RCDs: Neutral - Earth Faults

แชร์
ฝัง
  • เผยแพร่เมื่อ 28 ธ.ค. 2024

ความคิดเห็น • 331

  • @nowthenad3286
    @nowthenad3286 ปีที่แล้ว +10

    Here I am again watching this video 2 years later. You are a national treasure JW.

  • @rezorro1983
    @rezorro1983 หลายเดือนก่อน +1

    Thanks for the great video. 10 years later its still enlightening people like myself

  • @roberthorwat6747
    @roberthorwat6747 8 ปีที่แล้ว +9

    This used to drive me nuts in my old house. Such a simple explanation but all the same I'd have never figured it out in a zillion years. I am demystified at last. Thank you so much for this!!!

  • @tobybarker6808
    @tobybarker6808 3 ปีที่แล้ว +10

    you have a knack of explaining stuff that even I can understand

  • @benharris2217
    @benharris2217 9 ปีที่แล้ว +61

    This guy is great. So informative and explains things clearly

  • @NOELTM
    @NOELTM 9 หลายเดือนก่อน +2

    Thank you for explaining this so clearly. The scenario you mentioned in the first 40 seconds was exactly what happened to me today!
    I knew what I did - but didn't understand why this happened. Now I do - 9 years after you made the video!

  • @Non-Stick_Pan
    @Non-Stick_Pan 3 หลายเดือนก่อน +2

    It's like TH-cam is reading my mind... I removed a light from the circuit this week and couldn't work out why the RCD tripped, been thinking about it for a few days then this video pops up in my recommendations!

  • @derekincambs5165
    @derekincambs5165 7 ปีที่แล้ว +3

    No one would fail their Electrical exams if you were the tutor. Great stuff. From a non electrical person!

  • @RandyDarkshade2
    @RandyDarkshade2 9 ปีที่แล้ว +35

    Thank you. I have always wondered why an RCD can still trip even if you have the power off on the circuit you are working on, now I know.

  • @examplerkey
    @examplerkey 5 ปีที่แล้ว +4

    Extremely helpful video as usual from John. I watched it so carefully that I noticed that you edited the video at 4:27 :) Thank you very much. You saved my day! Your video confirmed my suspicion of a N-E fault in a residential installation in which the responsible 30mA RCB was switching off every 5 minutes! despite all the MCBs switched off (and Live bus bar removed, just in case). Locating or narrowing down the fault is as easy as removing the Neutral wires one by one from the Neutral bar and see which one trips the RCD.

  • @Paula-xo5bb
    @Paula-xo5bb ปีที่แล้ว +1

    This is one of the best explanatuons with demonstrations I've seen. Well articulated.

  • @glennbowers9901
    @glennbowers9901 5 ปีที่แล้ว +5

    This guy is quality... Makes everything make perfect sense... Thanks alot John

  • @ninjaman1138
    @ninjaman1138 5 ปีที่แล้ว +3

    great video, explains what i was after. this happened to a street light while i was working on eastenders. the lamp wasnt working, it was disconnected from the supply but there was about 50v between earth and neutral. i have been trying to figure out the cause since. thats scratched an itch! cheers john, all the best.

  • @vhsable
    @vhsable 8 ปีที่แล้ว +8

    Thanks for the videos John, I find them very informative, easy to understand and a great back up for my level 3 2365 . Thumbs up on every video so far.
    Thanks.

  • @melliflousbufo
    @melliflousbufo 10 ปีที่แล้ว +18

    Brilliant explanation - thanks John! As well as understanding why neutral/earth shorts trip the RCD I also finally understand why the RCD has no interest in the state of the earth!

  • @uhtredthebold2
    @uhtredthebold2 2 ปีที่แล้ว +1

    You have answered a question from years ago when I replaced a socket in my house. I tripped the RCD even though the circuit I was working on was isolated and I suspect I did exactly this. Thank you

  • @ionutpiglesan8348
    @ionutpiglesan8348 5 ปีที่แล้ว +7

    Great video ! I just saw it and I think one solution for this is to use 2poles or 1p+n MCB s instead of 1 pole. So when you disconnect the MCB both line and neutral are off . The regulations in my country recommends to use that kind of MCB s.
    Of course RCBO s on all circuits is the best solution but it is more expensive.

    • @mwkoskamp1
      @mwkoskamp1 4 ปีที่แล้ว

      In NL we use one RCD for every 4 MCB's. And indeed 2p RCD's. They recommend RCBO's for outdoor units like airconditioners, outside lighting and solar panels.

    • @luluboxingtv2880
      @luluboxingtv2880 2 ปีที่แล้ว

      Where you from ? Romainia ? They use cow shit to build houses

  • @michaelherbert2982
    @michaelherbert2982 4 ปีที่แล้ว

    Hi John... Many thanks for your time too explain in depth the earth / neutral faults.

  • @spiro6363
    @spiro6363 4 ปีที่แล้ว +2

    I just love the occasional dry humour, makes for interesting listening.
    many thanks for the detailed explanation.

  • @kevinrabela9634
    @kevinrabela9634 4 ปีที่แล้ว

    Absolutely brilliantly explained for a layperson to understand the basic concepts! Well done!

  • @shiamjad
    @shiamjad 3 ปีที่แล้ว +1

    I faced this issue last month and was surprised that even though Sockets MCB is turned off , why does RCD trip whenever Neutral touched Metal/Earth...Thank you very much for your videos

  • @Mtaalas
    @Mtaalas 8 ปีที่แล้ว

    You know, we're redesigning our Hackerspace's electric circuits, and your videos are very big help. :)
    We're situated in the buildings decommissioned bunker and thus we have only one single 10A fuse for our space and it's pretty much inadequate for our needs. All the sockets and lightning is behind that one fuse, so we're going to replace the main cable with bigger one, install bigger fuse to the other end and a consumer unit for our space so if we trip something, we don't have to walk all the way to the buildings main fuse box (that's behind locked door) to get everything up and running again.
    The idea is, that we design and build all the new connections etc, without making them live and then sparky with proper equipment and credentials comes up, measures and checks everything and connects it up to the mains so it's legal.
    But since it's been like 13 years when I went trough the courses about electric installations, it's been a good resource to remind myself about the topic. :)
    Luckily we have a memeber with automation as his credentials, so he's a big help even if he doesn't have the classifications of a sparky.
    All we need to do is to make sure, that the differences in standards between Finland an UK aren't going to be too large so our sparky doesn't get a face palm when he sees our designs. :D
    So thanks a lot :)

  • @RODALCO2007
    @RODALCO2007 9 ปีที่แล้ว +12

    Great informative video. Interesting to see that the cooker goes through the RCD. In NZ the cooker and hotwater cylinder don't go throught the RCD as heating elements sometimes have leakage and cause nuisance tripping of the RCD.

