Assalamualkum. Bhai kya hal ha MashAllah.bhot achi malomati videos hoti hain bhai aap ke. fire pump controller or main electric pump ka 24×7 k sath conection ka tariqa btyan relys kasy lagyn gain
Thank you very much sir u are giving amazing information for practical experience. Please continue too make a video and please make a one detailed video to BMS System 🙏🙏
Facility m zyda tar fire technician badi site k liye hi hoty hai jaha par fault ya maintenance requirements hota hai.. Or BMS system handle karna hota hai...
Hi Sir, I am your big fan, want to ask something raleted to fire Panel. Actually our fire Panel is weeping continuously due to fire in zone but we have checked all the smoke detector which is installed the same zone but didn't found any smoke detector activated. So pls suggest us what should to do.
Type change matlab apka jo detector ha wo baki detector jaisa yani model number same hona chahiye. Ya fir aap panel ki programming m jaky setting m device type change kar k dekhiye issue solve hojayega
Sir can you tell me what is IDP protocol how this is works in addressable fire alarm system. i've searched a lot but did not find any helping meterial. i want know how fire alarm controller know about connected devices which protocols use to identify device, how to assign addressing of devices and my main question is how these devices communicate with controller just using 2 wire specially in triga honeywell fire alarm cotroller.
In my Conventional Panel showing hooter fault, I removed the hooter connection and add resister but hooter fault problem not solved, Do you have any suggestions ?
Sir common fault kya hota hai kisi panel mein mahine din mein fault aata hai reset karne per theek ho jata hai FIR 20 25 dinon mein a jata hai. Please reply sir
Common fault bohot type ka ho sakta hai .. detector faulty, Detector missing, cable open... depends karta hai....aysa fault sirf conventional panel m hi show hota hai... because addressable m exact fault show hota h
I think u r the first to make such quality videos on fire alarm.
Assalamoalakum aap bahut a6e se samjahte hai samjhane ka tareeqa bahut a6a hai
Thank you brother
U r really good,as a good teacher.I like this,i am also F.A.tecnician.
Thanks for your comments 😊 pls share my videos in your company group
Really I have seen so many videos related to FAS. But Ur way of explanation outstanding 👍 keep it continues 🙂
Thanks for your comments, please share my videos in your company group
ماشاء اللہ بہت خوب
Thanks
PC या laptop के through कैसे configure, device add etc करते हैं, एक वीडियो बना दीजिए, बाकी सब वीडियो आपको बहुत informative होता है, thanks sir
Thanks for your comment 😊
Pls share my videos in your company group
Apna no.do
Your explanation is very good
Thanks a lot 😊
Very nice knowledge. Program Corrupted kaise thik kiya jaaye sir ... please explain
Need to do Re-Commissioning
Thanks for Very good video
Kindly explain about all the components which is used inside the Addressable FACP.
Is it devices....??? Or components...??
Assalamualkum. Bhai kya hal ha MashAllah.bhot achi malomati videos hoti hain bhai aap ke. fire pump controller or main electric pump ka 24×7 k sath conection ka tariqa btyan relys kasy lagyn gain
Try karta ho bhai.
Very nice sir
Thanks and welcome
ماشاءاللہ
Thanks
Pakistan iam saudya nice bye@@Ansari29
Thank you very much sir u are giving amazing information for practical experience. Please continue too make a video and please make a one detailed video to BMS System 🙏🙏
Thanks Shubham for your comment 😊
Pls share my videos in your company group
Yes sir definitely
Thanks
You would have so many more views and subscribers if you had an English version or at least subtitles.
Overall, very informational and great video.
Thanks for your comments. I will try to add subtitle in my video
Yeah sure please make a video how to give address to device in panel through laptop
I will try
Thank you so much sir nice work
Most welcome. Pls share my videos in your company group
Very good video, awesome bro. Can you please make video aur guide me for troubleshooting of Synchro AS Kentec addressable fire alarm Panel, please.
Yes Sure, I will try
Very good
Sir programing ka video bnaiye you all video good
Thank you so much
Thank you sir
Mera 1 questions hai.
