Allen Bradley powerflex 4m parameter settings.

แชร์
ฝัง
  • เผยแพร่เมื่อ 11 ธ.ค. 2024

ความคิดเห็น • 4

  • @user-dz1nm6ed4y
    @user-dz1nm6ed4y 6 หลายเดือนก่อน +1

    Hello! You can clarify about the parameter P103. What current should I set if the rated current of the motor is 5 Amperes when connected by a triangle. Should I set 2 times less than the overload current by 150 percent and divided by 2, that is, 3.75 Amperes? Or are the overload parameters set in section A?

    • @user-dz1nm6ed4y
      @user-dz1nm6ed4y 6 หลายเดือนก่อน

      @@c4circuit Thanks for the reply. As I understood from the manual, the motor current min 0.00 max x2 is set in the P103. And if the current consumption
      if it exceeds the setpoint in P103 by 150%, then after 60 seconds, the error F 07 should occur and the drive will stop the engine or by 200%, then after 3 seconds. The current consumption of the engine is shown in D 103 3.2 A instead of 5A, as indicated on the engine when connected by a triangle. To be more precise, the 1.1kW 380 V motor consumes 2.9 A , and the 220V 5A triangle. I connected it to a triangle, since the frequency converter is from one phase to three 230 V. I set the setpoint 2.1 A in P 103 and the drive gave an error F07 a minute later and stopped the drive. It's a pity I didn't check the current with an external device. So it will turn out strangely if you set the setpoint to x2 of the nominal value of the engine. Have you checked the actual operation with the current set in the drive and the current consumption of the engine?

    • @c4circuit
      @c4circuit  6 หลายเดือนก่อน

      Thank you we will check and get back to you soon.

    • @user-dz1nm6ed4y
      @user-dz1nm6ed4y 5 หลายเดือนก่อน +1

      I checked it out. In this parameter, you need to set the rated current of the motors. If it is 5 A, we set 5A. There is no need to apply any multiplicities to the motor current.