    • @jwflame
      @jwflame  9 ปีที่แล้ว +9

      RODALCO2007 Virtually everything has RCDs now, as regulations require it for cables concealed in walls. The other options being to use armoured cables, steel conduit or having concealed cables more than 50mm below the surface - all of which are far more inconvenient and expensive than fitting an RCD.
      Cookers and similar are a problem, such as where a new consumer unit is fitted and the cooker which worked perfectly before now trips the RCD on a regular basis. Have also seen the same problem with people buying a new cooker, where it's been stored in a damp environment before delivery.

    • @RODALCO2007
      @RODALCO2007 9 ปีที่แล้ว +5

      ***** Thanks for your reply. In New Zealand a hotwater cylinder and range/cookers don't have to be on a RCD because of the leakage issues encountered sometimes with enclosed elements. Values are often around 10-15 kO.hms. and the element has still plenty of life left in them. The NZ standard also requires 2 RCD's at least to avoid loosing all power in the house.

    • @MrObiwankanoobi
      @MrObiwankanoobi 6 ปีที่แล้ว +3

      greetings, I'm well late to the party here, but nonetheless I thought you would be interested to know The AS/NZ 3000 wiring rules are just about to have a new edition released, with one of the big changes being RCD everything. Every circuit needs its own individual RCD, including water heaters, ovens and cookers.
      One other big change is that if anyone who is working at a domestic residence needs to do work in the roof, they need to shut the power off to the whole installation which is interesting.
      you can follow this link for a preview of the planned revisions. www.commerce.wa.gov.au/energysafety/new-wiring-rules

    • @Wowzersdude-k5c
      @Wowzersdude-k5c 6 ปีที่แล้ว +5

      We still use GFCIs at the receptacle here in the States, even though GFCI breakers are perfectly acceptable and code compliant. The big thing now here are AFCI's (Arc fault breakers). They are required at the breaker panel on almost every circuit in residential installations these days. (They've been required since 1999 in bedrooms, but now are required everywhere). I hear they aren't a requirement yet in the UK, I presume because you guys protect all cables with metallic sheathing.
      In any case, studies have shown that around 50% of electrical related home fires in the U.S. are a result of arc faults (series more than parralel) hence the new requirement. Here most homes use non-metallic plastic sheathing rated at 90C. While it's safe cable, it's still non-metallic sheathed meaning it is feasible that it can be damaged in the wall (errant nails or rodent chewing), thus the potential for unseen arcs which normal breakers won't detect.
      Some metro areas require metal sheathing for residential applications. Chicago is one city with very strict standards in that regard. (Here states and local munincipalities have the authority to override the national code with their own code). It makes sense in those areas because if one condo or apartment building burns, the whole block burns. It doesn't make as much sense in the country where your nearest neighbor is a mile away.
      We also have many very old homes here. It is not uncommon to see old homes with "knob and tube" wiring from the 20's. It is legal, but if renovation is done it must be brought up to code. And we have tons of homes from the 50's to 70's using wiring code from back then. Grounding has been code since the early 60's I believe, but there's still many homes out there without an earth ground circuit (all receptacles are two prong). Some unscrupulous people will install 3 prong receptacles in an old home without a ground circuit, thereby creating a "bootleg" ground. This is achieved by connecting the neutral to the metal electrical box. This will trick the inexpensive receptacle testers into reporting there is a proper ground. These cheap testers are used by most home inspectors, and creates a dangerous situation for an unknowing home buyer.

  • @fowhak69
    @fowhak69 8 ปีที่แล้ว

    Thank You John Word for all your lectures. you have used a simple and clear way to be understand

  • @jmx318
    @jmx318 3 ปีที่แล้ว +2

    How is that any different to an MEN link?

    • @jwflame
      @jwflame  3 ปีที่แล้ว +2

      MEN link is before the RCD, the fault described in this video would be after the RCD within the installation.

    • @jmx318
      @jmx318 3 ปีที่แล้ว +1

      @@jwflame thanks mate absolutely great content you provide

  • @mikeZL3XD7029
    @mikeZL3XD7029 4 ปีที่แล้ว +1

    Excellent explanation, John.
    I see this sort of things with inspecting caravans, where the owner has wired the damn thing themselves and left the link in between the
    Neutral and Earth busbars at the little switchboard, that's normally in the smallest cupboard ever.
    It's that time of the year at the moment, considering people can't fly out of New Zealand because of Covid-19 restrictions.

  • @KM-cb8ff
    @KM-cb8ff 8 ปีที่แล้ว

    This has helped massively to understand a fault that developed after getting some walls plastered.
    Trying to work out the fault using the MCBs alone was fruitless as the RCD would randomly trip. knowing the RCDs are double pole and mcbs are single leads me to believe something is still wet causing an NE trip. Problem is trying to work out what is wet..
    Nice clear video tho!

  • @daviddavidson2357
    @daviddavidson2357 ปีที่แล้ว

    Cheers. Excellent explanation. This had me puzzled while doing some electrical work up in my gran's attic, I thought she was flipping the main breaker as she's terrified of electricity. I'm cautious; test with a NCV tester then a multimeter before work especially as whoever did the wiring in that attic had no idea what they were doing, flourescent strip light in *series* with a ceiling rose (not for lack of wire, they just left the live wire flapping in the breeze),steel cored speaker wire (or something similar) hooked up to live and neutral leading to seemingly nothing, if I had to hazard a guess it was for an old doorbell and just reconnected by every contractor who did some work there, though why it is on the attic lighting circuit is beyond me.
    All of these things had me fairly worried about the house being plunged into darkness as I was concerned that there was a live (or intermittently live) conductor somewhere. Turns out it was neutral touching earth, which I'm sure of as I tested it twice. Measured with a multimeter and got .7 volts, guess the current was enough to trip the breaker though.