Fire TX fault kese normal kare
Which panel.. Tx means communication as per my knowledge, pls let me know panel make model
@@Ansari29
Honey well sir
Sir video banaiye.
How to solve battery missing faults.thnks god bless
Check battery terminal or else replace thermistor.. Or placed thermistor between the 2 battery...
Asalamualikum mera sawal ye hy repair krny ki kia mazdori lain ya theka karain
Your video is more helpfull if u atleast english subtitles...tnx more video to come...
Thanks for your comment 😊
Sir agni convancnal panel ki bhi fault aur troubleshooting ka video banao pls
Yes sure
Good job sir thank you
Most welcome
Pls share my videos in your company group
thank you so much sir veary healf ul video sir
sir seand you what shop
Thanks for your wishes, pls share my videos in your company groups
Sir 🙏 namaste. EST3 fire panel me bhi trable shooting ki yahi prosess hai
Good vedio bhai
Thanks for your comment 😊
Good video sir
Thanks
Super man
Thanks for your comments 🙂
Pls share my videos in your company group
Thank you so much sir very helpful video 👌
Thanks meraj😊
Please make a Video for Beam Detector Alignment.
Open circuit ka ek drawings Kar ke vedio Bana ke explains karo 👌😍
Sir GST penal and smoke pr video banayi
Sir asking any idea in honeywell FACP corrupt trouble thanks and have a good day..
Check programming
Pls make video on how to add device in FAS panel
Thnks❤
Nice mes 👍
Thanks for your comment 😊
Bai facility management me fire alarm technician job easy hota hai kya
Facility m zyda tar fire technician badi site k liye hi hoty hai jaha par fault ya maintenance requirements hota hai.. Or BMS system handle karna hota hai...
Awaiting your new vedio
Thanks for your comment 😊
How many smoke devices we can connect in one zone circuit.
Waiting for your reply and one more thing I have a question about co2 system ,may I know what is isolation of co2 system .please reply
Hi Sir,
I am your big fan, want to ask something raleted to fire Panel.
Actually our fire Panel is weeping continuously due to fire in zone but we have checked all the smoke detector which is installed the same zone but didn't found any smoke detector activated.
So pls suggest us what should to do.
Sorry for replying in delay. May I know the panel make....???
Sir ji notifier pe ek video bana dijiye.How to add device mannualy or with verifier tool.
Yes Sure, ye topic m ny list m add kiya hai.
Thanks for your comment 😊
Pls share my videos in your company group
Sir simplex 4100 es panal me total detectors kitne lage hai kaise chk kare panal se pls bataiga zaroor
Hooters folt ki upper video bno sir
Thanks sir
Most welcome, pls share my video in your company group
Awesome
Thanks for your comments
Sir 1loop me kitne moudle daal sakte
Menvier facp me gst ka device add hota haii kya.
Sir can you make a video on NAC and earth fault solution.
Please check my Ground fault video u can also understand
Dear ansari29 ji please make a video morley panel dubble address fault how to find and delete if possible
السلام علیکم
Bhai short circuit pe banao video seimmens FACS ki
Yes Sure
Your Query solved in Video | Pls Check
th-cam.com/video/VKImg1jDvm0/w-d-xo.html
Sir normally how much voltage does flow in FAS circuit
24VDC
Ok sir
Good
please make video on software programming of fas system
Ok i will try
@@Ansari29 please sir...I really in need of software programming part of fire alarm system....please 🙏
Base detector humara part no. 9793 laga hai..kya part no. 9792 is ki jaga lga skte hai
Make..???
Response indicator ka agar led Tut gya ho to kya device missing dikhayega
No
Sir, gst company ka panel supervisor fault kiya hai
May be monitor module activate hua hoga...
Addressable Ravel ka Vedio banaie
Ok, I will try
Smoke sancer ko kasy find kren or kasy pata chaly ga k kon sa detacter folty ha
Ansari Bhai device Lagane ke bad power chala jaaye device nikaalne ke bad power hai kya problem
Device faulty, check loop
Sir NCM common failure aur wrong component trouble kaise solve hoga ye btayo
Which panel....???
