Sir ek dout tha. Aap bol rahe ho ki circuit breaker abnormalities sence nhi karta. Use tripping command relay provide karta hai. To fir mcb ke case mai mcb to apne aap current badhne par trip ho jata hai. Aisa q sir please reply me
Sir you say that CB in not a sensing divice.... When short circuit and over load condition occurred in our circuit then MCB close our circuit... So can you explained MCB is not a circuit breker
Nice explanation sir i hv question if in line momentory 10,000 Amps current flow then 100 Amps will flow on ct secondary? So what about protection of relay and amp meter from high secondary current?
measuring CT will be saturated therefore meter will be protected... whereas protection purpose CT will be used to operate at 40-50 times of full load current there for during this time protection devices comes into picture and further operation will take place..above that current protection CT will be also saturated...
Sir we knw relay is used for switching purpose which make contact and break contact , but ur saying relay is sensing device and gives signal to circuit breaker. Sir can u cleare this doubt plz.
Sir ji....i have 1 doubt please clarify....at our 22 KV Incoming Breaker, Schneider Electric's Micom P122 relay is there, few days back 1 alarm noticed like- I> 1/1 Phase L1 L2 L3 Kindly elaborate by explaining this fault alarm....what does it means nd why it generally comes. I have generally seen it many times on other breakers' too. Sir, please do the needful in order to clarify my this doubt🙏 so that I would be highly grateful to you
Sir जो आपका explanation करणे का style है.. बहुत ही बढिया है....आपके Guidance से बहुत लोगो को help मिलती है........भगवान आपको लंबी उमर दे 🙌👌
You have excellent knowledge in electrical engineering.
God bless you sir.
Thank you sir.
Perfect!!!
If any one wants to clear basics pls go with this.
Good knowledge and presentation quality also nice
Is questions answer series ko continue rkhna sir
Sir, i am highly thankful to you for your video lectures. Best Regards
Aapka samjane ki speech bht masat he
Good useful basic information of subject
Pls continue settings of generator protection
Good evening sir.
Thank you sir for sharing your knowledge free of cost.
Plesse make a video on medium voltage switch gear.
Like GIS, AIS
Okay...
nice video sir ji aur sikhne bhi mila
#anilautomationhindi👍
Very Important Information 👍👍👍
Thank you...
Very helpful video sir thankyou
Nice knowledge
Sir aap bout acha samjhate ho lekin ager site me text bhi hota to ज्यादा samjh me aata🙏👍👍👍🌹
Thank you for the feedback...👍
Sahi bole aap
Excellent explanation sir..❤❤
Thank you sir...CT operated relay ke upar aur ek video banaie Pls ...
Amazing 🔥 can you please enlighten the dual ct ratio ? Where and what it's used?
Okay Danish...
Dear v nice and useful
Nice explain sir🎉
Sir ek dout tha. Aap bol rahe ho ki circuit breaker abnormalities sence nhi karta. Use tripping command relay provide karta hai. To fir mcb ke case mai mcb to apne aap current badhne par trip ho jata hai. Aisa q sir please reply me
Waiting for reply 🙂
All videos very good
Well explained sir 👍👍👍
Battery Earth fault is one of the most common failure in dc , make a video on it sir..
Dear Abhishek sir apka video achha laga kya aap hum generator me kon kon se Maintainance karte hai iska video bana sakte hai
Sir ek vedio electrical parameters par bhi bana degeye.
You,are excellent, sir, thanks
#anilautomationhindi 👌
Nice explained 👍
Sir Practical electrical interview related aur vi video Banaiye?
Aur unka ek alag se playlist banaiye.
Excellent sir thanks
Very useful video sir, plzz type of commons Replay in industrial pr ek video bnaaye sir.
Superb sir 👍
Thank you Amit..
Sir please lets make vedio on overcurrent & Earth fault setting. in Schneider relay & one brief explain about Bay control relay.
Thanks man very helpful❤️
#anilautomationhindi 👌
Good video...
Thank you..
One more important about electrical machines
#anilautomationhindi👍
Superb great knowledgeable video till I saw🙏👌
#anilautomationhindi 👌
Very informative , sir which we dont learn in any colleges..
Thank you Abhijith...
That is the purpose of this Channel..
Sir can you please make video on DI input and DO output, how to check it.. Plz make a series
Abhishek Bhai : pl prepare a video of relay settings calculations for O/C and E/F
Sir maza agaya
Star delta starters me primary protection me mccb kya range ki leng jaise Full load current 100A h to mccb ki rating kya lenge
Too good sir
#anilautomationhindi 👌
Sir, please upload relay configuration video all type relay
Sir, pls provide 132/33 kv switchyard protective relay setting details
Star delta starter me relay ki setting 58% kr di to kya sar vo phit delta me start ho payega
Excellent 👍
#anilautomationhindi
👍
informative video
Very good
Sir Ac power on honeke bavajood bhi high voltage uper mera 500 kva dg auto me start ho jata hai no load pe so me kya check Karu?
Nice video 👍
Thanku sir.. Plz make a video of auto transformer
Okay Sumit..
Also watch playlist for videos related to Drawing, Calculation, Motor, Transformer, Power Factor Correction and many more..
