LINE TO NEUTRAL 2 WIRE SYSTEM

แชร์
ฝัง
  • เผยแพร่เมื่อ 16 ธ.ค. 2024

ความคิดเห็น • 51

  • @pinoy_electrician
    @pinoy_electrician 3 ปีที่แล้ว +3

    Sa lahat ng napanood ko ito lng tlga ang tama at sumusunod sa PEC. Good job sir. Yong iba kasi vlog puro kamoteng electrician. Kadalasan walang bonding sa nema. Ito tlga ang tama.

  • @TrackdayDaddyPH
    @TrackdayDaddyPH ปีที่แล้ว

    galing.. very well explained... needed this to understand neutral wiring for smart lighting systems

  • @markjaysonbalundo
    @markjaysonbalundo 2 ปีที่แล้ว

    Thank you sir alam kona..kac nalinawan po ako sa paliwanag nyo po..❤️❤️❤️

  • @mariejoycacay4840
    @mariejoycacay4840 3 ปีที่แล้ว

    Wow thank you po sa dagdag kaalaman master Joe

  • @buddy6819
    @buddy6819 3 ปีที่แล้ว

    Sobrang thanks Idol, God bless and more power to you & your family

  • @gerrybenavides63
    @gerrybenavides63 2 ปีที่แล้ว

    Very nice explanation sir...

  • @johncarlbalibado2953
    @johncarlbalibado2953 2 ปีที่แล้ว

    Karamihan dito saamin sa probinsya Yan ang nkasanayan dinadaanan ung neutral sa breaker.

    • @masterjoeelectrical
      @masterjoeelectrical  2 ปีที่แล้ว

      Master delikado po yan

    • @johncarlbalibado2953
      @johncarlbalibado2953 2 ปีที่แล้ว

      Master paano po ang koneksyon ng mts since dto saamin line 2 neutral Diba po sbi nio hindi dpt dumaan ang neutral sa circuit breaker khit anung search ko ng mts dto sa TH-cam same PA din ung koneksyon ng mts.

    • @johncarlbalibado2953
      @johncarlbalibado2953 2 ปีที่แล้ว

      @@masterjoeelectrical paano po ung koneksyon ng manual transfer switch sa line 2 neutral kc di ba sbi nio wag idadaan ung neutral sa circuit breaker at kailangan wla pong putol paano po ung koneksyon nun sa line 2 neutral.

  • @buddy6819
    @buddy6819 3 ปีที่แล้ว +1

    Maraming salamat Idol

  • @roweldelmonte4508
    @roweldelmonte4508 9 หลายเดือนก่อน

    Maraming salamat po

  • @ivanquinterro5274
    @ivanquinterro5274 ปีที่แล้ว

    Ask ko ulit joe kapag gusto mo e check yun isang line 1 sa service entrance ang isang line is 220v at yun Line 2 is zero volt kahit naka bare foot kapa. Wag lang hawakan ang Isang line kasi 220 volt sya.

  • @astuvlog8360
    @astuvlog8360 ปีที่แล้ว

    Dito sa probinsya namin wala naman silang nilalagay na nema 3r. Direkta na cb ng household ang service drop wire na galing sa metro.

  • @electricalworksstudio3558
    @electricalworksstudio3558 3 ปีที่แล้ว

    Nice explanation Sir..

  • @teodybenson2812
    @teodybenson2812 8 หลายเดือนก่อน

    👍❤️❤️

  • @kennedyagbayani6820
    @kennedyagbayani6820 2 ปีที่แล้ว +1

    Master, di ba dapat green ang color ng grounding connection from ground rod to ground bus bar inside service equipment?
    Para consistent yong color coding?

  • @rangerzxcasuga1017
    @rangerzxcasuga1017 ปีที่แล้ว

    Sir bakit po kailangan bonded ung neutral at ground? By the way ganda po ng pagkaka discuss pulido ung detalye ang klaro

  • @ivanquinterro5274
    @ivanquinterro5274 ปีที่แล้ว

    Ask ko lang joe dito po sa cavite ang wire connector ditto ay 2 wire lang ang isang wire L1 220volt at yun L2 is zero volt kahit hawakan mo L2 hindi ka makokoryente.paano na yun gusto mo mag installe ng 110 v?