  • @davids7627
    @davids7627 9 ปีที่แล้ว +8

    Hello,
    Excellent video, as usual.
    Could you please do a video on RCBOs, and particularly on why they have the separate white earth leads. I am a trainee electrician, and was told by one qualified electrician that they are to prevent nuisance tripping, but another qualified electrician didn't know what they were for

    • @jaycee1980
      @jaycee1980 5 ปีที่แล้ว +2

      The white lead is an earth connection and it is usually used by the TEST function of the RCBO... which creates a deliberate imbalance to earth in order to cause the RCD part to trip. If you don't connect it, the TEST function usually doesnt work. Some RCBO's are designed so that they don't require that earth connection

  • @andyisthebestest
    @andyisthebestest 3 ปีที่แล้ว

    This exact thing happened me tonight. I thought it was something to do the balance, but you explained it perfectly. Thanks.

  • @johnmurrell3175
    @johnmurrell3175 4 ปีที่แล้ว +1

    Been there and done that - I was rewiring a socket and I twisted the bare ends of the cable together and the RCD tripped as explained plunging the building into darkness. The situation was only saved as I had a head torch in my pocket that I was able to find in the dark. Moral carry a torch at night particually when working on electric circuits.

  • @paulekstorm-hughes1894
    @paulekstorm-hughes1894 10 ปีที่แล้ว +8

    Well this explains exactly what happened to me the other day! Great timing with the video. Thanks

  • @hansdavid8112
    @hansdavid8112 9 ปีที่แล้ว +1

    Hi i would like to ask a question about yr wiring, Why to you insert the link bar at the outlet of all the circuit breaker?? im talking about the LIVE bar.it should not be upper side of the circuit breaker please??

    • @jwflame
      @jwflame  9 ปีที่แล้ว +1

      hans david Most consumer units in the UK have the circuit breakers arranged with the supply at the bottom, and circuits connected at the top.

    • @hansdavid8112
      @hansdavid8112 9 ปีที่แล้ว

      Ohh ok, and the c.breaker works same ???

  • @mastergx1
    @mastergx1 9 ปีที่แล้ว +3

    Another interesting point to make in regards to this irritation is it is far more likely to happen on a TN supply as the impedance of the earth is generally much much smaller than that of a TT. On a TT supply somewhere in the sticks where the local transformer (and ground) is miles from the house and your main earth is little more than a stick in the ground...This is far less likely to happen, if even possible in some situations. An example would be my stepfathers farmhouse that has no equipotential bonding at all because there is no gas and all local supplies come in plastic, the only earth connection is a single earth spike. So poor is the earth, I test the RCD's every single time I go there as a precaution.

    • @lawolsten
      @lawolsten 6 ปีที่แล้ว

      I'm by no means an expert. When you say the earth is so poor. What reading would you describe as poor? Thanks

  • @zerosparky9510
    @zerosparky9510 5 ปีที่แล้ว +1

    interesting in that in the US on the main panel is that the neutral and ground bar are together as one.

  • @jpegxguy
    @jpegxguy 11 หลายเดือนก่อน

    What you're saying is that double pole mcbs are the way to go (especially since they exist in slim form factors), so that I can also isolate neutrals. The system of only disconnecting the line is a pain in fault-finding

  • @jacksonroad9263
    @jacksonroad9263 3 ปีที่แล้ว +1

    excellent simple explaination straight to the point. thank you

  • @BloodmoonDawn
    @BloodmoonDawn 4 ปีที่แล้ว

    if i am replacing a light fitting on an individual circuit containing several lights ( and ive isolated it and made it safe) and i know its going to trip the rcd to other circuits which will bring a shop to a grinding halt, which conductor would i reconnect first to prevent it tripping and then in which order after that (to reconnect the other two).
    also could you explain why they are reconnected in that order. thanks John, i hope the question makes sense

  • @britannic2000
    @britannic2000 7 ปีที่แล้ว

    Hi John would a quick way to identify the problem be to remove the neutrals at th fuse box one at a time thanks

  • @TheMeishi
    @TheMeishi 9 ปีที่แล้ว

    Can you tell me how are surge suppressor installed? I mean those the look like rcd and are attached to the board. Thanks for your wonderful videos.

  • @odysseus-2058
    @odysseus-2058 8 ปีที่แล้ว

    Hi,is that neutral "u" link a standard ulink or have you made it,and what diameter is it.thank you.

  • @normanboyes4983
    @normanboyes4983 6 ปีที่แล้ว +2

    Thanks for doing this John - very well explained.👍

  • @sofasoul5367
    @sofasoul5367 8 ปีที่แล้ว +2

    John, it would be nice to include what is happening when ALL MCB's are off (no load) and the RCD still trips. e.g. there could be equipment in the circuit that carries potential even with the power off. :-)

    • @enycenyc3144
      @enycenyc3144 6 ปีที่แล้ว +1

      +Sofa Soul
      "TheChipmunk2008" above actually pointed this out...
      If you have a N-E fault, and you are on a TN-S supply, then you can easily get small currents between Neutral and Earth on supply-cable (as they may have a few volts difference between them). These will still trip your RCD when power (line) applied to the primary of rcd.

  • @chazwalker7156
    @chazwalker7156 4 ปีที่แล้ว

    Is there any way to simply determine if it's a 'neutral to earth' / 'live to earth' / 'live to neutral' fault that trips the downstairs light breaker?
    Cheers for advice.

  • @acomment2242
    @acomment2242 4 ปีที่แล้ว

    Hello John - thanks for above explanation. I have a question - I have a volex rcd vr80 . Where can I find out what the in and out connections are. I noted in your diagram that the neutrals are on the left side with the live's on the right, and mains input at the top pair of connections. The problem I have is that there is a small label with a capital 'L' next to the top left connection of my RCD. If I assume the L is load or live, that makes the way my RCD is connected different from your diagram. Any advice? Thanks in advance. JS.

