Sir kirloskar company ka 40 kva three phase chock wala altinator hai humne Charo filed winding Kiya to bhoot jeyada hit hone lega to transformer hta ker avr lgaya to bilkul shi hogeya abhi short hone se avr khrab hua Hai to dursa avr lgane se feer do coil gram ho rhi hai
Amit bhai JCB ka DG genset hai L1 240 L2 240 L3 m 218 aa jaati voltage... please suggest solution uske baad DG beep beep karne lg jaata hai or bund ho jata hai...first phase 4Amp 2nd phase 5 Amp or 3rd pr 28 Amp dikha rha hai
In my DG There is voltage fluctuation y phase only other phase ok. After some time y ph voltage going under voltage also , its fluctuation from 180 to 220 v. But other ph its 230v , plz advice me the troubleshooting.
Sir mere pass 110 kva ka dg set hai dg set jyada voltage bana raha hai chake kiya to singal fhase me 315volt dikha raha hai jabki 240 dena chahiye aur duble fhase me 540 volt dikha raha hai jabki 415/420 hona chahiye isme kya problem ho sakta hai sir....
Sir mere pass 110kva dg set hai dg set jyada voltge bana raha hai single fhase me chake kiya to 315 de raha hai jabki 240 dena chahiye aur duble fhase me 540/545 de raha hai jabki 415/420 dena chahiye bataiye sir isme kya problem jo sakta hai plss
@@ElectricalAmit1 bhai aap apna WhatsApp no de sakte hai mere pass avr hai but 12 volt se kaise check kare aapne avr mai bataya per mere pass avr badi hai kafi sare wires hai
@@ElectricalAmit1 janrator 1100 kW 380 ka hai voltage starting mai 40 volt aa rahe deaod change kar diya uske baad 170 volt aa raha hai avr available nahi hai extra
@@ElectricalAmit1 sir mega DG Voltage unbalanced banaraha he ph1-380, ph2-380, ph3-500 Voltage ban raha he what is the problem and I change AVR also same problem
Mere pass 25 KVA ka dijiye hai kabhi kabhi apne aap band ho ja raha overload dikha kar kabhi kabhi Lal button ko ham dawat Hain band karne ke liye hi hua reading aata hai bad mein fir se chalu ho jata aur welding machine chalane se ho overload karke band ho iska kya solution
Check excitation voltage on load,should not show down,it should be gradually increase as per load increase,otherwise check ecitor stator and rotor winding...
सर आपका वाट्सएप नम्बर मिल जाऐगा अगर जनरेटर सेट में कोई दिक्कत या टेक्निकल प्रोब्लम है तों आपको वीडियो या फोटो भेजकर समस्या का समाधान पा सके सर हमारे कमेंट का जवाब जरूर दीजियेगा
आप सही से बताते हैं सर 👍
Physical training de rhe ho app
Jabardast video
Tq
Tq so much sir.... What dedication to make the video... Super sir❤
Please do more videos
Tq
It's good Idea,I tried and it was successful
Tq
Thanks very good knowledge given
Very nice information sir 🙌❤️🧿
Tq
Very nice explain sir
Bhot achha sir
Very good Knowledge
👌👌nyc explain
Tq
Good job brother
Tq
Exciting field Mein current dene ke liye Negative positive Kahin bandh Diya Ja sakta Andar Se Khud Hi Ho transfer kar leta hai apni DC manfield
Great gankarey sir
Thanks
Very nice thanks sir
Nice video sir ji
1 number sir
very nice, very good❤
Sir kirloskar company ka 40 kva three phase chock wala altinator hai humne Charo filed winding Kiya to bhoot jeyada hit hone lega to transformer hta ker avr lgaya to bilkul shi hogeya abhi short hone se avr khrab hua Hai to dursa avr lgane se feer do coil gram ho rhi hai
Very useful video
Thenks you sir ji
Good teaching sir
Amit bhai JCB ka DG genset hai L1 240 L2 240 L3 m 218 aa jaati voltage... please suggest solution uske baad DG beep beep karne lg jaata hai or bund ho jata hai...first phase 4Amp 2nd phase 5 Amp or 3rd pr 28 Amp dikha rha hai
Very nice
Very nice 👍
Tq
❤ thankyou sir
Great 👍🏻👍
Tq
Kya bat h yar good ho gya
Sir mera 45 kva singal phase h ganretor stad karne pe 250 voltez de raha lekin lod dene ke bad 50 ampr dalane ke 30 min bad voltez 160 ho ja raha h
Avr check kariye
Super sir
Load dalane per voltage 4 bar up dowen kar raha hay 40 k.v.a single phas kya karaiy sir
Fault code kay aa raha haai
Abhi singal phase me convert Kiya hai shi hai lekin char sodium light per 10 volteg drop ho rha hai
Thank u
Nice
Thanks
Sr 5kb, 5kb janetar kmila ke 10 kb hojaiga 7kilo way motar chlan hi
Ha
In my DG There is voltage fluctuation y phase only other phase ok. After some time y ph voltage going under voltage also , its fluctuation from 180 to 220 v. But other ph its 230v , plz advice me the troubleshooting.