  • @sipansibabdreddknot5179
    @sipansibabdreddknot5179 7 หลายเดือนก่อน

    need di ba ng grounding rod yung main cb?

  • @CatTV2024
    @CatTV2024 หลายเดือนก่อน

    Magkadikit yung Green at White Wire?

  • @boylerio
    @boylerio 10 หลายเดือนก่อน

    new comment po sir puide ba po gamitin 2 pole breakers sa panel

  • @nielgab2731
    @nielgab2731 ปีที่แล้ว

    sir, ano kung walang service equipment kasi malapit lng naman ang bahay sa service pole ano po yung connection nun at bonding sa ground?

  • @jaybeefernandez3450
    @jaybeefernandez3450 ปีที่แล้ว

    Sir ask klang yung nuetral bas bar b nkadikit mismo sa bakal or insulated sya?

    • @masterjoeelectrical
      @masterjoeelectrical  ปีที่แล้ว +1

      Depende sa sustem kung line to neutral hindi yan nkdikit sa metal parts.kung line to line nkdikit

  • @autocadchicken3491
    @autocadchicken3491 2 ปีที่แล้ว

    ANG DAMI KO PONG NATUTUNAN DITO

  • @paanovlog3296
    @paanovlog3296 ปีที่แล้ว

    Boss tanong lang po ulit dyan sa part ng nema enclosure po yang white wire connected sa busbar papuntang grounding rod and also iyang papasok sa bahay po na ground na green wire connected din dyan sa white wire sa nema?boss diba magkakaroon ng ground or diba makaka kuryente sa tao pag hinawakan ang nema 3r kasi naka bonding sila naka kabiy sa case ng nema 3r ang neutral po

    • @masterjoeelectrical
      @masterjoeelectrical  ปีที่แล้ว

      Sa line to line system wala png current na dumadaloy sa grounding system.maliban kung ang live wire ay aksidenteng dumikit sa metal parts ng panel board.ngunit ito ay split seconds lng dahil automatic nitong e trip ang breaker.but in the absence of grounding system hindi nito ma trip ang circuit breaker kaya nagkakaroon ng fault current sa grounding at lahat ng metal parts thank you and god bless

  • @melreyes8461
    @melreyes8461 2 ปีที่แล้ว

    Master tanong lang po.. pano kung ang ginamit sa installation ay pvc yung conduit, junction box, at utility box at wala rin lagayan ng equipment grounding conductor yung mga device na gagamitin?? Gaya ng set up ng sa mga tesda center na nonmetallic gamit... Required pa ba na maglagay na equpment grounding conductor?? Or may exception poba?

    • @masterjoeelectrical
      @masterjoeelectrical  2 ปีที่แล้ว

      una sa lahat safety ang concern natin sa lahat ng installation kilangan ng grounded type outlet sa ating mga appliances lalo na sa laundry

    • @melreyes8461
      @melreyes8461 2 ปีที่แล้ว

      @@masterjoeelectrical yes po master sa saksakan po maglalagay po talaga ng EGC. Sorry po di ko namention pero ang tinutukoy ko po jan is yung sa lgihting circuit po master.. kasi yung normal na 4x4 na receptacle gamit wala po yun metal tsaka yung switch nya yung walang lagayan ng EGC?yung gamit din po na utility at junction box ay nonmetallic po. Need pa po ba lagyan? Kasi sabi ng ibang nagtotoro dito sa YT if wala naman daw exposed metal parts na ginamit sa installation no need na daw maglagay EGC po master .lgihting circuit po tinutukoy ko master..

    • @masterjoeelectrical
      @masterjoeelectrical  2 ปีที่แล้ว

      @@melreyes8461 tama po yon

  • @astuvlog8360
    @astuvlog8360 ปีที่แล้ว

    Sir ibig sabihin mali po na idaan ang neutral sa cb. Ang nema 3r enclosure puro 2pole wala pa ako nakita na singlepole na.