    • @jwflame
      @jwflame  4 ปีที่แล้ว

      The Volex ones were made to go either way - on those consumer units it was usually one RCD at each end of the row of MCBs, the left RCD had L on the right, the right RCD had L on the left. The two RCD were identical other than the placement of the 'L' label, and that's why they had a stick on label rather than it being moulded/printed on.
      Supply in on the top for those - for most RCDs that doesn't usually matter either.

    • @acomment2242
      @acomment2242 4 ปีที่แล้ว

      @@jwflame Thanks for your reply John, that is very helpful information. I had taught some electrical installation classes many years ago but did not remember dealing with consumer units or their contents. Currently facing the installation of consumer units in a summer house and a cellar - for lighting and power. Thanks again. JS.

  • @halesworth01
    @halesworth01 10 ปีที่แล้ว +1

    Thank you John....I could never get an answer why I was getting a "tingle" from a registered 'leccy whenever i've done work on any "disconnected" circuit in my house.....plain as day now through your explanation....My "disconnected circuit" is in fact still connected!!!...in future I WILL TURN OFF EVERYTHING at the main R.C.B...I Know before anyone else chips in, yes you have to be a 17th edition certified Electrician to work on ANYTHING more than wiring a plug these days...and it is advised that even if you do that, it is checked by one!!! But in my defence I ALWAYS DO ANY WORK MYSELF & GET IT CHECKED AND SIGNED OFF (by a registered electrician) before "flicking the switch"

    • @Alan_Stinchcombe
      @Alan_Stinchcombe 6 ปีที่แล้ว

      Clive, I don't think anything John has said would explain why your disconnected live wire would feel tingly. This may be because the disconnected live conductor was capacitively coupled to another circuit that ran alongside it for a few metres.

  • @shilks8773
    @shilks8773 5 ปีที่แล้ว +1

    It surprises me that there seems to be few DP RCBOs available to fit into UK CU's These would seem to provide the safest isolation. Each of the Line and Neutral would be separate connections on ether the line or neutral. An inherent design flaw in the UK consumer units.

  • @rich1051414
    @rich1051414 9 ปีที่แล้ว

    I have a question that maybe you can illuminate for me. Recently, I moved into a new house with RCBO's and one of my AC's has a built in fault detecting plug which occasionally trips the one for the outlet it is plugged into. Why would one RCBO trip another? I have recently solved it by adding a third which sits between and have really be scratching my head on this one. It has not tripped since I added the fault detecting plug between the AC's and the one in the breaker box. It is not a amperage issue, as that was the first thing I eliminated, but was rather a load imbalance fault.
    I can only assume the one on the AC is faulty, and soon I will be replacing it with a new one, unless there is a reason you could give me that would cause this or if it is a weird gremlin I may never figure out.

    • @_______DR_______
      @_______DR_______ 9 ปีที่แล้ว

      +Richard Smith it's likely that the fault is within the AC and the RCD in your house has a quicker trip time than the one in the plug, you generally want to avoid using the same rating of RCD downstream from another as it's often the case that they'll both trip simultaneously or the one upstream will trip first instead of the one closest to the fault

  • @serbuserbaserbi6808
    @serbuserbaserbi6808 5 ปีที่แล้ว

    Mr.John please help understand me. With regards to rccb that is too sensitive when lightning occurs.
    whether grounding is not good enough or there is another reason.

  • @2wheelsrbest327
    @2wheelsrbest327 6 ปีที่แล้ว

    Great videos John. Currently got this problem and after disconnecting and replacing all neutrals got the problem down to sockets in lounge but cannot locate where problem is by removing each socket as all wiring looks ok. Is there a possibility that it could be a faulty MCB.I am in UK. Thanks

  • @senaldeva
    @senaldeva 9 ปีที่แล้ว

    Hey JW, I took some readings between Line & Neutral, Earth(ground) & Neutral, the readings were LN= 240V, & EN=80V.. Do you know why the EN is 80V, I check if the earth wire was disconnect from the earthing rod, but it was not. PS. House has 3Phase Supply

    • @jwflame
      @jwflame  9 ปีที่แล้ว +2

      Senal Devasurendra If the earth is connected, then it's either due to voltage drop in the neutral, there is a fault between line and earth somewhere, or the test meter has a very high input impedance so the 80V measured is not actually there. Or a combination of all three.

  • @Forester17
    @Forester17 9 ปีที่แล้ว +3

    Great video, just one question: In a MEN earthing installation where there is a connection between the neutral bar and earth bar, how then can the RCD still operate how it is supposed to? Why doesn't the MEN link provide the leakage path to trip the RCD anytime there is a load?

    • @_______DR_______
      @_______DR_______ 9 ปีที่แล้ว +6

      +Forester226 The connection between the installations earthing conductor and the supplies neutral conductor is made before the RCD (at the supply inlet position in the uk) then when the line an neutral pass through the RCD the earth connection will serve as an alternate path in case of a fault, so if a live wire were to touch an appliance casing current would come via the RCD and follow the alternate path at which point the RCD will detect an imbalance and trip. No matter which earthing arrangement you have it all goes back to neutral at the transformer one way or another

  • @AngieE-144
    @AngieE-144 8 ปีที่แล้ว

    Hello John I have a therapy floating pool from America that recommends each appliance ( UV Pumps x 2, and heating pads that sit under the tank to heat the water which I have had earthed UK plugs put on) to have a GFCI connected to each of them. There is an RCD connected to the main electric board in the house. I have been told that I do not need the GFCIs on my appliances because of having the RCD already in the house. I am very concerned as water and electric do not mix and I need to find out if the RCD is sufficient enough without the extra GFCIs? Also the heating pads have a grounding probe and am also wondering if that is still needed as we have an earth in our plugs. I can ask the supplier all this but I would feel happier checking with someone who knows all about UK electricity. Thank you for your advice in advance.

