Inverter earth fault VLT 6000 Danfoss

แชร์
ฝัง
  • เผยแพร่เมื่อ 10 ก.ย. 2024
  • Inverter earth fault alarm 14 VLT 6000 Danfoss
    Possible earth faults:
    Cable insulation fault
    Motor insulation fault
    Water or moisture in motor
    Current measuring circuitry fault. Faulty current sensors cables, components or connections inside drive.
    For me, it was a cable from the current measuring module to the power board. Those cables are notorious of failing.

ความคิดเห็น • 11

  • @andisulaimanorc
    @andisulaimanorc ปีที่แล้ว

    what is l the solution for: Alarm "Low Temp. (W66)"?

    • @valentinaselektrikas
      @valentinaselektrikas  ปีที่แล้ว

      Hello. There is no such alarm W66 low temp for vlt6000. But there is warning 66 fdb high. Maybe you have other drive?

  • @masfiy947
    @masfiy947 10 หลายเดือนก่อน

    apakah di sebabkan oleh kabel fleksibel?

  • @Industrialvelog
    @Industrialvelog ปีที่แล้ว

    sir in my drive VLT 6000 giving failed error showing on display

    • @valentinaselektrikas
      @valentinaselektrikas  ปีที่แล้ว

      Hi, I hope you will figure it out :⁠-⁠D

    • @Industrialvelog
      @Industrialvelog ปีที่แล้ว

      @@valentinaselektrikas I don't understand

    • @valentinaselektrikas
      @valentinaselektrikas  ปีที่แล้ว

      @@Industrialvelog In order to understand you can read manual. You can look in troubleshooting section where alarms and warnings listed. Alarm or and warning have numbers representing certain trouble.

    • @Industrialvelog
      @Industrialvelog ปีที่แล้ว

      @@valentinaselektrikas actually my invertor has become hanging position

    • @valentinaselektrikas
      @valentinaselektrikas  ปีที่แล้ว

      @@Industrialvelog lol