  • @iancarido2053
    @iancarido2053 3 ปีที่แล้ว

    Sir pwede ba na mag bukod nalang ng grounding wire .yung neutral di na sya bababa pa sa lupa .yung wire ng kulay green nalang .galing sa ground rod papunta sa panel

    • @masterjoeelectrical
      @masterjoeelectrical  3 ปีที่แล้ว

      pwede naman kailangan lang ng common bonding ang green for egc at ang white for neutral sa poste nema 3r,now ko lng nabasa na covid ako

  • @arielbalalilhe6500
    @arielbalalilhe6500 2 ปีที่แล้ว

    Gudpm master Joe pag line to neutral na connection at wala pong nema 3r saan ilagay ang bonding sa neutral at gound...

    • @masterjoeelectrical
      @masterjoeelectrical  2 ปีที่แล้ว +1

      Pwede doon sa ground screw ng meter base thanks for subscribing God bless

  • @allenlorezco8291
    @allenlorezco8291 2 ปีที่แล้ว

    Sir joe bkit po bwal na bawal sa pec na dumaan sa breaker ung Neutral at ground

    • @masterjoeelectrical
      @masterjoeelectrical  2 ปีที่แล้ว

      Dahil ang neurral conductor ay nagsisilbing return path ng current pabalik sa source.kapag kinabit mo ito sa circuit breaker at nag open kapag nagkaron ng fault current sa neutral conductor hindi magti trip ang line circuit breaker instead dadaan ito sa egc at delikado ito.lahat ng metal parts system ay agiging live.kapag nakahawak kayo sa metal parts ng appliances nyo makukuryente kayo

    • @masterjoeelectrical
      @masterjoeelectrical  2 ปีที่แล้ว

      Thanks for subscribing god bless

    • @dms3813
      @dms3813 2 ปีที่แล้ว

      @@masterjoeelectrical Permitted yan as long as may Trip Link (common trip link) yung 2 pole CB mo
      PEC 2 . 40 . 2 . 3 Grounded Conductor . No overcurrent device shall be connected in series with any conductor that is intentionally grounded unless one of the following two conditions is met ( 1 ( ) 2 , ) , :
      1. The overcurrent device opens all conductors of the circuit including the grounded conductor and is designed so that no pole can operate independently ,
      2. Where required by 4 . 30 . 3 . 6 or 4 . 30 . 3 . 7 . for motor overload protection .

    • @alainocfemia3867
      @alainocfemia3867 2 ปีที่แล้ว

      Useless po pla ung ung breaker n 2 pole eh karamihan dto s residential may optional n 1 pole at 2 pole pagdting s panel board pwde po cguro s nema 3r hindi dumaan pero ung pagdting s panel board pwde ipadaan

    • @alainocfemia3867
      @alainocfemia3867 2 ปีที่แล้ว

      S wiribg diagram n standard pwde nmn pagdting s panel board

  • @maninglabadan7820
    @maninglabadan7820 2 ปีที่แล้ว

    master joe anong ba yong 3R distribution? hindi ko na intindihan ibig ba sabihin dalawang panel board lahat sa 3R ngbonding ang nuetral at ground equiptment terminal sa isang panel board hiwalay tama ba?

    • @masterjoeelectrical
      @masterjoeelectrical  2 ปีที่แล้ว

      Opp master sa nema 3r sa poste lang dapat magbomd ang white galing sa meralco white papunta sa ground at sa panel sa loob bahay at green thanks for subscribing God bless

  • @kido41573
    @kido41573 2 ปีที่แล้ว

    Master Joe new subscriber po! anu po minimum size ng wire na EGC galing sa Nema3r papunta sa panel board? salamat

  • @danielvillanueva771
    @danielvillanueva771 2 ปีที่แล้ว

    Saan bawal

  • @geroneduque2816
    @geroneduque2816 2 ปีที่แล้ว

    di nman kailangan lahat spo, at bakit pa sila gumawa ng 2 pole ckt breakers kung di rin lng pala ito gagamitin. paano ma isolate completely ang load side kung single pole lng gagamitin although acceptable din nman iyan. matagal na po akong electrician, dalawang two storey schools na nawiringan ko, 2 six storey building at marami na rin mga bahay na malalaki ang nagawa ko. ang mentor ko ay electrical engr at ako nman ay malapit na rin maging eim instructor. pero minsan, di ako gumamit ng single pole kasi di iyan ang itinuro sa akin.