Brilliant and informative. Fitted a 3/4 bypass valve in a system with Trench Radiators just before the room Thermostat controlled TRV for them. If the room gets hot with its big floor to ceiling windows in the spring sunshine the boiler gets the hot water back and shuts off. Lots of solar gain and not wasted heating. Thankyou I fit kitchens and plumbers are so busy no one wants to fit my T/heaters. Thanks for your calm knowledge👌
@@matsuz100 because if every radiator has a trv and all the trvs are closed and the heating is switched on, the boiler could overheat as the hot water has nowhere to go.
Thank you for your video, apparently the new main boiler does not have a bypass built in it anymore so if all the thermostat valves are closed it will overhead. Your video has helped me. Thank you
Very good instuctional Utube - and I feel as though you are a friend, even though we have never met. Well done - you've saved me hundreds from getting cowboys in who never really seem to understand how the system works!
Hey Al, have an issue with an automatic bypass valve that i think is causing the CH gas boiler to pump over... History as follows - - Home is 30 years old running an open vented F&E system. 9 Radiators. - Potterton Suprima 50l (2004) serviced and running very well. - Climote controller and 3 x Zone valves fitted approx 2 years ago. - Recently was in the attic and noticed quite bad condensation, noticed the vent pipe from the CH was pumping over into the F&E tank. Eventually figured out it was only pumping over when a single zone was turned on i.e upstairs heating only. - Had issues with cold spots on downstairs rads so ran X400 for nearly 4 weeks and drained the system, decided to remove all effected rads, cleaned and hosed them out thoroughly until they ran clear. 30 years of sludge was bad! Cleaned F&E tank spotless, refilled the system and added X100 inhibitor. I think that eliminates any chance of blockage/obstruction in the system as all rads heat perfect now with no cold spots. - The boiler is still pumping over on a single zone and as normal over-runs(but pumps over) for approx 2 mins when the CH is timed off. If two zones are put on together i.e upstairs and downstairs the boiler does not pump over except for when timing off… - An automatic bypass valves is fitted to the immersion pipes upstair in the cubby, I thought that may be the issue so tried resetting it by closing it fully to 0.6 and then turning off all the rads except one for the purpose of backing off the ABV until flow through… - Turned on the upstairs and downstairs heating and the vent pipe(blue) immediately got hot (system pumping over) the (green) pipe also got hot in the lower part but not in the upper part after the compression fitting and then the (orange) pipe got hot within about 3-4 mins with the ABV still fully closed, should that not be the case? Im confused as to the operation and location of the auto bypass valve, its there to prevent pump-over? is it working and fitted in the correct location, direction? Pics below of pipework above boiler and cubby for reference… ibb.co/JHyMb7z ibb.co/QYxzhfR ibb.co/3y4vc3x
Auto bypass valves are normally installed to allow for thermostatic rad valves, which may all be closed, a route around the system in order to stop the pump burning out, a kind of short cut. I have never come across them being used in this way. I would opt for changing the bypass, even if just to rule it out. Have to admit this is a great way to use bypass valves. By the way have you tried simply turning your pump speed down to number 1.
@@dereton33 Thanks Al, not a plumber myself plasterer actually but like to figure these things out! So yeah just reading into it seems that ABV will be installed on zoned heating also because of the restrictions in flow when only one zone is used. I have tried pump speed 1 but the rads don't heat up fully. In the last pic I shared is the arrowed green pipe the flow and arrowed orange pipe the return, so the bypass opens to allow the water run back the return to the boiler? That what i find confusing!
Also it avoids heat loss when open so its not circulating throughout the pipework it zones or TRV's are closed. Thats actually what it was designed for. Nice job on the video
Hi fantastic intuitive video but hope you don't mind me asking at 5:40 you say make sure the arrow on the bypass is pointing towards the flow? But the flow heads towards the port valve A and B so surely the arrow points towards the return pipe from the flow 🤔
Like the way you also replaced that isolation valve on the discharge of the pump as those suckers tend to leak at the spindle and also seize in the open position....
Had a new boiler fitted to a decades old vented S-Plan 2 valve system. When CH is turned off the valve shuts immediately but the pump overruns for a minute. It has a bypass valve that joins the return but BEHIND the HW valve which is also shut! Very concerned as it appears the water has nowhere to go. Fitter didn’t say anything about the existing location when he upgraded the gate bypass to an auto one. Is this in the wrong location?
Would having a bypass rad only partially open (eg if the rad is balanced in a way that it's partially restricted with fairly low flow) be OK, or does the bypass rad need to be fully open?
