Balanced (Symmetrical) Fault Analysis - Part 1 of 3

แชร์
ฝัง
  • เผยแพร่เมื่อ 17 ต.ค. 2024

ความคิดเห็น • 59

  • @eepower
    @eepower 7 ปีที่แล้ว +4

    Simple, clear and amazing.! Keep making them good videos. They truly help a lot of ppl

  • @sizwenkosi5218
    @sizwenkosi5218 3 ปีที่แล้ว

    is it an sign error when you add the 0.3+i0.52-i10.23 = 0.3+j9.71 or I am missing some concept ?

  • @shashankcholleti8855
    @shashankcholleti8855 ปีที่แล้ว

    sir in problem 1 the impedance of the generator need to be neglected right , why cannot we calculate the line reactance taking into account

  • @ricorenato5291
    @ricorenato5291 4 ปีที่แล้ว +1

    Your operation in division was wrong you cant divide polar form to rectanguLarform. Convert tha polar form to rectangular form then divide bythedinominTor by. j 0.25 simply 1(cos0+j sin0) multiply both numerator and dinominator by -j0.25

  • @Sobzz_Poetaster
    @Sobzz_Poetaster 7 ปีที่แล้ว +2

    Thank you Sir. You lectures have rescued me and my career. You're much more than just being Awesome :)

  • @adambodom
    @adambodom 7 ปีที่แล้ว

    hye sir. i want to clarify.For the second example If = net current = 0.3 + j3.48 pu after considering the load current, Io?.
    without conaidering the load, If -j4 pu?

  • @SebaAbhilasha
    @SebaAbhilasha 5 ปีที่แล้ว

    Sir, why you kept the bus voltage on the generator side 1

  • @PrabathAthurupana
    @PrabathAthurupana 4 ปีที่แล้ว

    A 250 MVA, 13.8 kV star connected with the neutral connected to the earth through a reactance, is
    connected to a 250 MVA, 13.8 kV/220 kV transformer. Primary and secondary windings of the
    transformer are star connected with neutral point is solidly grounded. Generator reactances are : X”
    =0.2 pu, X’=0.3 pu, X2=0.2 Xo=0.1 p.u., Xn=0.05 p.u. Positive, negative and zero sequence reactance of
    the transformer is 11%.A single line to ground fault is developed at the high voltage side of the
    transformer . Calculate:
    a) Fault current during sub-transient period
    b) Voltage at the generator terminals during sub transient period
    c) Fault current during transient period
    d) Voltage at the generator terminals during transiwnt period
    How solve this question

  • @RaviShankar-db5jc
    @RaviShankar-db5jc 7 ปีที่แล้ว

    sir,in the last question,we have used Xd" for both prefault and post fault condition (but you said earlier that Xd" is used post fault only).Can you clarify?

  • @sanjeevrana8317
    @sanjeevrana8317 4 ปีที่แล้ว

    I have a long-pending query.
    1. For a balanced 3 Phase, positive phase sequence components current in Fig. (or diagram) show the direction of rotation in ANTI-CLOCKWISE direction and mention RYB. But, in moving ANTI-CLOCKWISE direction, sequence to face first IR1 further IB1 and at last IY1
    2. Similarly for balanced negative sequence components current in Fig. (or diagram) show the direction of arrow ANTI-CLOCKWISE direction and mention RBY. But, in moving ANTI-CLOCKWISE, sequence to face IR2 further IY2 and at last IB2
    It is not understandable.
    Till now, in every power system book, this is mentioned. For your ready reference, Page 424 from Power System VK Mehta.

  • @Yusuf-dx4hw
    @Yusuf-dx4hw 2 ปีที่แล้ว

    Thank you Sir, greetings from Ankara,Turkey

  • @diwashbhandari329
    @diwashbhandari329 7 ปีที่แล้ว +12

    at 30:33, you calculate pu of real power (12 Mw) and at 31.19 you are considering it as apparent power.....i think you need to correct your question ...12 Mw should be 12 MVA ..if i m not wrong.

