What are the most common electrical mistakes made ? for a Wall Rough

แชร์
ฝัง
  • เผยแพร่เมื่อ 26 ธ.ค. 2024

ความคิดเห็น • 31

  • @Sk8n2Enjoi
    @Sk8n2Enjoi 15 ชั่วโมงที่ผ่านมา +1

    I'm on vacation and don't have my code book handy. At minute 2:31 you indicate/imply that it is a violation that they don't have 240V GFCI protection on their temp panel. I'm curious about your interpretation of this. The panel is receiving 240V and has a two pole main disconnect breaker but the only circuits I see run are the two 120V GFCI protected circuits. If a 240V circuit had been run from the panel for higher voltage construction equipment, I would conclude it is that circuit which requires the GFCI protection. I look forward to your insight.

  • @Devin-_-
    @Devin-_- วันที่ผ่านมา +7

    Jesus, what’s with all the outdoor outlets?

    • @jay9308
      @jay9308 วันที่ผ่านมา +3

      Lol I was thinking the same thing. Are they planning on putting up 16 miles of christmas lights?

    • @toolsandtactics
      @toolsandtactics  23 ชั่วโมงที่ผ่านมา +2

      @Devin-_- if it is my house, I'd probably do the same thing though. You never know. cheap to add now

  • @johnmichael642
    @johnmichael642 วันที่ผ่านมา +4

    As I understand it the 20amp GFCI bathroom receptacle can serve the entire bathroom (lights, fan) as long as it only serves that bathroom

    • @toolsandtactics
      @toolsandtactics  23 ชั่วโมงที่ผ่านมา

      @johnmichael642 you know now that you mention it, I might be wrong about that. Let me check thanks

  • @AntonioRamirez-xg5ce
    @AntonioRamirez-xg5ce 16 ชั่วโมงที่ผ่านมา

    In my area, you’re allowed to fill the 7/8 hole ass tight as you want. They took away the de rating for nm cable. Also the bathroom outlet can be on with the lights in the bathroom as well. Just needs to be a dedicated circuit.

  • @gabequeiroga4471
    @gabequeiroga4471 วันที่ผ่านมา +4

    Fire caulk / fire stop anywhere?

    • @toolsandtactics
      @toolsandtactics  23 ชั่วโมงที่ผ่านมา

      @gabequeiroga4471 no, the builder is going to do that himself
      But you're right.It should be there before they close the wall

  • @kdubs3
    @kdubs3 วันที่ผ่านมา +3

    those automatic wire twist tools are all fun and games until you have to rewire something.

    • @toolsandtactics
      @toolsandtactics  23 ชั่วโมงที่ผ่านมา +1

      @kdubs3 yeah, I think the basics should certainly be taught before you start using one of those, but they're okay in moderation
      Using a driver with a clutch helps a lot

    • @jltaco85
      @jltaco85 11 ชั่วโมงที่ผ่านมา

      Good thing the company i work at uses wagos for all make ups. Those 6 and 8 wire connection wagos are a time saver.

  • @jolyonwelsh9834
    @jolyonwelsh9834 3 ชั่วโมงที่ผ่านมา

    At 3:37 I use wago 221 levernuts. They are great for that many neutrals.

  • @georgezloitro5702
    @georgezloitro5702 วันที่ผ่านมา +4

    Why is it all 12 to Romex what about some 14/2 everyone's a 20 amp circuit

    • @jay9308
      @jay9308 วันที่ผ่านมา +4

      Agreed. If you can afford to have your entire house wired with #12, you should be able to afford a better electrician lol

    • @toolsandtactics
      @toolsandtactics  23 ชั่วโมงที่ผ่านมา +2

      @jay9308 that's a good point, if I was building my own house.Though, for the total cost, I would just use number twelve on every circuit myself

  • @sku32956
    @sku32956 วันที่ผ่านมา +2

    Yeah, I was thinking the screws in😊 the outside boxes weren’t too bad but if they’re not hitting any meat and just hit the siding that is bogus that will loosen up for sure