Great video, I watched it before installing my valve. It might be because I bought the cheapest valve toolstation had, but is it normal to always have some flow through the valve even when TRVs are open? If my pump is on speed 3 I get hot water going through the valve, even when it's on the tightest setting, and the radiators don't heat up properly but the boiler gets up to temp and switches off. So I put the pump on speed 2 but even when the valve is on the least tight setting, there isn't enough pressure to open the valve when all the TRVs are closed, so it causes a flow error on the boiler. Just can't find a setting where the water only goes to the radiators until all the TRVs are closed.
They do but, as an example, my Greenstar CDi Compact (2013) manual states that although it has one internally, it also must have an external one if there is a risk of all TRVs shut, or an all-zone-valve system.
Thanks. I like the channel and very well explained. You can make this work by having a cheaper non modulating pump so that will keep the valve open when the modulating pump slows down if TRV's close or zone closes.
Does it have to be installed near the boiler/pump? Does bigger loop will make it better or worse? I have TVRs installed (with one radiator on manual setting just slightly open for the winter to allow flow when all TVRs close) and thought about removing radiator in the kitchen (it's always shut), and placing bypass valve instead of radiator. Is it good or bad idea...or just genius or stupid? ;)
Hello thanks for another informative video, I have just moved into a new house, and my system currently has a gate valve on the heating return (which is fully open), and a small section of pipe joining the flow and return which presumably acts as a bypass if all trvs are shut. Currently the rads downstairs are not hot at all, is this because the return gate valve is fully open or is there another possibility? Many thanks for any guidance
Hi, i tried the bypass on half a turn and then turned every radiator off and fired up the system, the pump sounded fine and not too noisy, the boiler sounded fine it didn't make any strange noises however i noticed the flame light was out, is this because there is not enough circulation or is it because the heat is not being dissipated anywhere because its only going through the bypass and making the return pipe too hot? The boiler is a worcester 18ri Thanks
@@dereton33 thanks, do i need to open this valve more or is what i have experienced normal? I take it this valve is more to protect the pump rather than the boiler? Cheers
the auto bypass valve I have appears to stuck open causing radiators to fail to receive hot feed. Can I replace just the plastic head from a new valve?
Hello I have a y-plan and my boiler is showing FA issue (reverse flow), after changing the pump and the motor in the 3 port valve, this gas engineer spotted a by pass valve in the airing cupboard with some silicon on and he said this might be the problem of the reverse flow but I am adamant to remove it as this must have been there since the house was built 2007 and I don't get why should cause this FA issue if always been there. Basically when FA kicks in, cylinder becomes noisy and heating upstairs become also warm even if heating system is on. I have looked and it seems one radiator has just the valve with plus and minus and the others are trv's, would you reckon removing it might cause a problem?
I know you can have auto bypass valves etc , but could you please do a video on setting up the manual bypass valves please, and also when my hot water and rads are both on it robs the radiator heat away, can you please help, I have already balance the rads etc
Sorry for late response, just discovered this video. Very helpful video, but one question. Will this type of bypass work with a 'Smart Pump' like my Grundfos Alpha 2. With that unit, as the TRV's close down the pump automatically reduces its speed to try to maintain a near constant pressure (so without a pressure rise, what would force the bypass valve to open)? If a system needs a bypass, does it mean that the pump's 'dumb' speed settings must be used?
Hi, I have a baxi ecoblue 30 system boiler feeding 16 radiators which have Danfoss radiator thermostats. I have installed a Honeywell DU144A1001 to replace the gate valve on my heating system. Any idea how I determine what setting to choose on the new valve?
Have managed to find this useful info, To set the auto bye pass set it to the high number turn off rad valves,run boiler & turn down Auto byepass until water is curculating through the byepass.
I know most combis have them built in now. But if the gate valve version is banned now, does that mean having the rad in the downstairs WC not having a TRV to act as a bypass also banned? all the best
There is a valve right after the pump. And there´s a "note" saying there is a separate video on how to renew those, but after spending a good 20 min going through your channel, I was still unable to find what that valve it. Would appreciate if you could enlighten me. Your videos are super helpful, BTW! Really appreciate them!
