Trane RTAC Leak Repair + Oil Filter Part 1

แชร์
ฝัง
  • เผยแพร่เมื่อ 28 ก.ย. 2024
  • What could have been a pretty quick fix turned into a lengthier ordeal when isolation valves on a Trane RTAC chiller didn't hold. Leak Repair + oil filter change on screw compressor. Like, comment, and subscribe for future uploads. Will post follow up video when job is complete.

ความคิดเห็น • 39

  • @twaymangaming683
    @twaymangaming683 2 ปีที่แล้ว +7

    This guy has been running hvac for over a decade definitely a guy to watch

    • @dfwhvac
      @dfwhvac  2 ปีที่แล้ว

      Thanks bud , back at you. Sick gaming channel

    • @ChingusTheOneAndOnly
      @ChingusTheOneAndOnly ปีที่แล้ว +1

      I’m watching, Great stuff on here , Thank you , This channel should take off soon

    • @AGON17
      @AGON17 8 หลายเดือนก่อน +1

      I don't know how all these large commercial TH-cam accounts went under my radar til I started searching for CGAM and RTAA videos

  • @joshstevens9826
    @joshstevens9826 ปีที่แล้ว +2

    Coat the entire gasket in oil , nylog, or what i use vacuum grease. Will be easier to get the gasket off next time.

  • @jasonjohnsonHVAC
    @jasonjohnsonHVAC 10 หลายเดือนก่อน

    Did you send the oil in for analysis by any chance

    • @lammaking333
      @lammaking333 10 หลายเดือนก่อน +1

      No sir we did not . But we came back a month or two after this call for all the chillers on this school district and submitted oil analysis as part of the annual pm

    • @jasonjohnsonHVAC
      @jasonjohnsonHVAC 10 หลายเดือนก่อน +2

      @lammaking333 nicely done...oil analysis is a big key to spot a potential major issue

  • @diegoandrade5953
    @diegoandrade5953 ปีที่แล้ว +1

    Hello, about the compressor low oil flow failure. my chiller has 2 compressors on the circuit and one of them has a low oil flow alarm. the oil level is ok. what could it be in this case?

    • @dfwhvac
      @dfwhvac  ปีที่แล้ว

      Depends on the make and model
      Of the chiller and it’s components. But it could be a dirty / clogged oil filter or strainer or oil pump not operating properly if you can visibly see oil in a sight-glass

    • @joshstevens9826
      @joshstevens9826 ปีที่แล้ว

      Dirty co dessert coils can give you an oil alarm. Cant remember the numbers, butnif the oil temp is close enough to SAT discharge temp it will alarm on oil flow. Usually tranr uses the top couple rows of the condenser for oil cooling. So dirty coils will give you elevated oil temps

    • @jevonhoward
      @jevonhoward ปีที่แล้ว

      If its a RTAC, more than likely the oil filter or check valve that sits in front of the filter.The IOM has the formula to calculate the oil flow ratio.If ratio is too high you will get that alarm.Also make sure transducers are reading properly as the computer is using transducer pressures to calculate the ratio.If high ratio is confirmed, I would replace both the check valve and the oil filter since both involve pumping down and opening the system.2" deep socket needed to replace that check valve.

  • @fernandocanales9002
    @fernandocanales9002 หลายเดือนก่อน +1

    "...bleeding out the remaining fumes of the refrigerant..." Is that normal? On large chillers those fumes could mean a lot of pounds of refrigerant.

    • @lammaking333
      @lammaking333 หลายเดือนก่อน +1

      Do you often work on large chillers? This is a completely normal de minimus release. When pressures on both sides ( low and high ) are under 8 psi or even lower , there’s no way to fully recover remaining fumes of vapor left - even if you bring your gauges to zero out - disconnect your hoses and there will still be vapor in the system. Now a days newer recovery machines just as the new field piece will even cut themselves off at around 2-4 psi. Totally normal to vent off vapor at that low of remaining standing pressure - and now , it’s not “ a lot of pounds of refrigerant “ - I’m the YT creator for this video responding on my personal page . Hope this comment helps - thanks for watching. When recovering 100+ pounds of refrigerant , you are not going to be able to suck such a large circuit down into vacuum through a recovery process

    • @fernandocanales9002
      @fernandocanales9002 หลายเดือนก่อน

      @@lammaking333 Thanks for answering the question. I didn't know. Largest chiller I have worked on was an RTAC1554. I have worked on York and Carriers scrolls of similar size or smaller. I will look into recovery practices of larger chillers. And yes, your comment helps.

