Trane sensor bind in step by step TechView

แชร์
ฝัง
  • เผยแพร่เมื่อ 28 ส.ค. 2024
  • Step by step hvac trane sensor bind in with tech view. Centrifugal chiller or air cooled chiller sensors. Texas hvac learning video

ความคิดเห็น • 52

  • @swank1975
    @swank1975 หลายเดือนก่อน +1

    This video was a lifesaver today. We had a new oil pump high current relay board installed but needed it bound. Easy download and install of Techview, used the magnet on my flashlight on the board beside the com cable connection to get the green light on then it bound and we're up and running again. (replaced the capacitor at the same time). Thanks for sharing.

  • @ZeroGameplays117
    @ZeroGameplays117 2 ปีที่แล้ว +3

    Ur the Best, men

  • @GrumpFish22
    @GrumpFish22 3 ปีที่แล้ว +1

    Thanks for the walk through. Saved me a lot of money!

  • @autolancegega599
    @autolancegega599 2 ปีที่แล้ว +1

    Thanks a lot for sharing this video and it was really helpful. I will share the video with my other colleagues. Keep posting new videos and may your channel grow.

  • @HVACTechGuidebysreejith
    @HVACTechGuidebysreejith 3 ปีที่แล้ว +2

    Valuable information. Thank you sir

  • @leeeng478
    @leeeng478 3 ปีที่แล้ว +1

    Thanks man we have the same system. Tons of good information!

  • @kurniawan76
    @kurniawan76 ปีที่แล้ว +1

    Nice info ... Thank you bro

  • @neilskelly7970
    @neilskelly7970 2 หลายเดือนก่อน

  • @abdelouahedchibane
    @abdelouahedchibane 10 หลายเดือนก่อน +1

    Ok merci thanks

  • @bernardviyuyi8974
    @bernardviyuyi8974 ปีที่แล้ว +1

    Great video. We have a situation where we can't reset communication loss fan stage 1,2 and 3. All plugs and the cable are OK. What could be the problem?

    • @Junkremoval-hvac
      @Junkremoval-hvac  ปีที่แล้ว

      If plugs and cables are good it has to be what they are wired in to like a bored or something went bad.

  • @irfvnfaedah5776
    @irfvnfaedah5776 2 ปีที่แล้ว +1

    Sir,i have some binding issue,i can lightup the led at the liquid level sensor,but when i bind the techview says unnnable to find selected device
    The liquid level is a new part installed
    Then i do binding the old liquid level and i had same problem, i have change module ch530 and doesnt work , is my new liquid level part is defective

  • @edwardcrane7520
    @edwardcrane7520 3 ปีที่แล้ว

    Awesome video

  • @user-ts2nd9qy1m
    @user-ts2nd9qy1m 4 หลายเดือนก่อน

    Is it possible to get Castrel View

  • @_Padma_TausikHasan
    @_Padma_TausikHasan 3 ปีที่แล้ว +1

    Why is it necessary to hold a magnet on the LED to bind the sensors of the trane brand chiller?
    Why and how does the LED light up when you hold the magnet?

    • @Junkremoval-hvac
      @Junkremoval-hvac  3 ปีที่แล้ว

      Not sure how but using the magnet lights up the sensor. Reason you light it up is because they computer will ask if it’s lit up so it knows the proper sensor to bind in. There are many in the system.

  • @maxwolfhunt23
    @maxwolfhunt23 3 ปีที่แล้ว

    hello, is this working for the expension valve?
    Tank you

  • @andryushkurin2287
    @andryushkurin2287 2 ปีที่แล้ว +1

    Show and explain how to tie and untie the control boards

    • @Junkremoval-hvac
      @Junkremoval-hvac  2 ปีที่แล้ว

      I will definitely show once I run across that. Have not yet.

  • @diananggara5977
    @diananggara5977 8 หลายเดือนก่อน +1

    hello sir, can i get trane chiller software?