I'm guessing you'll struggle to use the chart with these modern Combi types that have variable pumps though? But, as you say, maybe adjust by feel. Good vid, thanks :)
Thanks for that - Our system seems to be using the secondary coil in the immersion copper cylinder in the immersion cupboard as a 'relief system' / bypass if all the radiator TRV's were closed - have you ever seen that kind of system? - I dare say you have. There is no zone valve to shut off the HW to the immersion tank coil so i have to make sure the oil boiler stat shuts off at between 60c-65c which is a bit of a pain because if i wanted say 70c in the rads but 60c in the immersion coil I cannot set it that way because there is no zone valve fitted. Also I see in your system there the CH pump is on the flow, on our system the CH pump is on the return pipe inside the outdoor boiler module - in your opinion which do you find best? - do you find pump best on the flow or the return?
Hi Al, Just had a Worcester External boiler fitted... Me being a little nosy I decide Check it out after they had gone.... grrrr. The boiler has a froststat, They ran a new cable with switched and constant live for the stat....Thought I would check the wiring and guess what, after all the work to run the cable they have not wired the constant live! No Stat... further investigations show they have not fitting auto bypass Valve, so now I am thinking a). they didnt fit bypass to save time and b) they knew they were not going to fit one or run the boiler frost stat, or why would it not be wired in after all that work. If it was wired frost stat would cut in with no bypass valve. would this burn the pump out and destroy the boiler? Greenstar Danesmoor External Regular 18/25...any advice welcome
Hi Big Al, quick question is the valve fully open at 0.1 or at 0.6? Also my Pump is a Grundfos Alpha2 and I have it set to auto, what setting do you think would be best for the bypass valve? Thanks
Bit confusing because for Y plan setups with a mid position 3 way valve, my boiler manual is saying a automatic bypass is not required. I guess because the mid position valve has a default position of allowing water to hot water circuit even in the off position so this is the bypass already...? Makes sense.
Also to be noted that closer to the boiler the better that if your pump is installed to correct spec. One of the main reasons for an auto bypass valve is that the CH water won't be flowing through the pipe work throughout the house if its 2 pipe system. Less heat loss makes it about 5 to 10 percent more efficient.
I have a boiler question for you. My boiler is from the late 70s would it be worth installing one of them electronic smart thermostats that control each rad. Got given a second had one that someone upgraded. So the boiler will come on and off when it needs,would it be a waste? Any help would be great, thanks Stephen
Brilliant and informative.
Fitted a 3/4 bypass valve in a system with Trench Radiators just before the room Thermostat controlled TRV for them.
If the room gets hot with its big floor to ceiling windows in the spring sunshine the boiler gets the hot water back and shuts off. Lots of solar gain and not wasted heating.
Thankyou
I fit kitchens and plumbers are so busy no one wants to fit my T/heaters.
Thanks for your calm knowledge👌
No problem Paul.
Your plumbing videos are the best on you tube. Hats off to you. You should run training courses.
Thanks Norherian.
This is why it is also good practice to fit atleast one without TRVs and fit lock shields. Preferably this should be nearest to the thermostat.
@@matsuz100 because if every radiator has a trv and all the trvs are closed and the heating is switched on, the boiler could overheat as the hot water has nowhere to go.
Thank you for your video, apparently the new main boiler does not have a bypass built in it anymore so if all the thermostat valves are closed it will overhead. Your video has helped me. Thank you
No problem.
Just to thank you. I have visitors coming in 2 weeks. Don't want them to be cold. Manged to get the all the radiators working , with yourhelp.
No problem.
Great video Dereton I remember the old bypass with the gate valve these are much better
Yes they were the old ones.
Very good instuctional Utube - and I feel as though you are a friend, even though we have never met. Well done - you've saved me hundreds from getting cowboys in who never really seem to understand how the system works!
Thanks David.
Hey Al, have an issue with an automatic bypass valve that i think is causing the CH gas boiler to pump over...
History as follows -
- Home is 30 years old running an open vented F&E system. 9 Radiators.
- Potterton Suprima 50l (2004) serviced and running very well.
- Climote controller and 3 x Zone valves fitted approx 2 years ago.
- Recently was in the attic and noticed quite bad condensation, noticed the vent pipe from the CH was pumping over into the F&E tank. Eventually figured out it was only pumping over when a single zone was turned on i.e upstairs heating only.
- Had issues with cold spots on downstairs rads so ran X400 for nearly 4 weeks and drained the system, decided to remove all effected rads, cleaned and hosed them out thoroughly until they ran clear. 30 years of sludge was bad! Cleaned F&E tank spotless, refilled the system and added X100 inhibitor. I think that eliminates any chance of blockage/obstruction in the system as all rads heat perfect now with no cold spots.
