Calculating Voltage Drop

แชร์
ฝัง
  • เผยแพร่เมื่อ 21 พ.ย. 2024

ความคิดเห็น • 62

  • @Jayson8181
    @Jayson8181 4 ปีที่แล้ว +8

    There is so much garbage out there, I'm really happy to find someone who is clear, easy to understand and stays focused on the question at hand. Thanks and keep on doing what you're doing!

  • @KevinCoop1
    @KevinCoop1 4 ปีที่แล้ว +3

    As a designer for a contractor and doing thousands of calculations over the years, I always wanted to know the wire size needed in one calculation. I did not want to keep guessing until I got less than 3%. Less complicated method. 2xKxampsxLdivided by 3% of voltage= cm. Conductor properties table will give you needed wire size. Also, for balanced 3 phase 3 wire multiply single phase calculation at end by .86. 1.73/2=.865. And for balanced three phase 4 wire, multiply single phase calc at end times .5. If balanced load, then no neutral current. 1/2=.5.
    Respectfully submitted, Kevin

  • @12mandingos
    @12mandingos 5 ปีที่แล้ว +2

    Thank you for putting these videos together! For someone getting underway in the trade I find these videos very helpful. Shout out to the 209 too!

  • @frankvieira764
    @frankvieira764 2 ปีที่แล้ว

    I think you're Portuguese, but I love you're videos. Thank You.

  • @jeremiahwoodhull6122
    @jeremiahwoodhull6122 ปีที่แล้ว +1

    Thank you for your time in making this video. It is easy to follow along and understand. Especially on impedance. Once again thank you.

    • @AccessToPower
      @AccessToPower  ปีที่แล้ว

      Thanks for commenting. I appreciate the feedback.

  • @energyexecs
    @energyexecs 2 ปีที่แล้ว +1

    ...Nice learning video. I also like using Z (the impedance) because it provides a glimpse for the human that impedance plays an important role in voltage delivery to the end point.

  • @crisrobersonsantos9192
    @crisrobersonsantos9192 3 ปีที่แล้ว +1

    Thank you very much for the very clear, detailed and straight forward video lesson. This helps me a lot on my studies.
    NEC Table 9 have a title of:
    Alternating-Current Resistance and Reactance for 600-Volt Cables, "3-Phase", 60 Hz, 75C (167F) - Three Single Conductors in Conduit
    May I kindly consult if we can use NEC Table 9 for 1-Phase circuits?
    even though the title indicates "3-Phase"
    Thanks again and more power to your channel.

  • @Mahle-f2b
    @Mahle-f2b 13 วันที่ผ่านมา

    Great explanation. Thank you very much.

  • @ernestocortez2957
    @ernestocortez2957 4 ปีที่แล้ว +1

    Thank you! Im getting ready to take my state test here in CA this Saturday. I'm ready for a voltage drop question.

    • @AccessToPower
      @AccessToPower  4 ปีที่แล้ว +1

      Ernesto Cortez, thanks for the comment. Good luck on your test.

  • @ethanbrewer14
    @ethanbrewer14 4 ปีที่แล้ว +1

    Thank you for this video! It helped me a lot in understanding and feeling confident in my calculations.

  • @georgegenteroni6645
    @georgegenteroni6645 2 ปีที่แล้ว

    Thank you for the clear discussion abou voltage drop.

  • @bcv3934
    @bcv3934 5 ปีที่แล้ว +1

    Another good informational video👍
    Your doing such a good job for those who want to learn more and improve.

  • @davidjackson4112
    @davidjackson4112 ปีที่แล้ว

    Thanks for your help in solving voltage drop calculation.

  • @azscib
    @azscib 4 ปีที่แล้ว +1

    That was such a WELL done video. So clear and precise! great job. Others should follow as some ramble through their videos. Again ~ thank you!!!!

    • @AccessToPower
      @AccessToPower  4 ปีที่แล้ว

      Rich Scibetta thanks for the great comment!

  • @Buhzuka
    @Buhzuka 4 ปีที่แล้ว +1

    Super Helpful! Good Informational video!!