    • @Junkremoval-hvac
      @Junkremoval-hvac  8 หลายเดือนก่อน

      Yes just have to go to trane website and download off there.

  • @fkdeazevedo
    @fkdeazevedo 2 ปีที่แล้ว +1

    Why is it when I click local connection it ask me to select communication port com 1, 2 , 3 which one is it ? Do o Try em all to see which one please help. I have techview latest version 14.0 and the 14.0 sp16 install both please help.

    • @Junkremoval-hvac
      @Junkremoval-hvac  2 ปีที่แล้ว

      I have not ran into this issue before. I would say, yeah try em all see what happens. Sorry unable to help in this question

    • @jevonhoward
      @jevonhoward 2 ปีที่แล้ว

      Go to device manager on your computer while the adapter is connected to see which Com port is in use.

  • @nafissiddiqui5009
    @nafissiddiqui5009 ปีที่แล้ว

    From where we can download and install Techview CH 530

  • @EfrenBParal
    @EfrenBParal 2 ปีที่แล้ว

    Hi where can we download software CH530

  • @dadykr9645
    @dadykr9645 2 ปีที่แล้ว

    Hi,
    Many thanks for this helpfull video
    I want change damage trane sensor X13650726100 Sen02133 .
    please , i use UC800 conntroller, is it necessary that i bind the new sensor after i replaced the old damage one?

    • @Junkremoval-hvac
      @Junkremoval-hvac  2 ปีที่แล้ว

      Yes you have to bind in the sensor. Thanks for watching.

    • @dadykr9645
      @dadykr9645 2 ปีที่แล้ว

      @@Junkremoval-hvac , please what i need to bind it?

    • @jevonhoward
      @jevonhoward 2 ปีที่แล้ว

      Tracer TU software for a UC800

  • @onesimpleman1
    @onesimpleman1 ปีที่แล้ว +1

    Where can I get software to bind sensors ?

    • @Junkremoval-hvac
      @Junkremoval-hvac  ปีที่แล้ว

      www.trane.com/commercial/north-america/us/en/products-systems/building-management---automation/chiller-controllers.html

  • @onesimpleman1
    @onesimpleman1 2 ปีที่แล้ว +1

    Where can I get tech view software ?

    • @Junkremoval-hvac
      @Junkremoval-hvac  2 ปีที่แล้ว

      Go to trane.com or type in tech view software to google and it will pop up. Download it from there or email it to your self then download it to your computer later on. Let me know if it works.

  • @edwardcrane7520
    @edwardcrane7520 3 ปีที่แล้ว

    Hey you might want to teach them how to unbind first

    • @Junkremoval-hvac
      @Junkremoval-hvac  3 ปีที่แล้ว

      Every time I have found 1 that has failed it’s already unbound. The system is already not seeing or reading it.

  • @paulooliquino9461
    @paulooliquino9461 3 ปีที่แล้ว +2

    sir where I can download software? techview

    • @Junkremoval-hvac
      @Junkremoval-hvac  3 ปีที่แล้ว +2

      Google trane TechView it’s the second icon down then have it send to your email then download from your email. I will do a video on it here soon. No problem. When you google it, it will say trane QC click that then it will take you to the download page.

    • @paulooliquino9461
      @paulooliquino9461 3 ปีที่แล้ว

      @@Junkremoval-hvac the trane page was not found... just wait for your video how to download software....

    • @paulooliquino9461
      @paulooliquino9461 3 ปีที่แล้ว

      @@Junkremoval-hvac techview software will work also in cvhf1300? or for ch530 only??

    • @julianass7354
      @julianass7354 3 ปีที่แล้ว

      @@paulooliquino9461 try with this link, is directly with the Trane page: www.trane.com/commercial/latin-america/cl/es/controls/HVAC-equipment-controls/trane-lontalk-controllers/TechView.html
      good luck!

    • @julianass7354
      @julianass7354 3 ปีที่แล้ว

      @@paulooliquino9461 trane techview y only for CH530, newer centrifugal chillers are with another control system, techview is not supported.