- The boiler is still pumping over on a single zone and as normal over-runs(but pumps over) for approx 2 mins when the CH is timed off. If two zones are put on together i.e upstairs and downstairs the boiler does not pump over except for when timing off…
- An automatic bypass valves is fitted to the immersion pipes upstair in the cubby, I thought that may be the issue so tried resetting it by closing it fully to 0.6 and then turning off all the rads except one for the purpose of backing off the ABV until flow through…
- Turned on the upstairs and downstairs heating and the vent pipe(blue) immediately got hot (system pumping over) the (green) pipe also got hot in the lower part but not in the upper part after the compression fitting and then the (orange) pipe got hot within about 3-4 mins with the ABV still fully closed, should that not be the case?
Im confused as to the operation and location of the auto bypass valve, its there to prevent pump-over? is it working and fitted in the correct location, direction?
Pics below of pipework above boiler and cubby for reference…
ibb.co/JHyMb7z
ibb.co/QYxzhfR
ibb.co/3y4vc3x
Auto bypass valves are normally installed to allow for thermostatic rad valves, which may all be closed, a route around the system in order to stop the pump burning out, a kind of short cut. I have never come across them being used in this way. I would opt for changing the bypass, even if just to rule it out. Have to admit this is a great way to use bypass valves. By the way have you tried simply turning your pump speed down to number 1.
@@dereton33 Thanks Al, not a plumber myself plasterer actually but like to figure these things out! So yeah just reading into it seems that ABV will be installed on zoned heating also because of the restrictions in flow when only one zone is used. I have tried pump speed 1 but the rads don't heat up fully. In the last pic I shared is the arrowed green pipe the flow and arrowed orange pipe the return, so the bypass opens to allow the water run back the return to the boiler? That what i find confusing!
Also it avoids heat loss when open so its not circulating throughout the pipework it zones or TRV's are closed.
Thats actually what it was designed for.
Nice job on the video
Thank you.
Thanks for your very good videos
Hi fantastic intuitive video but hope you don't mind me asking at 5:40 you say make sure the arrow on the bypass is pointing towards the flow?
But the flow heads towards the port valve A and B so surely the arrow points towards the return pipe from the flow 🤔
The 3 way valve is on the flow.
Like the way you also replaced that isolation valve on the discharge of the pump as those suckers tend to leak at the spindle and also seize in the open position....
Very informative, thank you. Is something dripping at @ the 7"00 mark?
A joint needed tightening a bit more.
Had a new boiler fitted to a decades old vented S-Plan 2 valve system. When CH is turned off the valve shuts immediately but the pump overruns for a minute. It has a bypass valve that joins the return but BEHIND the HW valve which is also shut! Very concerned as it appears the water has nowhere to go. Fitter didn’t say anything about the existing location when he upgraded the gate bypass to an auto one. Is this in the wrong location?
Yes should be in front of the HW valve.
Brilliant! Informative and very, very clear instructions. Much appreciated .
No problem.
Would having a bypass rad only partially open (eg if the rad is balanced in a way that it's partially restricted with fairly low flow) be OK, or does the bypass rad need to be fully open?
Restricted is ok.
Great video, I watched it before installing my valve.
It might be because I bought the cheapest valve toolstation had, but is it normal to always have some flow through the valve even when TRVs are open?
If my pump is on speed 3 I get hot water going through the valve, even when it's on the tightest setting, and the radiators don't heat up properly but the boiler gets up to temp and switches off.
So I put the pump on speed 2 but even when the valve is on the least tight setting, there isn't enough pressure to open the valve when all the TRVs are closed, so it causes a flow error on the boiler.
Just can't find a setting where the water only goes to the radiators until all the TRVs are closed.
You bought too cheap.
Combi boilers usually have this built-in btw, have done for a long time.
They do but, as an example, my Greenstar CDi Compact (2013) manual states that although it has one internally, it also must have an external one if there is a risk of all TRVs shut, or an all-zone-valve system.
It’s combi Worcester Bosch
It's always sunny where you live, always rains right up in the north east
shortyian Yes Devon is always nice. Al.
Hi my loft expansion tank overfills and the ballcock shuts off ok i wonder if this would cure it?
More than likely a pinhole in the inner coil of your hot water cylinder. An auto bypass will not fix it.
@@dereton33 I thought the water would be discoloured if it was the cylinder?
Thanks. I like the channel and very well explained.
You can make this work by having a cheaper non modulating pump so that will keep the valve open when the modulating pump slows down if TRV's close or zone closes.
Thanks for the tip.
