regards

    • @CeyhunAbasov-lq8pr
      @CeyhunAbasov-lq8pr 2 หลายเดือนก่อน +1

      @@mechanicalengineeringpract140What is the main reason for low consumption of diesel fuel?

    • @mechanicalengineeringpract140
      @mechanicalengineeringpract140  2 หลายเดือนก่อน

      There are many factors involved for less fuel consumption
      1. DG working with in safe operating range i.e. 40% to 75% load. Beyond this range, will result more fuel consumption, erosion in moving parts etc.
      2. Calibration of fuel injection system when required
      3. Timely oil change as per recommended frequency of particular DG whatever it is.
      4. Balanced connected load on three phases. Unbalanced connected load like phase one-100A, phase two-140A, phase three-90Amp which is not recommended so all phases load should be equally distributed like phase one=100Amp, phase two=100Amp, phase three= 100Amp
      5. DG consume engine oil due to eroded rings, pistons,liners, valves etc. so DG should be got top end or major overhaul depending upon requirements
      Best Regards

    • @CeyhunAbasov-lq8pr
      @CeyhunAbasov-lq8pr 2 หลายเดือนก่อน +1

      @@mechanicalengineeringpract140 Çox sağ ol. Generator test rejimində işləyirsə, daha çox və ya az yanacaq sərf edəcək?

    • @mechanicalengineeringpract140
      @mechanicalengineeringpract140  2 หลายเดือนก่อน

      @@CeyhunAbasov-lq8pr I don't understand your language also this message have no any easy translate option

  • @mdabuzafar5958
    @mdabuzafar5958 7 หลายเดือนก่อน +1

    It's for kirloskar dg

  • @Lokeshkumar-lf5kt
    @Lokeshkumar-lf5kt 7 หลายเดือนก่อน +1

    .26 kya h
    Iska samajh nhi aaya

    • @mechanicalengineeringpract140
      @mechanicalengineeringpract140  7 หลายเดือนก่อน

      It is factor for designing of any capacity fc. Gensets are assembled considering this factor of FC
      Best regards

  • @purushottamraj1
    @purushottamraj1 3 วันที่ผ่านมา +1

    Bhai urdu mein kyon bol rahe ho english mein bol detey samajh nahin aaya kuchh points