    • @habibaghasafari2237
      @habibaghasafari2237 7 ปีที่แล้ว

      I thought the same thing.

    • @travelwithme1808
      @travelwithme1808 6 ปีที่แล้ว +2

      Diwash Bhandari exactly it must be ratio of 24 MVA/20MVA = 1.2 pu for load then further we will solve

    • @ashutoshjaiswal7524
      @ashutoshjaiswal7524 6 ปีที่แล้ว

      yes it has to MVA/MVA

    • @varuntejreddy5912
      @varuntejreddy5912 5 ปีที่แล้ว

      yes me too find the same mistake

    • @ambushtunes
      @ambushtunes 5 ปีที่แล้ว

      I think ur right.... What he got was p.u of apparent power I think

  • @sungmopark0405
    @sungmopark0405 6 ปีที่แล้ว

    Could you explain why symmetrical fault
    L-L-L-G and L-L-L is same?

  • @adambodom
    @adambodom 7 ปีที่แล้ว

    hye sir.at 33:47, you use the formula I= Sconj/ Vconj.Just wondering since we are doing 3 phase calculation should there be a square root of 3 somewhere? Same for LF I saw S= VIconj. No square root of 3.

    • @pradeepyemula6015
      @pradeepyemula6015  7 ปีที่แล้ว

      I used the formula I_pu = conj(S_pu)/conj(V_pu) that means i am calculating everything in per unit. So sqrt(3) is not required. Root 3 will come when you want to convert the pu value to actual value.

    • @adambodom
      @adambodom 7 ปีที่แล้ว

      thanks sir.at first I thought it was due to the fact balance 3 phase can be analysed using 1 phase circuit. As long as we use pu, no square root of 3 involves?

    • @pradeepyemula6015
      @pradeepyemula6015  7 ปีที่แล้ว

      see this th-cam.com/video/BGor7OKJSyw/w-d-xo.html

    • @adambodom
      @adambodom 7 ปีที่แล้ว

      tqsm for the video

  • @manavmanishbhatnagar8967
    @manavmanishbhatnagar8967 ปีที่แล้ว

    at 30:00, isnt P= 12 MW? why have we taken it to be S?

  • @RaviShankar-db5jc
    @RaviShankar-db5jc 7 ปีที่แล้ว

    In Q1 we are getting fault current with negative sign.Does that mean current is flowing from ground to the generator.And if yes how this is possible??
    if time permits please reply sir

  • @zhibinzhou9471
    @zhibinzhou9471 6 ปีที่แล้ว

    Thanks for this good lecture first ! I have a quetion at 33:15 when you caclulate the line current I, for this 3-phase system it is supposed that V is the line-to-line voltage, therefore S=sqrt(3)*V*I_conj. So when we calculate the complex current, I should = S_conj/(sqrt(3)*V_conj).....not S_conj/V_conj

  • @adambodom
    @adambodom 7 ปีที่แล้ว

    Hye Sir.
    To clarify; if load is considered we use superposition method and if load is not considered we use normal thevenin theorem?

  • @kishennathangunalethcemy296
    @kishennathangunalethcemy296 7 ปีที่แล้ว

    Sir just want to clarify,the load power is in MW and if we divide with Sbase we will obtain the real power right???

  • @rajarapunagarajuyadav8686
    @rajarapunagarajuyadav8686 7 ปีที่แล้ว

    sir at 22.30 why j0.1 is included after bus 1 , but actually it has to be before bus1 am i right sir ??

    • @pradeepyemula6015
      @pradeepyemula6015  7 ปีที่แล้ว

      again I made a mistake, bus 1 should be after j0.1.

    • @NAVEENDUBEYMUSIC
      @NAVEENDUBEYMUSIC 7 ปีที่แล้ว

      sir but that will hardly effect the calculation as the fault to be found out is at bus2 or at the load end..(load here is 0) ?

  • @VikramSingh-le8pc
    @VikramSingh-le8pc 7 ปีที่แล้ว

    sir ,why we neglect the effect of saliency during fault analysis??

  • @Buranku-go3wu
    @Buranku-go3wu 5 ปีที่แล้ว

    At 47:02 why you neglect the left side ?