  • @rickydags
    @rickydags 3 ปีที่แล้ว +1

    Thank you for this video. Question for you about the impedance for the single phase case. The Chapter 9 Table 9 of the NEC says in the title that it is for three phase power, but you used it in the single phase case. Is there something in the NEC that indicated that table 9 can be used on the single phase case or is there another table for the single phase case?

  • @ankitpanchal5766
    @ankitpanchal5766 3 ปีที่แล้ว +1

    Great video. But can we use Vd = 2*L*R*I / 1000 formula?

  • @tedecacao
    @tedecacao ปีที่แล้ว +1

    Thank you so much for this video! Subscribing now

    • @AccessToPower
      @AccessToPower  ปีที่แล้ว

      Thanks! Glad the video was helpful!

  • @elc2k385
    @elc2k385 3 ปีที่แล้ว +1

    Awesome! Thank you once again.

  • @victorvasquez5418
    @victorvasquez5418 4 หลายเดือนก่อน

    Good job thank you for your help

  • @yasirjohny
    @yasirjohny 5 ปีที่แล้ว

    Thanks A lot , your method of teach is very unique I completely understand of VD calculations. 🌹🌹🌹

  • @bojitti
    @bojitti 4 ปีที่แล้ว +1

    Thanks a lot. I find this very useful.

  • @peterponcedeleon3368
    @peterponcedeleon3368 4 ปีที่แล้ว

    Thanks!! Keep them coming.

  • @reyniernunezbeltran2730
    @reyniernunezbeltran2730 ปีที่แล้ว +1

    Both methods should give equivalent results. The reason why using table 9 gives you a slightly different result is because eddys current (Q) losses is not taken into account. But if (Q) is used both methods should be 99.9 % equivalent.

  • @washingtonmazzini9120
    @washingtonmazzini9120 ปีที่แล้ว

    GOOD AFTERNOON, I HAVE THE FOLLOWING QUESTION: IF A THREE-PHASE FEEDER IS INSTALLED IN A METAL WIREWAYS, TABLE 9 IS APPLIED TO CALCULATE THE VOLTAGE DROP?

  • @bryanbecker
    @bryanbecker 11 หลายเดือนก่อน

    When would one use the “coated” section?

  • @pululunguente
    @pululunguente 7 หลายเดือนก่อน

    And what about you having 2 sets of conductors with Z method? Please Help!!

  • @omargarcia4401
    @omargarcia4401 3 ปีที่แล้ว

    Great video only issue with using the table 9 formula with impedance (z value) is that the impedance of Table 9 is only good for 3phase - Three single conductors in conduit as per the title of that Table so I’d assume it’s not totally accurate for use with Single Phase Voltage drop calculations. Sorry to be that guy.

  • @aimansado3457
    @aimansado3457 4 ปีที่แล้ว +2

    where can I get the formula book? internet?

  • @rowellcanillo7469
    @rowellcanillo7469 7 หลายเดือนก่อน

    Is table 8 is only applicable in DC system?

  • @josemarti8642
    @josemarti8642 4 ปีที่แล้ว +1

    How do you factor in multiple runs of conductors into that Voltage Drop equation?

    • @rupe53
      @rupe53 3 ปีที่แล้ว

      Jose ... you need to figure the drop for each run separate then add up the results for the whole run. If the numbers are too high (percentage of drop) then you need larger wire. You will almost never have a problem if you stick to 80% loading of a branch circuit and stay under 100 ft in a run. To ease the brain work use one of the voltage drop calculators on the web. You plug in wire size, load, and run length. They will tell you voltage drop and percentage. After you use it a few times you will get a feel for where you need to be.

  • @bluesolarmx
    @bluesolarmx 3 ปีที่แล้ว

    If using meters, for example with a 10AWG cable, would it be the same? 4.070*10380/1000m?

