  • Schneider Altivar ATV71, displaying nLP and SCF2 fault when command to run. Disassembled, troubleshooted, replaced faulty components and tested ok.
    Additionally, by clicking and buying any products from the below link will earn me a commission. kol.jumia.com/...
    Disclaimer: The products is not my own idea neither do I designed, create, manufactured or supply it. Therefore, any damage, deformity or low appearance quality observed in the course of purchase is done at owners risk.

ความคิดเห็น • 7

  • @texugodomel3454
    @texugodomel3454 ปีที่แล้ว +3

    Tnks 🙏

  • @AzamatChisamov
    @AzamatChisamov 7 หลายเดือนก่อน

    Здравствуйте, скажите пожалуйста как устранить ошибку PRA?

    • @renew6255
      @renew6255  7 หลายเดือนก่อน

      PRA means there is loss of control voltage 24V supply. Check with a multimeter on the terminal link to the ground terminal if 24V is present in PWR terminal and the internal 24V terminal.

  • @rajulg1036
    @rajulg1036 ปีที่แล้ว

    Hello, I have same inverter & same problem, what can I do, if I used dc 440v then same problem, please tel me, thanks.

    • @renew6255
      @renew6255  ปีที่แล้ว

      What's the inverter displaying on the screen?

    • @renew6255
      @renew6255  ปีที่แล้ว

      Since I haven't heard from you for the nLP fault try DIY by removing the electronics board clean it look for any ring spot and re- solder then remove all the visible plugs and re-socket in case of any partial contact.
      For SCF2 fault, check for insulation breakdown on the output side of the inverter towards the motor and if all correct try replacing the filters.