Lift floor pe wait karti hai us time pe ML1 Or ML2 ka signal off hota hai to ye error ata hai.. 1. Ek bar ML1 & ML2 sensor check kariye floor level pe dono continue on hone chahiye 2. Travelling cable FX cube to LCB card ka connection proper hona chahiye for ML1 & ML2 wire ka 3. Ek bar 24 V ka supply FX cube card me check kijye agar 24 se kam hai to use increase kijye SMPS se
Bhai UCM ka jumper Dalo … unintended car movement phir sahi Jo jayega
Arkel ka manual & drawing follow karo
Lift floor pe wait karti hai us time pe ML1 Or ML2 ka signal off hota hai to ye error ata hai..
1. Ek bar ML1 & ML2 sensor check kariye floor level pe dono continue on hone chahiye
2. Travelling cable FX cube to LCB card ka connection proper hona chahiye for ML1 & ML2 wire ka
3. Ek bar 24 V ka supply FX cube card me check kijye agar 24 se kam hai to use increase kijye SMPS se
ye to hume pata hai par aisa hota kya hai ML1 or ML2 ka signal off kyo ho jaata hai
Arkel: Kone same controller
दिन में एक बार ऐसा प्रॉब्लम होता है
Contact number sir please
description me number hai
सर मेरे भी यही प्रॉब्लम हो रहा है चौथा फ्लोर से 4 इंच ऊपर आ गई है
thik hui problem ya nahi