    • @jwflame
      @jwflame  8 ปีที่แล้ว

      Having multiple RCDs/GFCIs is not necessary, provided the house one is a 30mA type. However if the pool already has them fitted there is no reason to remove them either. The only minor problems can be that if they have a test button on them, pressing this may trip the main house RCD as well, and if a fault occurs it may not be the pool one which trips, the house one could trip first, or both could trip.
      The ground probes is an unusual design and should not be necessary either, the circuit already provides an earth connection.
      Even if the probes were required, just shoving a probe into the ground is next to useless, as it has to be tested to confirm the impedance is low enough. In some locations, earth rods have to be many metres long to be effective, or other methods such as buried grids must be used.

  • @spihon9481
    @spihon9481 2 ปีที่แล้ว

    and why it does not trip when i touch the neutral?is it because i have high resistance so V/R < 30mA?

  • @glynstein2922
    @glynstein2922 8 ปีที่แล้ว

    Obviously the best installation, the only problem I have come across is the immediate diagnosis that it's an earth or overcurrent fault, as the RCBO trips regardless. The older system would only trip one of the devices depending on the fault. A recent intermittent fault caused me to install seperate breakers in order to deduct the fault (temporary measure) I don't know if an RCBO exists with seperate indication flags as to the reason it tripped?

    • @jwflame
      @jwflame  8 ปีที่แล้ว

      Not as far as I know. Hager make an RCD which has a trip indicator, but that only shows the difference between the device being tripped due to a fault or switched off manually.

  • @ronbonick4265
    @ronbonick4265 6 ปีที่แล้ว

    JW Ive been wanting to get a Fluke 1653B - to test systems here in the US... But now we have ARC fault breakers - will this damage the meter in anyway? I was wanting to do a trip test and get a time/ amp reading on each 120vt circuit here in the US , any advise ?

  • @stewartw99
    @stewartw99 4 ปีที่แล้ว

    Hi John, yet another very helpful video - you have a great talent for education. Thanks very much for all the time and effort you put into this Channel, cheers.

  • @davidpatterson1574
    @davidpatterson1574 3 ปีที่แล้ว +2

    Very informative video John, and explained extremely well.

  • @1987kahil
    @1987kahil 5 ปีที่แล้ว +1

    Very good video as usual John

  • @DjResR
    @DjResR 9 ปีที่แล้ว

    Good video. In Estonia the RCD is not required for entire building, it's optional for bathrooms (water heater, washing machine, optional socket by the mirror) and other moist rooms like basement.

    • @jwflame
      @jwflame  9 ปีที่แล้ว +1

      DjResR They used to be optional here as well, but over time, more and more things have required them, and today almost all circuits in a house must have an RCD.

  • @enggind365
    @enggind365 9 ปีที่แล้ว

    @John Ward
    I stand corrected. I agree there should be a common neutral bar for the neutral connection of all loads controlled by this RCD. But I believe this neutral bar should be unique to this RCD and should not be connected to the neutral bar where the incoming neutral and non-RCD loads are connected. Please confirm.

  • @JohnDundee-el2ro
    @JohnDundee-el2ro 5 หลายเดือนก่อน

    Hi. What would or could happen if you did not clear the neutral to earth fault when the single pole rcbo trips and you don't have a 100 MA double pole S type rcd up front Cheers

    • @jwflame
      @jwflame  5 หลายเดือนก่อน

      Current could flow between N&E via that fault.
      On a TN system that won't matter at all.
      On a TT system it could result in elevated voltages at the earth electrode or at other parts connected to it.
      If you use SP RCBOs with an upfront RCD, the upfront TCD will still trip even if the RCBO disconnects.

    • @JohnDundee-el2ro
      @JohnDundee-el2ro 5 หลายเดือนก่อน

      @@jwflame yes but I take it it will clear the dangerous N-E fault the sp RCBO would not

  • @michaelcostello6991
    @michaelcostello6991 ปีที่แล้ว

    Was there any MEN link between neutral and earth in this installation

    • @jwflame
      @jwflame  ปีที่แล้ว

      No, that arrangement is not used in the UK. The only link N-E is in the fused cutout located before the meter and owned by the electricity distributor.
      Not permitted to have such links within the installation or to use combined neutral and earth conductors in an installation.

    • @michaelcostello6991
      @michaelcostello6991 ปีที่แล้ว

      @jwflame Thanks. Australia has neutral and earth bar joined.

  • @sebshep18
    @sebshep18 7 ปีที่แล้ว

    Hi John, brilliant videos very informative. I have a similar problem, i have an old lighting ring which was on the old fashion black covered consumer unit, iv since replaced the consumer unit to have a RCD installed. I have reconnected the lighting ring and now each time i try and turn on the the circuit breaker for the lights it doesn't trip the CB it trips the RCD instead. Nothing has changed everything is ok as far as i can see the lights all worked fine now the RCD, any simple or easier ways of detecting where the issue could be ? Thanks again

    • @seanbrennan3472
      @seanbrennan3472 7 ปีที่แล้ว

      I would be looking to see if you have a shared neutral on your lighting circuit

  • @TheChipmunk2008
    @TheChipmunk2008 10 ปีที่แล้ว +5

    One point John, in the event you're on a TN-S system, even if there's no current from the installation, you might get current flowing from the neutral to earth from other consumers on the same TN-S supply cable, even if they're down the street, or even several streets away (In that case there's zero current in the line, sometimes quite a high current on the neutral)

    • @TheEulerID
      @TheEulerID 6 ปีที่แล้ว

      Isn't neutral & earth bonded where the supply enters the meter box on a TN-S system, so there really ought not be any flowing within the house from external properties.

    • @Alan_Stinchcombe
      @Alan_Stinchcombe 6 ปีที่แล้ว

      Steve, in TN-S, neutral and earth are *separate* conductors that are only connected remote from the premises (e.g. substation). Typically, load imbalances in the 3-phase distribution network would cause the neutral to "invert", or rise slightly above earth. This is how urban supplies used to be delivered in the UK (with the separate earth soldered to the lead sheath of the distribution cable) and I can remember seeing (small) sparks when I accidentally connected neutral and earth.
      What you are describing is TN-C-S (formerly "PME" in the UK), in which a *combined* neutral and earth conductor arrives at the premises, then *separates* into neutral and earth conductors for the consumer. There is still the potential (no pun intended) for a dead short on one phase of the distribution network close to the premises to pull the combined conductor well away from local earth potential, which is one reason why the UK is pretty hot on bonding of plumbing and other metalwork, so that there is less likelihood of 100V suddenly appearing between your metal-bodied kettle and the kitchen sink while you are touching both with different hands.
      You may find the Earthing system article in Wikipedia of interest.