Does it have to be installed near the boiler/pump? Does bigger loop will make it better or worse? I have TVRs installed (with one radiator on manual setting just slightly open for the winter to allow flow when all TVRs close) and thought about removing radiator in the kitchen (it's always shut), and placing bypass valve instead of radiator. Is it good or bad idea...or just genius or stupid? ;)
It does not need to be installed near the pump or boiler just a convenient location. You can change that kitchen rad for a bypass valve if you want.
Hello thanks for another informative video, I have just moved into a new house, and my system currently has a gate valve on the heating return (which is fully open), and a small section of pipe joining the flow and return which presumably acts as a bypass if all trvs are shut. Currently the rads downstairs are not hot at all, is this because the return gate valve is fully open or is there another possibility? Many thanks for any guidance
Yes it is . Turn the gate valve fully off then on by just one full turn.
Could you replace the gate valve then simply?
Yes.
Hi when you say you can leave it in the fully open position is that 0.1 or 0.6
0.6
Ok muchly appreciated
Hi, i tried the bypass on half a turn and then turned every radiator off and fired up the system, the pump sounded fine and not too noisy, the boiler sounded fine it didn't make any strange noises however i noticed the flame light was out, is this because there is not enough circulation or is it because the heat is not being dissipated anywhere because its only going through the bypass and making the return pipe too hot? The boiler is a worcester 18ri
Thanks
To much heat in the boiler it would go into safety mode.
@@dereton33 thanks, do i need to open this valve more or is what i have experienced normal? I take it this valve is more to protect the pump rather than the boiler?
Cheers
the auto bypass valve I have appears to stuck open causing radiators to fail to receive hot feed. Can I replace just the plastic head from a new valve?
No you have to replace the whole valve.
Another great vid from the master, thanks.
Much appreciated. All the best.
Hello I have a y-plan and my boiler is showing FA issue (reverse flow), after changing the pump and the motor in the 3 port valve, this gas engineer spotted a by pass valve in the airing cupboard with some silicon on and he said this might be the problem of the reverse flow but I am adamant to remove it as this must have been there since the house was built 2007 and I don't get why should cause this FA issue if always been there. Basically when FA kicks in, cylinder becomes noisy and heating upstairs become also warm even if heating system is on. I have looked and it seems one radiator has just the valve with plus and minus and the others are trv's, would you reckon removing it might cause a problem?
Yes be very careful about removing those. They are there for a reason. You could always swop it for a gate valve that you could manually adjust.
@@dereton33 What does happen if the valve is faulty? Does it cause a reverse flow or can it be the 3 port valve ?
I know you can have auto bypass valves etc , but could you please do a video on setting up the manual bypass valves please, and also when my hot water and rads are both on it robs the radiator heat away, can you please help, I have already balance the rads etc
Fit one of these valves and then a gate valve on the flow into the hot water cylinder you could then govern down the amount of water the tank gets.
You talk just about TRV’s, but I guess the same problem occurs when all the zone valves close, and the pump overruns; Is that correct?
Yes.
Sorry for late response, just discovered this video. Very helpful video, but one question.
Will this type of bypass work with a 'Smart Pump' like my Grundfos Alpha 2. With that unit, as the TRV's close down the pump automatically reduces its speed to try to maintain a near constant pressure (so without a pressure rise, what would force the bypass valve to open)? If a system needs a bypass, does it mean that the pump's 'dumb' speed settings must be used?
Yes it is more for the old 3 speed pumps.
Another nice nugget of information.
Thanks
Hi Al, I've got to replace my valve just wondered if you've ever froze the pipes rather than drain the system? Good or bad idea. Cheers
A good idea so long as you complete the job within a small time scale before the ice melts, I got caught out once, never used them again.
Hi, I have a baxi ecoblue 30 system boiler feeding 16 radiators which have Danfoss radiator thermostats. I have installed a Honeywell DU144A1001 to replace the gate valve on my heating system. Any idea how I determine what setting to choose on the new valve?
Usually number 3 but trial and error is best if not sure.
@@dereton33 - the scale goes from 0.1 to 0.6mbar. I shall give it a try at 0.4mbar. A video on how to set them up would be very useful. Many thanks.
4 is ok give it a go, you will here when it bypasses. Will look into the setting up of one of these.
@@dereton33 - thanks.
Have managed to find this useful info, To set the auto bye pass set it to the high number turn off rad valves,run boiler & turn down Auto byepass until water is curculating through the byepass.