Sir please LV and MV switch gear pe ek video bnae. Aur isme use hone wale types of relay pe.
Thank you sir.
Okay...
Sir sabhi video ko separate Kar dete relay Ka ak jagha separate,t/f Ka , motor Ka circuit breaker Ka etc shabhi Ka please
Thanks allot Abhishek air
Most welcome Faisal..
Nice video sir
Examples ke sath banaiye video
Sir you say that CB in not a sensing divice....
When short circuit and over load condition occurred in our circuit then MCB close our circuit...
So can you explained MCB is not a circuit breker
MCB trip bcoz of mechanical action. Not by sensing a fault.
Sir ji Motor , Generator & Transformer ke Name plate ke upar video banaiye na please 🙏🙏🙏🙏🙏🙏🙏
Pls upload videos about working of 50/51,86 ,52 relay.
Sir earthing and grounding me difference he ya nhi agar he to konsa?
Sir aap Birla group ki kon se unit me work karte hai
Mayanand Mai Ultratech Cement mein hu. Manikgarh Cement Works in Maharashtra.
Sir pls make a video on 21 distance relay and it's Zone settings how to do it
Thanks guruji
Nice explanation sir i hv question if in line momentory 10,000 Amps current flow then 100 Amps will flow on ct secondary? So what about protection of relay and amp meter from high secondary current?
measuring CT will be saturated therefore meter will be protected... whereas protection purpose CT will be used to operate at 40-50 times of full load current there for during this time protection devices comes into picture and further operation will take place..above that current protection CT will be also saturated...
Sir relay control room me lagi hoti hai or instruments bahar hote hai gss me.. fir relay kese sense kar leti hai fault?
Sir Please make a video on relay testing. 🙏
Sir why CT current will take more in bus bar protection relay.like 200/1 or 800/1 like that
Over fluxing protection of transformer. Ke bare me bataye sir g
Dear sir.
Please prepare videos on generator protection and its working principle.
Sir 500amp 3pole mccb me single pole me Kitna Amp hoga.
Good
Nice sir jee 🙏🙏🙏🙏
Plz make UVR and OVR settings videos.
Thanks sir
Pls make video on TCS relay
Sir CT ratio agar 450-900-1-1a ho or 50/100 1-1-1a ho to ispe ek video bana dijiye sir
Sir 66/11kv mai all equipment ar calculation of cable and selection pr vdo banaao plz
Sf6 me kitne type ke relay hotey hai sir🙏🏻🙏🏻
Relay to switching device hai na sir automation
Sir in star delta statarter 58% means 100% of full load current why not in 80%
Shivraj, I have made a separate video on setting in star Delta Starter. Kindly watch that video..
@@electricalwithabhishekjoshi ok sir thanks
Sir practical vdo bhi banaye plz
Sir please make vidio on combiflex relay
Okay Dhruv...
sir vancay hai kya apke company me
Thank you sir...
#anilautomationhindi 👌
Sir we knw relay is used for switching purpose which make contact and break contact , but ur saying relay is sensing device and gives signal to circuit breaker.
Sir can u cleare this doubt plz.
After sensing abnormalities, relay switch their contact and trip circuit breaker.
sir solar power plant par video banaiye please
Sir ji....i have 1 doubt please clarify....at our 22 KV Incoming Breaker, Schneider Electric's Micom P122 relay is there, few days back 1 alarm noticed like-
I> 1/1
Phase L1 L2 L3
Kindly elaborate by explaining this fault alarm....what does it means nd why it generally comes. I have generally seen it many times on other breakers' too. Sir, please do the needful in order to clarify my this doubt🙏 so that I would be highly grateful to you
After clearing this alarm also noticed all 3 phases current nearly equal like-
196.2, 199.3
197.7, 0.00
Sir HT capacitor testing aur kvar &mfd relation ke bare me calculation sikhaia thanks
DG abcb check ki video banao
And industry ups ki video please banao
sir Industrial mein schematic diagram kaise design karte hai plz make the video
Please make practical video of motor,
Gulf interview me most question or answer pe video banao
Makati, ye sab interview question hi hai.
@@electricalwithabhishekjoshi ha bt most imp question Jo every interview me puche hi Jaye.
Sir ek doubt, ham sirf industries me hi relay ka use karte hene small rating ke cb me tho inka use hota nahi na, for example hamare home pe
#anilautomationhindi
👍
Thank you so much
#anilautomationhindi 👌
In DOL start motor may be delta connected. So why we keep 80% settings of FL not 58% of FL lidhe ke star delta stater. Pls helogen on it.
Career selection switch in relay please explain
Sir,what is the meaning of MVAJM in relay, explain about this topic
O/c or E/f Ralay settings calculation full load current
Sir what is difference between earth fault and short circuit fault ??
Plz make video....
#anilautomationhindi 🧐
Thank you sir
Most welcome Dev..
Explain induction type idmt oc/ef relay setting.
It means CB can't sense fault? then how can CB operate in homes without relays?
Sirjiii....
For a CT operated Ammeter, turn ratio of CT is 500:5, if line current goes 400, then what reading the ammeter will show ? 400 A or 4A.
4A
400
4A
Ammeter will show 400A...it is calibrated like that...but the current flowing through CT secondary will show 4 ampere