    • @TheEulerID
      @TheEulerID 6 ปีที่แล้ว

      Thanks - I was, indeed thinking of TN-C-S.

  • @leexgx
    @leexgx 9 ปีที่แล้ว +3

    RCD are annoying in their current install setups (1 or 2 protecting all of them) wish RCBO where more standard
    i guess this explains why the RCD would not latch when even all MCBs was off
    customer has got a 2 soldering irons and both of them trips the RCD the moment you plug them in and if left plugged in you can not reset the RCD even if the MCBs are all off, so i guess that is the Neutral and earth fault, but others have said this is a common thing with soldering irons

    • @alerighi
      @alerighi 6 ปีที่แล้ว +1

      Why not using MCBs that also interrupt neutral ? Here in Italy it's the standard, I don't get why they are not used everywhere in the world. Putting a RCD on every circuit it's expensive, here the common setup is a main RCD and then MCB that also interrupt neutral for every circuit. A fault is simple to isolate, you turn off all the MCB and turn them on one by one since you fine the one that trips the main RCD.

    • @joefrayling9263
      @joefrayling9263 6 ปีที่แล้ว

      A1eR that’s what an RCBO does

    • @alerighi
      @alerighi 5 ปีที่แล้ว +2

      @@joefrayling9263 Not the same, RCBO is a single RCD for every circuit, that could be rather expensive if you have a lot of circuits. A 1P+N MCB that also interrupts neutral costs practically as much as a standard MCB and solves the problem without having you buy N RCBO. In my county single pole MCB are practically never used, you always found double pole everywhere.

  • @lrdisco2005
    @lrdisco2005 6 หลายเดือนก่อน

    Excellent explanation from real world experience.

  • @GregoryBryant-fj9bz
    @GregoryBryant-fj9bz ปีที่แล้ว +1

    When making alterations to a circuit covered by a shared RCD (i.e. split load board), I will now disconnect the L, N & E of that circuit to prevent nuisance tripping as well as being a means of isolation. It will need to be done for dead testing anyway!

  • @seanandersonbey3768
    @seanandersonbey3768 4 ปีที่แล้ว

    The moment this man started talking I knew everything was going to make sense..

  • @randomgamingsource9139
    @randomgamingsource9139 3 หลายเดือนก่อน

    Very nice way of teaching I really appreciate it.

  • @michaelcostello6991
    @michaelcostello6991 3 ปีที่แล้ว

    Should an RCBO be single pole or double pole ? Does it matter ?

    • @jwflame
      @jwflame  3 ปีที่แล้ว +1

      Can be either, on TN-S or TN-C-S single pole or double pole is allowed. Single pole is not permitted on TT installations.

  • @alexchong1979
    @alexchong1979 9 ปีที่แล้ว +2

    great teach ! it help me self repair the damage breaker ! thanks John Ward !

  • @kimbo1966
    @kimbo1966 ปีที่แล้ว

    Thanks so much , my broken underfloor heating caused me issues and was tripping the other RCD circuit confusingly, Just disconnected from the thermostat and all good now.

  • @mrloy99
    @mrloy99 9 ปีที่แล้ว

    Just wondering about rcbo's and why they switch only the live cable and not the neutral too...surely it couln't be much more expensive to trip the neutral as well?

    • @jwflame
      @jwflame  9 ปีที่แล้ว +1

      +mrloy99 You can get double pole switched RCBOs, but even a small price difference is enough to make them uncommon.

    • @m.b-ee8815
      @m.b-ee8815 5 ปีที่แล้ว

      @@@jwflame I thought all modern RCBO'S were d.p.

  • @andyr4735
    @andyr4735 3 ปีที่แล้ว

    I was changed a switch and when putting the two neutrals back in the RCD tripped. Is that due to a similar reason?

    • @jwflame
      @jwflame  3 ปีที่แล้ว

      Yes, even with that circuit isolated, the neutral and earth are still connected at the consumer unit, and if they make contact, current can flow there due to loads on other circuits.

  • @JC-jv5xw
    @JC-jv5xw 3 ปีที่แล้ว +1

    A very good case for fitting dual pole RCBOs which are now becoming available. The RCBO will remove the fault if it trips, plus it can be used to fully isolate the circuit.

    • @michaelcostello6991
      @michaelcostello6991 3 ปีที่แล้ว

      Are you saying if the RCBO has a neutral fault it will effect other RCBO's ? Surely that would not cause other RCBO's to trip ?

  • @jacintocosta
    @jacintocosta ปีที่แล้ว

    best explanation ever. as simple as that! thank you!

  • @stephenainsworth629
    @stephenainsworth629 10 ปีที่แล้ว

    Hi jw just like some help with Thailand earth and neutral in the breaker box it seems they join the earth and neutral together as theres only a live and neutral coming into the house I have a earth rod in the ground which is joined with the neutral in the breaker box can I separate them or not

    • @jwflame
      @jwflame  10 ปีที่แล้ว

      stephen brain There is no reason to separate them, and doing so could make things worse than they are. N-E linked in the main panel is a fairly common arrangement in some countries. If local regulations permit that, it is preferable to an earth rod alone, as a metallic earth path will have a much lower impedance. Also fairly common to have a local earth rod as well as the N-E link.

    • @andrewdickson821
      @andrewdickson821 9 ปีที่แล้ว

      no

    • @istoreit
      @istoreit 9 ปีที่แล้ว +3

      ***** But if the N-E is linked, wouldn't that create the likelihood of RCD tripping like what you described in the video? Put it another way, is linking N-E the same as NE fault?