I know most combis have them built in now. But if the gate valve version is banned now, does that mean having the rad in the downstairs WC not having a TRV to act as a bypass also banned?
all the best
Sirus No that is still Ok. Al.
There is a valve right after the pump. And there´s a "note" saying there is a separate video on how to renew those, but after spending a good 20 min going through your channel, I was still unable to find what that valve it. Would appreciate if you could enlighten me. Your videos are super helpful, BTW! Really appreciate them!
I believe it is part of the renew pump video . th-cam.com/video/QEoYwlbBApY/w-d-xo.html
is this the same for combi?
No combis haVe one built in.
Your video helped me out yesterday massively Thank you
No problem
I'm guessing you'll struggle to use the chart with these modern Combi types that have variable pumps though? But, as you say, maybe adjust by feel. Good vid, thanks :)
No problem.
Thanks for that - Our system seems to be using the secondary coil in the immersion copper cylinder in the immersion cupboard as a 'relief system' / bypass if all the radiator TRV's were closed - have you ever seen that kind of system? - I dare say you have. There is no zone valve to shut off the HW to the immersion tank coil so i have to make sure the oil boiler stat shuts off at between 60c-65c which is a bit of a pain because if i wanted say 70c in the rads but 60c in the immersion coil I cannot set it that way because there is no zone valve fitted.
Also I see in your system there the CH pump is on the flow, on our system the CH pump is on the return pipe inside the outdoor boiler module - in your opinion which do you find best? - do you find pump best on the flow or the return?
Hi Andy, it does not really matter if the pump is on the flow or return, just that most modern systems seem to be on the flow these days.
Thanks for the video really educational
No problem .
Hi Al, Just had a Worcester External boiler fitted... Me being a little nosy I decide Check it out after they had gone.... grrrr. The boiler has a froststat, They ran a new cable with switched and constant live for the stat....Thought I would check the wiring and guess what, after all the work to run the cable they have not wired the constant live! No Stat... further investigations show they have not fitting auto bypass Valve, so now I am thinking a). they didnt fit bypass to save time and b) they knew they were not going to fit one or run the boiler frost stat, or why would it not be wired in after all that work. If it was wired frost stat would cut in with no bypass valve. would this burn the pump out and destroy the boiler?
Greenstar Danesmoor External Regular 18/25...any advice welcome
Those bad boys, if the frost stat switches on it would not burn the pump out as this also switches on. Or should do if wired correctly.
Thanks for your help and advice. Great video 😊👍
No problem 👍
Hi Big Al, quick question is the valve fully open at 0.1 or at 0.6? Also my Pump is a Grundfos Alpha2 and I have it set to auto, what setting do you think would be best for the bypass valve?
Thanks
It is fully open at 0.6. Keep the pump on auto it is the best setting.
+dereton33 thanks, keep up the good work with the videos.
Bit confusing because for Y plan setups with a mid position 3 way valve, my boiler manual is saying a automatic bypass is not required. I guess because the mid position valve has a default position of allowing water to hot water circuit even in the off position so this is the bypass already...? Makes sense.
No wrong.
@@dereton33can you explain why you say it's wrong?
Do I need one of these on a combi, I have all trv on my rads?
No not on a combi
Why don’t you need one on a combi?
Sorry Al, great video....
Thanks for the information.
Any time!
I get why you need this on a one pipe system, but do you even need this on a 2 pipe system?
Yes.
Also to be noted that closer to the boiler the better that if your pump is installed to correct spec.
One of the main reasons for an auto bypass valve is that the CH water won't be flowing through the pipe work throughout the house if its 2 pipe system. Less heat loss makes it about 5 to 10 percent more efficient.
Thanks for the extra info .
Very useful. Thanks for posting this.
No problem.
I have a boiler question for you. My boiler is from the late 70s would it be worth installing one of them electronic smart thermostats that control each rad. Got given a second had one that someone upgraded. So the boiler will come on and off when it needs,would it be a waste? Any help would be great, thanks Stephen
Stephen Lyons Yes it would still work OK, anything that saves on energy has to be good.
thank you
thanks,well explained!
You're welcome!
Great video thank you so much
Glad it was helpful!
thank you, very clear instruction.
You are welcome!
Awesome video
Thanks for the visit
thanks a lot for the clear instructions :)
No problem.
simple nice vid mate
Thanks.
Top video, thanks.
No problem.
Couldn't you just have taken a trv off and put on a lockshield ?
The 33 port valve will always rest in an open circuit .
3 port
thanks for sharing
cheers mate
m