  • @user-zl1xp3fw2p
    @user-zl1xp3fw2p 6 หลายเดือนก่อน

    Thanks sir

  • @sammystiltner9940
    @sammystiltner9940 3 ปีที่แล้ว

    Thank you for this

  • @kappu3295
    @kappu3295 3 ปีที่แล้ว +1

    Hello sir
    How to disable linear scale and eneble servo encoder in 840d

    • @guywiththebaja5690
      @guywiththebaja5690 ปีที่แล้ว

      Did you ever figure this out, I also need to disable a scale on an 840di

  • @nerwusek19
    @nerwusek19 3 ปีที่แล้ว

    Hello Sir.I have problem with additional axis on Sinumerik 808D turning.I did purchased licence key, and loaded it to machine.But thete are alarms 26006 and 25000.Maybe you know what is reason? I can see you know what tou are doing.Lukas

    • @feelerservice
      @feelerservice  3 ปีที่แล้ว +1

      Please refer to below alarm message, and you must contact original manufacturer to get the solution and correct the setting.
      Siemens alarm message explanation as below:
      25000 Axis %1 hardware fault of active encoder
      Parameters: %1 = Axis name, spindle number
      Explanation: The signals of the currently active actual position value encoder (NC/PLC interface signal DB380x DBX1.5 = 1 (Position
      measuring system 1) or DB380x DBX1.6 = 1 (Position measuring system 2)) are missing, do not have the same phase,
      or exhibit grounding/short-circuit.
      The alarm can be reprogrammed in the MD11412 $MN_ALARM_REACTION_CHAN_NOREADY (channel not ready).
      For PROFIdrive only:
      MD36310 $MA_ENC_ZERO_MONITORING >100 replaces the existing PowerOn alarm by the Reset alarm 25010.
      Reaction: Mode group not ready.
      The NC switches to follow-up mode.
      Channel not ready.
      NC Start disable in this channel.
      Axes of this channel must be re-referenced.
      Interface signals are set.
      Alarm display.
      NC Stop on alarm.
      Channel not ready.
      Remedy: Please inform the authorized personnel/service department. Check measuring circuit connectors for correct contacting.
      Check encoder signals and replace the encoder if faults are found.
      Monitoring can be switched off by setting MD36310 $MA_ENC_ZERO_MONITORING[n] to 100 (n = encoder number: 1,2).
      Programm
      continuation:
      Switch control OFF - ON.
      26006 Axis %1 encoder %2 encoder type/output type %3 not possible
      Parameters:
      %1 = Axis name, spindle number
      %2 = Encoder number
      %3 = Encoder type/output type
      Explanation: Not every encoder type or output type can be used with every control or drive variant.
      Permissible settings:
      MD30240 $MA_ENC_TYPE
      = 0 Simulation
      = 1 Raw signal incremental encoder (PROFIdrive)
      = 4 Absolute encoder (all drive-side absolute encoders supported by PROFIdrive)
      MD30130 $MA_CTRLOUT_TYPE
      = 0 Simulation
      = 1 Standard (PROFIdrive drives)
      The alarm can be reprogrammed in the MD11412 $MN_ALARM_REACTION_CHAN_NOREADY (channel not ready).
      Reaction: Mode group not ready.
      The NC switches to follow-up mode.
      Channel not ready.
      NC Start disable in this channel.
      Interface signals are set.
      Alarm display.
      NC Stop on alarm.
      Channel not ready.
      Remedy: Please inform the authorized personnel/service department.
      Check machine data MD30240 $MA_ENC_TYPE and/or MD30130 $MA_CTRLOUT_TYPE and make the necessary
      corrections.
      Programm
      continuation:
      Switch control OFF - ON.

    • @nerwusek19
      @nerwusek19 3 ปีที่แล้ว

      @@feelerservice Problem Solved Sir ! At last this problem:)
      Machine data 30130 and 30240 and 35000 needed to be change in one time then reset.Not one after another, that was problem, I was trying to change them separetely, and after changing each parameter I was reseting control.
      Now I have another problem , but its simple.I need to change PLC for A( new axis- milling spindle "live tool") axis. After Im sending command in MDI:
      SETMS(2)
      S2000 M3
      to run A ( milling axis) with 2000 Rpm there is comunicate:
      Wait:Axis feed ovveride is 0
      And on screen S2( spindle 2) is active.
      There need to be written new PLC A spindle program, similar to existing spindle PLC program
      But problem is Im not good enough in PLC programing.Could you help me?I can pay of course
      Lukas

    • @feelerservice
      @feelerservice  3 ปีที่แล้ว

      @@nerwusek19
      Please send my e-mail: feelerservice@gmail.com and we need you give us Feeler's serial number and discuss further issue through the e-mail is better, thank you!

  • @ibrahimkswani8228
    @ibrahimkswani8228 3 ปีที่แล้ว

    Hello sir I have a problem in sinumerik 808D milling, this Alarm is: 10203 channel NC start without reference point.
    I tried to solve after set password and put parameters but same alarm
    Can tell me how adjust the parameters? And thank you
    Your regards

    • @feelerservice
      @feelerservice  3 ปีที่แล้ว +1

      10203 [Channel %1: ] NC start without reference point (action=%2)
      Parameters: %1 = Channel number
      %2 = Action number/action name
      Definitions: NC start has been activated in the MDI or AUTOMATIC mode and at least one axis that needs to be referenced has
      not reached its reference point.
      Reaction: Interface signals are set.
      Alarm display.
      Remedy: Please inform the authorized personnel/service department. Via the channel-specific MD20700:
      $MC_REFP_NC_START_LOCK (NC Start without reference point) you can decide whether or not the axis has to be
      referenced before NC Start. The start of referencing can be enabled channel-specific or axis-specific.
      Channel-specific reference point approach: The rising edge of the NC/PLC interface signal DB3200 DBX1.0 (Activate
      referencing) starts an automatic sequence which starts the axes of the channel in the same sequence as specified in
      the axis-specific MD34110 $MA_REFP_CYCLE_NR (axis sequence channel-specific referencing). 0: The axis does
      not participate in channel-specific referencing, but it must be referenced for NC Start, -1: The axis does not participate
      in channel-specific referencing, but it need not be referenced for NC Start, 1- 8: Starting sequence for the channelspecific
      referencing (simultaneous start at the same no.), 1 - 31: CPU type
      Axis-specific referencing: Press the direction key that corresponds to the approach direction in the axis-specific
      MD34010 $MA_REFP_CAM_MDIR_IS_MINUS (reference point approach in minus direction).
      Program
      Continuation:
      Clear alarm with NC START or RESET key and continue the program

    • @ibrahimkswani8228
      @ibrahimkswani8228 3 ปีที่แล้ว

      @@feelerservice thanks .i have cnc punch machine incirde sinumerik 808d but after take reference i have problem when run program , X and Y in program are correct but punch does not move in hole automatically and no alarm message on screen
      How resolve the problem in your opinion.

  • @miguelarevalo4986
    @miguelarevalo4986 ปีที่แล้ว

    Need chinese translators 😢