We have Yokogawa's PLC through which if we give a command of 4-20mA to a positioner then it shows 1.29mA at 0% due to which the positioner stops and if we give 1% command then it comes back to 4mA and at 100% it comes to 20mA and after removing both the wires from the positioner we check 4-20mA again then on giving 0% command from DCS the same 1.29mA comes and on giving 1% command it comes to 4mA. What should we do in this condition
Sir please MPILC % output wala leval sensor ke bare me ek vedio banaiye.... jo continue leval show karta hai percentage me. vo kis principal par kam karta hai...uski working kya hai... ?
Very good class thankyou sir West Bengal se ❤
Very good sir
Guru ji control valve ka full video banaeya Guru ji please 🙏
Sir aap Mali comunity sa belong karta ho kya 😊
We have Yokogawa's PLC through which if we give a command of 4-20mA to a positioner then it shows 1.29mA at 0% due to which the positioner stops and if we give 1% command then it comes back to 4mA and at 100% it comes to 20mA and after removing both the wires from the positioner we check 4-20mA again then on giving 0% command from DCS the same 1.29mA comes and on giving 1% command it comes to 4mA. What should we do in this condition