Dg ka rpm sahi rahta hai
Yes maxm it goes 1510
Sir mere pass 110 kva ka dg set hai dg set jyada voltage bana raha hai chake kiya to singal fhase me 315volt dikha raha hai jabki 240 dena chahiye aur duble fhase me 540 volt dikha raha hai jabki 415/420 hona chahiye isme kya problem ho sakta hai sir....
Thanks bhai
Thanks
Minor trouble shoting kya hota hai sir espar ek video banao sir please
Thanks sir
भाइ साब DG मे auto stop timer कैसे सेट करे सिकादिजिये
Sir mera 320 kva Dg me 410/404 volt dekhata he. thik he kya
sir mere pass 62.5kva Dg he usme bhi voltech problem ho Rahi he tin fej me alag alag voltech dikha Raha hai use solve kaise kre sir plz batav
Sir mere pass 110kva dg set hai dg set jyada voltge bana raha hai single fhase me chake kiya to 315 de raha hai jabki 240 dena chahiye aur duble fhase me 540/545 de raha hai jabki 415/420 dena chahiye bataiye sir isme kya problem jo sakta hai plss
Good 👍 sir hamara jarneta display par hz likh kar bar bar band ho jata hai iska rijan bataye
Generator me current produce ho raha PN me 220 v raha hai naya avr replace kiya to bhi PN me 113v aa raha hai kya problem ho sakta hai
Abhi singal phase me convert Kiya hai shi hai lekin char sodium light per 10 volteg drop ho rha Hai sir please solution btaye
Can you do this video in English? You will get lots of English speaking viewers.
Sir dg battery boltese thik hai but dg k display me battery boltese low warning kiu dikha Raha hai
Mera 62.5 ka dg hai 30 30 ampere load dalne par voltage dab jata hai
Kitna drop hota h
Start power ka display hai jismein Maine khud se start aur switch se off Karta karna hai generator vah kaise lagega sar mere ko
👍
Cumins 250 dg trip ho rha hai
Chalu krne pr auto se ht jata hai or bnd ho jata hai
DG ka voltage kam jada ho raha hai esaliy lift drip hota hai
Rpm kitna hai dg ka
Neutral ki wire me current show karta hai aur R phase wire me current dikha raha hai. 3phase DG hai company name manindra 40 kva.
Nutral wire phase ke sath kahi pe tuch hoga nahi to koi phase ground hua hoga check kariye
@@ElectricalAmit1 shukriya jawab dene ke liye. Darasal problem ground earthing thik tarah se nahi tha. Ab sahi ho gaya hai.
Par party ka bahut nuksaan ho gaya hai.
Hamera DG ek face nhi day rha ha
2 face ma full light ha ek ma kam light ha aur neutral ma bi face show kr rha ha kya problem ha sir usma
Neutral charge ho gaya hoga aapka tino phase kaam kar raha hoga par jis phase se neutral charge hua hoga oo tester me supply so nhi kare ga
also check neutral ground earth properly..
