@Eli de la Torre the wall connector only need 2 hot (120v each) and a ground. Use at least 6 gauge for the hots, had I been able to find 4 gauge I would have use it since even with 6 gauge and charging at max of 48 amps the wires do get warm. Since I’m not rushing to charge I just decrease the amp to 32 and it still charges fine overnight.
Interesting, I thought you needed to use two hots (blk & red) and a Neutral to the panel, then a ground to the panel?
@Eli de la Torre the wall connector only need 2 hot (120v each) and a ground. Use at least 6 gauge for the hots, had I been able to find 4 gauge I would have use it since even with 6 gauge and charging at max of 48 amps the wires do get warm. Since I’m not rushing to charge I just decrease the amp to 32 and it still charges fine overnight.