  • @johnmurrell3175
    @johnmurrell3175 4 ปีที่แล้ว

    The other way to look at this is that the Neutral will always be at a potential above Earth due to current flowing in the Neutral - it need not even be current from your property as the Neutral and Live normally feed a number of properties. As the Neutral is at a potential above Earth connecting them will cause a current to flow which may well be sufficient to trip the RCCB. The voltage will fluctuate so if you have a low resistance short from Neutral to Earth there may not always be sufficient potential to trip the RCCB but when others load their circuits your RCCB will trip. Measuring the insulation from Neutral to Earth in your property should find this sort of fault but you need to disconnect the incoming Neutral as this will normally be earthed.

  • @keitho77
    @keitho77 8 ปีที่แล้ว

    Are RCBO's used instead of MCB's in modern/updated installations? If not, should they be?

    • @jwflame
      @jwflame  8 ปีที่แล้ว +2

      RCBOs are the better solution, one for each circuit. A cheaper and therefore more common option is several MCBs connected via a separate RCD as shown in this video, or in newer installations it's usually 2 RCDs in an attempt to ensure some power is still available in the event of a fault causing an RCD to trip.

    • @clarencelodge
      @clarencelodge 8 ปีที่แล้ว

      Ok great video. But what causes the RCD not to reset with any one of 9 mcb's turned on before resetting RCD?

  • @albertkleyn111
    @albertkleyn111 5 ปีที่แล้ว

    Hi John
    EVER So many thanks for this informative video. Now I know when cutting through a cable with the appropriate line mcb OFF, the rcd trips.
    Thank you again. For this brilliant video..
    Please keep up the good work.

  • @xdrcx
    @xdrcx 3 ปีที่แล้ว

    In Australia we always have that connection between neutral bar and earth bar, called MEN link (multiple earth neutral).
    Why, for us, does this not trip the RCDs?

    • @jwflame
      @jwflame  3 ปีที่แล้ว +1

      The link is before the RCD, only the final circuits are connected after the RCD.
      Most supplies in the UK are TNCS, which has the same N-E link, although it's contained within the suppliers equipment before the meter and not normally accessible.

    • @xdrcx
      @xdrcx 2 ปีที่แล้ว

      ​@@jwflame Sorry mate I don't quite understand. With our MEN system (basically looking like 8:10), why doesn't the current split between main neutral and MEN link to earth? Or does it?

  • @ahmedelectricianofiraq5550
    @ahmedelectricianofiraq5550 6 ปีที่แล้ว +1

    We don't use single rcd for hole house but we use about 3 rcd one for lights and one for sockets and plugs and one for air condition so by this 3 rcd we know where the fault happend

  • @427Ayub
    @427Ayub 9 ปีที่แล้ว

    Nice video...I have a doubt that what happens when i short neutral & earth manually.

  • @gatekeeper88
    @gatekeeper88 6 ปีที่แล้ว

    That's why Australia uses a MEN (Multiple Earthed Neutral - A physical wire linking the Neutral and Earth Bars) links, you in a roundabout way described what the link is meant to do in that it'll allow the RCD to detect the imbalance but only on a circuit that has an active load. This has been proved as I've used it to trip an RCD when fault finding in a large board by intentionally creating that imbalance as we couldn't ID the RCD of that circuit.

  • @joebrackenborough1051
    @joebrackenborough1051 3 ปีที่แล้ว

    Thank you so much for your videos it makes so much sense. Really interesting to understand how it all works.

  • @JasperJanssen
    @JasperJanssen 8 ปีที่แล้ว +1

    I'm always fascinated why certain countries choose to do things like this in a particular way.
    I don't think I know of any countries where the N is routinely fused. I do know that in NL there were one or two areas until as late as the nineties or something like that where houses did not have regular 220/230 single or three phase (220-380/230-400) feeds - they had a three phase 127V connection, where the voltage between each pair of phases would be 220. So typical circuits would be between two lives and naturally fused on both sides (which also means that any nonfunctional circuit probably still had power to it).
    OTOH most countries seem to leave the neutral un*switched*, like your UK example. Here in NL however we used to have assemblies of single fuse plus double pole switch per circuit, and we've now switched to breakers that thermally protect the phase and additionally switch the neutral. The N switches on first, and it switches off last.
    Sometimes we get 1.5 unit wide gear, with a normal as-seen-internationally 1 unit breaker plus an additional half unit switch beside, that are mechanically coupled in such a way that the breaker can trip on its own, but if you switch, you can only switch both off, or turn on just the N and then after turn on the breaker. Or the better option, gear targeted to us specifically is just a 1 unit combination breaker and switch with a single switch on the outside. (The savings in din rail space more than make up for the cost of the breakers...).
    Oh: our rules have been changed a decade or two ago to allow no more than 4 breakers per RCD, and a minimum of two RCDs per installation. Also, of course, to no longer allow non-RCD circuits.

    • @alerighi
      @alerighi 6 ปีที่แล้ว +1

      It's the same here in Italy, neutral is allways switched, for me it makes sense to do that, it's more convinent to have only one RCD and then 1P+N breakers, also you are protected in evenience that L and N gets swapped somewhere, that it is possibile.

    • @alerighi
      @alerighi 5 ปีที่แล้ว

      @@mernok2001 Really you don't get any benefit if you have a RCD in the circuit, the same current that passes on L must also pass on N, so even if the polarity for some reason gets swapped you are still protected from short circuit and overload, and you have the RCD that protects you from faults to earth.

  • @HoangNguyen-bo9ek
    @HoangNguyen-bo9ek 8 ปีที่แล้ว

    Hi John. I have 3 phase supply to my house. If I wire 1 RCD to 1 phase only ( say phase A ) to control all circuits ( light & power ) it works well, but if I wire another RCD to other phase ( say phase B ) the RCD trip off, I therefore have to use 1 phase only leaving other 2 phase unused. Could you please instruct me how to use all 3 phases (my house supply is three phase with 4 wires system, A,B.C & Neutral, and I have wired exactly as you have explained in this VDO) . thank you John

    • @zonepohpelonjih2070
      @zonepohpelonjih2070 8 ปีที่แล้ว

      The RCD is a DPDT that is double pole double throw

    • @HoangNguyen-bo9ek
      @HoangNguyen-bo9ek 8 ปีที่แล้ว

      Thank Zonepoh but much appreciated if you could tell me which type of RCD to use on the instantalation to stop the continuous tripping?