Emergency mai kitna time chala sakta hai
Aap jitna Kam chalao ge utna sahi h kyu ye aise voltage bhi kam dega
@@ElectricalAmit1 bhai aap apna WhatsApp no de sakte hai mere pass avr hai but 12 volt se kaise check kare aapne avr mai bataya per mere pass avr badi hai kafi sare wires hai
@@ElectricalAmit1 janrator 1100 kW 380 ka hai voltage starting mai 40 volt aa rahe deaod change kar diya uske baad 170 volt aa raha hai avr available nahi hai extra
Channel ke about me h
Mera 400kva dg pe voltage 415 barbar raheta he but jyada load pe phase neutral pe kapho variation hota he
aapka lode tino phase pe barabar nahi hoga
@@ElectricalAmit1 50 amp ka different he
@@ElectricalAmit1 sir mega DG Voltage unbalanced banaraha he ph1-380, ph2-380, ph3-500 Voltage ban raha he what is the problem and I change AVR also same problem
Control board me main input 12v positive kon sa hota hai
Mere pass 25 KVA ka dijiye hai kabhi kabhi apne aap band ho ja raha overload dikha kar kabhi kabhi Lal button ko ham dawat Hain band karne ke liye hi hua reading aata hai bad mein fir se chalu ho jata aur welding machine chalane se ho overload karke band ho iska kya solution
Battery me full voltage hai parbi dg chalu kortei voltage kom ho ja rahe chalu nhi horaha
Battery thik nahi hai ya charge nahi hai is liye lode pe voltage drop ho raha hoga
AVR Price 125 kva DG set
Sir mujhe ak problem haa may kaise up se baat karsakta hu
Sir frequency set kese krege AVR se
th-cam.com/video/I87d-en_omk/w-d-xo.html
Check kaise kare 10 second me dg stop hojata hai 1447 fault code ata hai kia kare
Sir DG high voltage fault kiya hai
engin heet kin kin kaarno से hota hai
Bhaiya dg water body kyo Tut jati hai?
50 kva generator how to rpm adjust in fuel pump.
What will be the avr dc output max ?
th-cam.com/video/I87d-en_omk/w-d-xo.html
@@ElectricalAmit1 very nice demonstration brother thanks for the informative video 🙏💐
7 to 12v dc
500kva dg load par voltage down hota he avr bhi change kar di he phir problem solve nahi ho rahi he
aap yak baar alternator ka exciter steter ka coil ko check kijiye ho sakta h oha par voltage kam banta hoga
Need charge lamp
Check excitation voltage on load,should not show down,it should be gradually increase as per load increase,otherwise check ecitor stator and rotor winding...
AVR set krain
AVR settings ka bhi video channel pe hai dekh lijiye
Wo pta hai g thanks brother
Sar dg chalu karna ka bad band ni hora ka problam hosakt ha
stop sonlid ka supply nahi kat ho raha hoga relay se
Sir loss ac sense sh aarha hai
JAKSON 125.5 KVA DG FAULT NO 0442 SOLUTION KIYA HI
Helo ser ser m penel ka ka kam krna chahta hu ser Kay aap marg drsen krenge
100%
Good morning sar hamara Ashok Leyland 62.5 dg me under Bolt dikha kar band Ho Raha hai kya Karen
Three phase alternator Kirloskar ka
एक फेस नही आता प्रॉब्लम बताए
Voltage kam keise kare
Rpm ko kasa adjustment karna hey bhai
Video bana dunga
@@ElectricalAmit1 thnku
Rpm kese addjest karte Hain sir otherwise video is good in fule pumps
Avr gaiya hi
एक ही बात बार बार बोलते हो,विडिओ लंबा करते हो...
Sir pll mob no
Channel ke about me h
सर आपका वाट्सएप नम्बर मिल जाऐगा अगर जनरेटर सेट में कोई दिक्कत या टेक्निकल प्रोब्लम है तों आपको वीडियो या फोटो भेजकर समस्या का समाधान पा सके सर हमारे कमेंट का जवाब जरूर दीजियेगा
Channel ke about me mera number hai
Thanks sir