We are using same, but there are two 2 problems we facing 1. Continue beep sound while running with either light or battery 2. In display both light & battery symbols are displaying alternatively When we have light also How to clear these two problems
Will you turn off the input supply UPS will be go to the battery then turn on input supply (make sure without output load) the UPS will come to normal mode
BR Code is meaning Battery Replace. So you should be check all batteries. If there any battery problem found. Replace the damaged battery then error code will be disappearing
Sir I am Nihar ranjan Pradhan from Odisha I am a technician I am facing a problem with Emerson gxt-mt-cx 1kva model problem is in display showing 230v but when I connect load it showing error code 3 plz help me
What is The reason for occasional battery faults?
yes it works well in a healthy environment
Sir when in battery mode. It continues beeping even after muting everytime. How to mute parmanatly?
what was showing fault code in display in continuous beep
@@rakeshmuthu9809 no error code sir. When main power is out. It beeps every 4 seconds indicating running on battery mode. I just want to off beeping.
@@rakeshmuthu9809 is it possible to off beep parmanatly on battery mode?
@@leolearning3048 no
@@rakeshmuthu9809 sir. I get t solution thanks
Hi, what we can do for waiting (WT) fault code? Ups is continuously beeping
Which model?
@@rakeshmuthu9809 same model
@@darksoul2734 Which model SB or LB? If is the SB model. Can you change front display board
We are using same, but there are two 2 problems we facing
1. Continue beep sound while running with either light or battery
2. In display both light & battery symbols are displaying alternatively When we have light also
How to clear these two problems
Which fault code?
@@rakeshmuthu9809 WT & CH
CH is Charger Board Complaint
WT is waiting. Replace the display board or replace the temperature sensor
Bhai ye charge kese hota h maine uske ek raat ON/OFF dono mod p charge kara magr bttry 1% nhi badhi orr charging show hota h
Sir I connected 6 new 12v 42ah batterys but in ups it giving signel like battery are not connected
Will you turn off the input supply UPS will be go to the battery then turn on input supply (make sure without output load) the UPS will come to normal mode
I found a faulty capacitor under the control board that started with 16jk, I changed it to a faulty
Capacitor 16jk?
take photographs and share
ups not online continue beep how to fix
Which is fault code showing in ups display
hello, what is fault 11 fault, how do we fix
ferit topaloğlu
fault 11 is Inverter soft start failure
Restart the ups, problem come again replace the Inverter Board
Is this stores fault alarms
Beeping sound ko kaise thik kare.bahut aawaj aa raha hai
Sent in English
@@rakeshmuthu9809 always beeping.
@@Heat-l7v can you see fault code in display
Sir is ups me bettry inbild ati he isme kitna time. Backup milta he
Ye iverter kitne watt ka hai??
This is 3kVA UPS
Maximum capacity is 2400 watts
Are Bhai log custemar care ka n. Jarurat hai jisme phone karke doket lete hai jharkkhand jamsedpur
Rupa kumari comment in English plz
Break trip in charging starts
Can you check the charger Board
Sir mera ups bip awaz continue Kar raha h
any code in display
code is right side top
which code showing in right side top
Sir mere ups m battery show nh kr rahi h m two battery lagai h connection bata dijiye
@@faisalahmed4698 which model ups ?
@@faisalahmed4698 do you mean 600va ups ?
2kv emarson ups falt no 1 dctodc card falty hai kya
3kw ups iam using
HOW TO FIX bR Error Please Help
BR Code is meaning Battery Replace. So you should be check all batteries. If there any battery problem found. Replace the damaged battery then error code will be disappearing
Sir alarm 13 show kar raha hai.
Inverter voltage low
@@rakeshmuthu9809 sir isko kaise rectify kare ?
Manual bhejo
106K 350VAC ( CBB2İB MODEL) CAPACİTOR BLACK
ferit topaloğlu now ups is working?
bhai mere ups main fault 11 aa raha hai
fault 11 is Inverter soft start failure
Restart the ups, problem come again replace the Inverter Board
Check the IGBT and Capacitor Inverter side
Connection kaise kare
Kto kv eta
Sir I am Nihar ranjan Pradhan from Odisha I am a technician I am facing a problem with Emerson gxt-mt-cx 1kva model problem is in display showing 230v but when I connect load it showing error code 3 plz help me
Can you check in battery mode on?
CH ha rha h व टी टी की आवाज आज रही ह
Charger Board Complaint, check the charger fuse, bridge rectifier
Nc problem show kar rha h
NC means Battery Not Connected. Please ensure battery connections
Sir for my ups also showing NC on display i connected 12v 42ah battry in series i checked with Multimeter batterys are good but displaying NC
Please sir email send me