  • @matthewgaskey4954
    @matthewgaskey4954 4 ปีที่แล้ว

    good video! a couple questions tho. How did you get 2.75% from 13.20 in the single phase method (15:27) and your applied voltage cell reads 480. thanks

    • @AccessToPower
      @AccessToPower  4 ปีที่แล้ว

      Matthew Gaskey also, this calculator may be helpful. www.calculatorsoup.com/calculators/algebra/percent-difference-calculator.php

  • @Rabb_L_Rouser
    @Rabb_L_Rouser ปีที่แล้ว

    Why does no one bring up how to find voltage drop of wire larger than 4/0? I need voltage drop of 850ft run of single conductor aluminum 750kcmil, 3000A.

  • @christopherestevez6375
    @christopherestevez6375 4 ปีที่แล้ว

    Only thing is i couldnt find where to find chapter 9 table 8 in my nec book

  • @JoesCountryGarage
    @JoesCountryGarage 2 หลายเดือนก่อน

    Please HELP looking for someone that's very good with voltage drop on extremely long runs on Main Service cable I'm running 4/0 4/0 4/0 2/0 aluminum direct burial to my shop 670 FEET away. I have 250 volts at my main panel I'm trying to understand how many effective amps I will really have when it gets to the shop I understand there's a big voltage drop and a loss of amperage but can anyone tell me what that would actually be or close to it I have tried voltage drop calculators online but I'm getting differentials that don't make sense. Trying to know if I would at least have enough amps to run a compressor welder and possible mini split with lights I understand I will be running close to capacity but need to know if it's really worth the extra $3,000 to do an extra run alongside my current run so that way I don't need to rip it out. How many usable amps should I expect for the shop.

  • @hoovie3000
    @hoovie3000 3 ปีที่แล้ว

    Why can't we use Chapter 9, Table 9 of the NEC?

  • @amadogomez436
    @amadogomez436 4 ปีที่แล้ว +1

    Great

  • @562sela8
    @562sela8 4 ปีที่แล้ว

    nice vedios

  • @Studi314
    @Studi314 4 ปีที่แล้ว

    Is the second formula 2xZxDx(I /1000) the way you have it written or is it really ( 2xZxDxI)/1000?

    • @AccessToPower
      @AccessToPower  4 ปีที่แล้ว

      Studi314, I’m not sure what you’re referring to because I have a written (2xZxDxI)/1000.

    • @Studi314
      @Studi314 4 ปีที่แล้ว

      At the time 13:00, the formulas do not have any parenthesis in them.

    • @AccessToPower
      @AccessToPower  4 ปีที่แล้ว

      Studi314 , I see what you’re saying. It would’ve been helpful to have the formulas with parentheses. But also under the rules of orders of operation in math, multiplication always comes before division. So the formula is correct with the parentheses or not but it is more helpful with the parentheses

  • @johnnytotheworld4802
    @johnnytotheworld4802 4 ปีที่แล้ว

    Which cable is affected by the voltage drop?

  • @veritasaequitas9875
    @veritasaequitas9875 4 ปีที่แล้ว

    CM in the equation. What are Circular Mills?

    • @veritasaequitas9875
      @veritasaequitas9875 4 ปีที่แล้ว

      It's ok. Got it. Just wondering what's wrong with square mils. Or even square inches.

    • @AccessToPower
      @AccessToPower  4 ปีที่แล้ว

      circular mills is the circular cross section of the wire we are examining. You can find the CM for each size of wire in Chapt 9, Table 8 of the NEC. Check minute mark 12:38 and you will see that table.

  • @josericardomarin6911
    @josericardomarin6911 5 ปีที่แล้ว +2

    Hola boss this Is José Marín can you please maje a vídeo for load calculacions for motors.
    Thanks

    • @AccessToPower
      @AccessToPower  5 ปีที่แล้ว

      hey Jose. hope all is going well with you... I will try and do a video on that subject.

    • @mikechan-nel8390
      @mikechan-nel8390 5 ปีที่แล้ว

      @@AccessToPower sir what is the formula to get the percent?

  • @oscar27ization
    @oscar27ization 4 ปีที่แล้ว +2

    You said single phase formula but the voltage drop was 480??? Wasn’t suppose to be 120v

  • @Michael-v4m2i
    @Michael-v4m2i 3 หลายเดือนก่อน

    Your great but we are gonna have to ask you to stop teaching us using spreadsheets. We cannot use them while taking the exam.