    • @scwfan08
      @scwfan08 8 ปีที่แล้ว

      Hoang Nguyen
      Did you maybe connect the neutral to the second RCD after it comes from the first RCD?

  • @Naters305ytg
    @Naters305ytg 9 ปีที่แล้ว

    What is the difference between RCD and GFCI or GFI I assume they are the same thing just with different ratings for the different voltage ratings in the us and canada.

    • @jwflame
      @jwflame  9 ปีที่แล้ว

      +Naters305 Essentially the same device, just different names.

  • @williefleete
    @williefleete 9 ปีที่แล้ว

    I've had this happen when I made up an adapter for a caravan to run on a regular 10amp NZ socket (for the lighting and light loads). The caravan fuse box had a linked neutral and earth bar and would trip the RCD when plugged in. I had to remove (cut) the earth neutral link while still keeping the earth neutral wires connected to the plug on the caravan

  • @ShahSaad
    @ShahSaad 8 ปีที่แล้ว

    Thank you. That was very well explained. Does the ELCB works on the same principle?

    • @jwflame
      @jwflame  8 ปีที่แล้ว +2

      Yes, ELCB is just another name for the same device (earth leakage circuit breaker), current operated in this case.
      The only ones which are different are voltage operated devices also called ELCBs, but they have been obsolete for decades.

  • @enggind365
    @enggind365 9 ปีที่แล้ว

    Why you have connected the neutral return from the lamp to the neutral bar instead of directly to the RCD, which causes the current to be split with other circuits?
    I guess the neutral bar is for connecting the incoming neutral.

    • @jwflame
      @jwflame  9 ปีที่แล้ว

      Karoly's The neutral bar is provided to connect the neutrals from each circuit, so that there is one terminal hole for each wire. It would be impractical to fit a dozen individual wires into a single terminal on the RCD.
      The incoming line and neutral connect directly to the RCD, the top terminals in the example in the video.

  • @Raj-cf6fe
    @Raj-cf6fe 4 ปีที่แล้ว

    I have my multimeter continuity beeper , beep when i connect neutral and ground. Is that normal??

    • @jwflame
      @jwflame  4 ปีที่แล้ว +1

      On some systems yes. Neutral and ground are connected together at the transformer.

    • @Raj-cf6fe
      @Raj-cf6fe 4 ปีที่แล้ว

      @@jwflame I have the grid Neutral coming to the distribution box and Ground is connected to the Earthened Copper Rods beside the house. So what can be wrong?

    • @johnmurrell3175
      @johnmurrell3175 4 ปีที่แล้ว

      @@Raj-cf6fe The neutral is probably grounded at the distribution transformer by rods driven into the Earth ( the brown crumbly sort ) thus the neutral & your local electrical earth are connected together via the brown crumbly earth. I am not sure what the normal resistance is.between two sets of earth electrodes but it should be quite low to provide protection.

  • @andrewwhite3793
    @andrewwhite3793 3 ปีที่แล้ว +1

    I get this a lot and try and help the customer over the phone where they will say but I have switched off the kitchen appliances at the socket. My reply is pull the plug out as the RCD still detects the fault via the neutral. They fight me tooth and nail then when they do it I get O thats the RCD reset ?
    I say great just saved you a callout so will you give me a review YEA YEA the reply I get
    Thing is they never do

  • @TheLulisBlue
    @TheLulisBlue 7 ปีที่แล้ว +1

    Thank you very much, that helped me to fix my fault last evening

  • @diprobase1000
    @diprobase1000 7 ปีที่แล้ว

    How come you don't get a shock from the neutral bar when the same current is flowing through it as in the busbar

    • @jwflame
      @jwflame  7 ปีที่แล้ว

      Neutral is at or very near the same voltage as ground.

    • @Ahmadalias1
      @Ahmadalias1 4 ปีที่แล้ว

      You get shock if there is an opened or loaded neutral. True boss?

  • @fragglepuppies
    @fragglepuppies 4 ปีที่แล้ว

    Thanks John. Exactly what I am experiencing with my oven at the moment.

  • @TheIcebon
    @TheIcebon 6 ปีที่แล้ว

    I have a lighting circuit which trips on rcd even when all the switches in that lighting circuit are off and nothing drawing. What reasons can cause this? Would it need to be a live fault

    • @jwflame
      @jwflame  6 ปีที่แล้ว

      Could be a L-E fault, although that would normally cause the MCB to trip (or fuse to blow). It could also be a N-E fault, it's not always necessary for there to be a load on that circuit, loads on other circuits connected to the same RCD can still cause it to trip even if the N-E fault is on a different circuit.
      Also check that there really is nothing else connected to the lighting circuit, things like smoke alarms and TV amplifiers in the loft are fairly common things to find connected to lighting circuits.

    • @TheIcebon
      @TheIcebon 6 ปีที่แล้ว

      Thanks John for the info, I have a feeling the outdoor light is off the same circuit, also the shower extractor fan, so will check those before I get an electrician out. Many thanks for the helpful vid. Matt

    • @jwflame
      @jwflame  6 ปีที่แล้ว

      Both fans and outdoor lights are very likely causes as they can get water inside them.

  • @g0fvt
    @g0fvt 3 ปีที่แล้ว

    An excellent explanation as always, in our house we have a single ring main serving both floors, the RCD drives me crazy. We have lots of low power devices around the house some inherently generating a little earth leakage current. Naturally it will maliciously wait until about 2:00am before it trips, to be fair there is always a good reason. (Last time it was the cordless kettle base had water spilt on it). I really should investigate splitting the supply to two rings, seems strange that a modernish 3 bedroom house would only have one....

    • @jwflame
      @jwflame  3 ปีที่แล้ว +1

      The concept of a ring for the whole house was several decades before RCDs were in common use.
      As almost all circuits in a modern installation require RCDs, the more sensible solution is multiple circuits each with their own separate RCBO.

    • @g0fvt
      @g0fvt 3 ปีที่แล้ว

      @@jwflame, the house is 1970s which sadly I regard as relatively modern. And yes having more circuits would be a great advantage, thank you for your videos, and this reply.

  • @jayjwin1178
    @jayjwin1178 3 ปีที่แล้ว

    thanks John for explaining this.