    • @toolsandtactics
      @toolsandtactics  23 ชั่วโมงที่ผ่านมา

      @sku32956 because it's not for a municipality and it's for an individual.( I know the guy that is building the house.) I think he's going to foam the walls, so this will likely be okay
      But it could potentially push the boxes out of the wall when he foams, l o l
      That's why I was not too thorough and critical during this inspection. As far as how many romex in each hole. Ect.
      But yeah, it's not done right

  • @MakeWithMike
    @MakeWithMike 2 วันที่ผ่านมา +3

    I'll be needing some guidance, Def researching electrician videos for a demolition I have coming up at a affordable health clinic in Palm Bay Florida, wish me luck 🙏

    • @toolsandtactics
      @toolsandtactics  23 ชั่วโมงที่ผ่านมา

      @MakeWithMike i've got a few videos on healthcare. If you're going back with healthcare, wiring it would definitely save a lot of people time.If you have any questions, let me know

  • @bassblastersc1094
    @bassblastersc1094 17 ชั่วโมงที่ผ่านมา

    Seeing Cocina (kitchen) written on the NM speaks volumes on the caliber of “electricians” they have working there.

  • @yessir640
    @yessir640 19 ชั่วโมงที่ผ่านมา

    Would Love to see more Electrical Rough in inspections from you, Good and Bad ones.

  • @jay9308
    @jay9308 วันที่ผ่านมา

    How would you go about 240volt GFCI protection at the temp panel if they don't have any 240volt loads?

    • @toolsandtactics
      @toolsandtactics  วันที่ผ่านมา +1

      @jay9308 they must provide 1 plug if the panel has the capability for 240 a plug must be provided so no one tries to make it
      Some companies are scheduled months in advance and are only there for 1 day to do one job, and they must have the power when they need it. So sometimes they take the cove off and try to make it. It's a safety hazard.

  • @Apache-Helicopter-Life
    @Apache-Helicopter-Life วันที่ผ่านมา

    2/0 CU 175a at 75 degree Column because terminations are rated as such and it’s SE? It would be 135a if it was AL, lemme know if that’s even close to right. 310.15(B).

    • @toolsandtactics
      @toolsandtactics  23 ชั่วโมงที่ผ่านมา

      @@Apache-Helicopter-Life yeah that's correct.
      We have the eighty three percent rule in effect here as well.Because it's a residence.
      As far as the copper goes, I'll have to look at the aluminum. When I get a chance
      Eighty three percent of two hundred is. 166.
      So any wire capable of delivering over 166 is good to go.

  • @ChrisCeinar
    @ChrisCeinar 12 ชั่วโมงที่ผ่านมา

    Nail plates

  • @hunterstark9556
    @hunterstark9556 วันที่ผ่านมา

    Damn
    Seen better, but I’ve seen worse.

  • @ChrisCeinar
    @ChrisCeinar 12 ชั่วโมงที่ผ่านมา

    Electricians never bond boxes? Hater

  • @russrockino-rr0864
    @russrockino-rr0864 วันที่ผ่านมา +2

    All around, a lazy, sh*tty job! Missing lots of nail plates. Outside boxes should be stubs to later add cut-in boxes or put on nail on boxes at rough, Ideal twister wire nuts instead of junk wirenuts. Why so much 12-2, where 14-2 would be more than adequate? Box make up is very messy! Too many romex cables through holes in studs and Top plates! Should have Cable Stackers(not code of course, but good practice) above multi-gang boxes,IMO. Forgetting to remove main bonding jumper screws in sub panels(Take them with you folks and put them in your van with subs), for getting to install them in service panels! Bushing instead of proper SER connector! Strap missing on Liqiud-tite! Bushings instead of proper NM Connectors on top of panel! Missing Receptacle Boxes? Missing mud ring for U-Fer Ground connection. J-box in attic is accessible, just not readily accessable.(IMO). Homeowner or Builder might be a real tight-wad too! Might be unsupervised apprentice too! Neither are an excuse! Thanks, Russ, 29 years in Electrical Trade.

    • @sku32956
      @sku32956 วันที่ผ่านมา

      It looks like a bang up job by the low bid. I can’t believe the way they butchered those outside boxes are just a box in general.