  • @kcomfortsystemshvac7060
    @kcomfortsystemshvac7060 16 วันที่ผ่านมา

    I just enjoyed this video,,,,,I what lean something 😊

  • @markcotter2355
    @markcotter2355 2 ปีที่แล้ว +4

    good job from fellow DFW tech

    • @dfwhvac
      @dfwhvac  2 ปีที่แล้ว

      Thanks watching ! DFW techs are bad ass 👍🏼

  • @HeavyDuty1337z
    @HeavyDuty1337z 9 หลายเดือนก่อน +1

    If that was a semi I’d say oil looks like 10+ years old/or dirty system/or running hot.
    Pre normal for a screw chiller tho considering compression ratios, you’ll get that darker tint on the POE pre quick from the elevated DLT

  • @JM-wk2tz
    @JM-wk2tz ปีที่แล้ว +2

    Great video I’ve never worked on chillers, always been curious as to their operation. I’ve worked mostly on supermarket refrigeration and for the most part I was able to follow along. We have oil filters and the same kind of drier cores. What would you recommend to learn more about chillers?

    • @dfwhvac
      @dfwhvac  ปีที่แล้ว +2

      Read Manufacturer IOM manuals. They are usually much more detailed and in depth as far as each operation of the system when compared to regular DX cooling units. There’s also a great channel called HVAC TIME . He works on chillers a lot and is very knowledgeable

    • @JM-wk2tz
      @JM-wk2tz ปีที่แล้ว

      @@dfwhvac great advice thanks !

    • @jevonhoward
      @jevonhoward ปีที่แล้ว +1

      Trane has a training class specific to the RTAC chiller in LaCrosse,Wi.They spend 3 1/2 days covering everything front to back if your Company is willing to pay for it.

  • @niggadonthatethis18
    @niggadonthatethis18 2 ปีที่แล้ว +3

    Great walkthrough! Great information!

    • @dfwhvac
      @dfwhvac  2 ปีที่แล้ว

      Thanks my guy ✅

  • @TheMaintenanceNetwork-DallasTX
    @TheMaintenanceNetwork-DallasTX 2 หลายเดือนก่อน

    Keep doing your thing!

  • @fkdeazevedo
    @fkdeazevedo ปีที่แล้ว

    Is that where you add too?

  • @ChingusTheOneAndOnly
    @ChingusTheOneAndOnly ปีที่แล้ว +2

    Great content , Thanks for posting

    • @dfwhvac
      @dfwhvac  ปีที่แล้ว

      Thanks for watching . Been busy on a contract that doesn’t allow filming on site , but will try to get some more content out soon.

  • @kennethlobo4420
    @kennethlobo4420 9 หลายเดือนก่อน +1

    Thanks for thus great tip to keep the chilled water pump running when on recovery mode,I know that this has to be done when breaking a vaccum.

    • @dfwhvac
      @dfwhvac  7 หลายเดือนก่อน

      Yessir , recovery and charging should only been done with verified water flow on chilled water systems to prevent potential freezing issues in the tubes or heat exchanger

  • @kennethlobo4420
    @kennethlobo4420 9 หลายเดือนก่อน +1

    Thanks A lot enjoyed watching this video.found ur cannel accidently

    • @dfwhvac
      @dfwhvac  7 หลายเดือนก่อน

      Thanks for watching

  • @FrankD-p5s
    @FrankD-p5s ปีที่แล้ว +1

    Great video man! Thanks now I feel alone more confident cleaning the oil filter.

    • @dfwhvac
      @dfwhvac  ปีที่แล้ว

      Great to hear man and glad I can help ! They’re intimidating at first but if you have someone show you how to do it it’s not as hard as you’d think ! That’s why I make these videos

  • @ajajomedia1220
    @ajajomedia1220 ปีที่แล้ว +1

    Is that chiller also

    • @dfwhvac
      @dfwhvac  ปีที่แล้ว

      Yes sir , it is an air cooled chiller with screw compressors . R134A refrigerant

  • @bobparrott8130
    @bobparrott8130 11 หลายเดือนก่อน

    Nice work 👍