  • @mohammadhabibullah5882
    @mohammadhabibullah5882 5 ปีที่แล้ว

    Very nice explanation. Highly appreciated

  • @rajarapunagarajuyadav8686
    @rajarapunagarajuyadav8686 7 ปีที่แล้ว

    at 48.26 at net current angle 2.79 is not considered why sir?

    • @pradeepyemula6015
      @pradeepyemula6015  7 ปีที่แล้ว +2

      You are write... I made a mistake in the video. that 2.79 degrees should be considered. In fact I made 2 mistakes at end.

  • @krishnasimhavemulapalli7124
    @krishnasimhavemulapalli7124 7 ปีที่แล้ว

    at 36 min of lecture .can u please explain the flow of current and reactive power

  • @NAVEENDUBEYMUSIC
    @NAVEENDUBEYMUSIC 7 ปีที่แล้ว

    sir at 43.41 u said that we have taken bus volatge at node B u have said to consider the potential at 1.0 pu and the overall potential differece will come out to be zero volts..i do agree with that sir...but why havent we considered the potential at bus b when we were calculating for yV2 ..please explain sir..?

    • @robbiegreen2164
      @robbiegreen2164 6 ปีที่แล้ว

      Superposition theory states that any voltage source must be considered individually (which he has done) and whilst doing so, all voltage sources should be replaced by a short circuit, considering explicitly only one source at a time and adding up the individual contributions. Therefore it is in fact xV2 that in my opinion has not been calculated correctly. Pre fault Voltage at bus b should be short circuit for purposes of superposition analysis, exactly as was done when he calculated YV2.

    • @robbiegreen2164
      @robbiegreen2164 6 ปีที่แล้ว

      *all other voltage sources

  • @keshaverande9176
    @keshaverande9176 6 ปีที่แล้ว

    Sir can you make a video for unbalanced fault
    I mean for Unsymmetrical fault analysis??

  • @rafaelleon9797
    @rafaelleon9797 7 ปีที่แล้ว

    I didn't understand the way you transformed load power into PU! I think you assumed it as MVA not MW! Please, I'll appreciate your clarifying Sir! Thanks for your magnificent examples and explanations!

    • @medolab-e3n
      @medolab-e3n ปีที่แล้ว

      do you have an idea for the reason why he did that?

  • @sohailjanjua123
    @sohailjanjua123 3 ปีที่แล้ว

    Hi Pradeep, I like your lecture

  • @ambushtunes
    @ambushtunes 5 ปีที่แล้ว

    When calculating voltage drop why did you do this... I*j0.15 ...i got lost there

  • @ferdinandgalut5798
    @ferdinandgalut5798 5 ปีที่แล้ว

    thank you sir i understand
    my report next week is about fault analysis

  • @ramziamineboukoullab778
    @ramziamineboukoullab778 6 ปีที่แล้ว

    thank you so much may allah protect you please make exemples for unbalanced fault analysis please i need it in my project please respect from your algeria student

  • @hayredinyasin8520
    @hayredinyasin8520 2 ปีที่แล้ว

    Thanks for your help

  • @muneerimran8919
    @muneerimran8919 4 ปีที่แล้ว

    Thank and it is so usefull for me

  • @juweleee8923
    @juweleee8923 6 ปีที่แล้ว

    i saw some of ur tutorial but u doing wrong calculation again and again... first see some tutorial how to do calculation

  • @berktaskin35
    @berktaskin35 6 ปีที่แล้ว +1

    this video us nothing but helpfull

  • @adambodom
    @adambodom 7 ปีที่แล้ว

    new vids...nice

  • @aswin972
    @aswin972 2 ปีที่แล้ว

    @47:43 error

  • @AbdulRazak-pr9ce
    @AbdulRazak-pr9ce 4 ปีที่แล้ว

    thannks

  • @renuabi7417
    @renuabi7417 7 ปีที่แล้ว

    Thank u sir

  • @satishwagh879
    @satishwagh879 7 ปีที่แล้ว

    thanks