@@Ansari29 Honeywell 3000
Sir, GST fire alram par video banaye please
Ok, I will try.
Sir sieman facp penal mai ground foult kaise slove kare usape ek video banana sir
Line fault and open circuit are same? Same way find ground fault
Which panel...???
@@Ansari29 simplex
Bhaijaan software se device ko addresing krke bataye plzzzzz
Try karuga uspy bhi video banany ki
What is the solution for Battery Wiring Fault Error for Morley IAS Fire Panel?
Already uploaded pls check my playlist
Fire telephone jack ke bare me batao sir ji
Tq sie ji 👍👍
please tell me about negative cable break/short circuit
It's same as open circuit fault troubleshooting.
Low Threshold kya issue hai?
ClassA cable and class B Video banan aur kon sa cable achahai
Please check my Fire Alarm course
Bhai repairing ka rate kia hy 900 fire detectors hain four panels hain .
MashaAllah
Sir pannel ke all system installation ke liye koun sa course kare fire me plz bataye sir
Bhai koi course nhi hota ha flide main jaoge sab pata chall jayega
Sir
Other fault types change and corrupt single
Type change matlab apka jo detector ha wo baki detector jaisa yani model number same hona chahiye. Ya fir aap panel ki programming m jaky setting m device type change kar k dekhiye issue solve hojayega
Sir can you tell me what is IDP protocol how this is works in addressable fire alarm system. i've searched a lot but did not find any helping meterial. i want know how fire alarm controller know about connected devices which protocols use to identify device, how to assign addressing of devices and my main question is how these devices communicate with controller just using 2 wire specially in triga honeywell fire alarm cotroller.
Hi...How to rectify DEVICE TYPE CHANGED trouble in fire panel??
Aapka doubt ka video upload hogaya h pls check, pls subscribe & press the bell icon for notifications
Ek Loop me kitna ditector hona chahiye iske bare me bhi bataiye
In morley IAS compensation fault is appearing. Not resolved even after system reset. Any hint on that?
Try to replace the detector
Please tell about system faults
Which fault...??
please explain short circuit fault in adressable system and short /oepn loop fault
Yes Sure, pls share my videos in your company group
In my Conventional Panel showing hooter fault, I removed the hooter connection and add resister but hooter fault problem not solved, Do you have any suggestions ?
Which make panel...??
Assalamu Alaikum kya bata sakte hain fike panel mein control module ka low voltage kyon bata raha hai
Control module k output p Voltage nhi hota hai.... Wo potential free yani NO NC contact hota hai
Input site m loop ka cable connect hota hai
Sir simplicity en54-2 addressable panel ha us ma weak signal orr Analoge fault aa rha ha kia problem ho sakti ha ?
May be detector faulty hoga
Nhi sir poray system ma aisa he bata rha ha yani sab detector ma aisa he ha weak signal
Please explain the "Trouble causing input fault"
Kon sa panel hai ...?
Manual call points If termination + - change termination mistake after device any problems??
Yes.. RI m + & - mai proper connection karna hai... Nhi toh RI activate nhi hoga....
How many homes teke for the one loop Curcit
Homes.... Or ohm....? Not understanding ur doubts
Sir or ak questions sir fire panel ma Dectction connection ma sir control module use hota na sir monitor module use hota hai
Dono bhi module integration k liye use hota hai.... Mera integration ka video dhekiye aapka doubt clear hojayega
Sir loop fault k bare me video bnayen
Loop fault m kya show kar raha h panel m
bhai supply ic kaha milegi ravel company ka h ic h L200C mil nahi rahi regulator supply ic h
No idea brother, but you can contact Ravel distributer.. Or OEM
Sir sieman Kai bare mai khucha batao na muze ek troubles shoot karrna hai custom massage not programmed troubles hai kaise slove kare
Sir module ko kse jaane ki wo faulty agr multimeter check kre to power thik h lekin panel me not responding show karw how to troubleshoot
Sir autronica k panel py wrong unit ka fault arha ha 2nd mains power fail arha
Main power fail matlab - Check input supply or panel SMPS card ... wrong unit matlab - Aapny jo device connect kiya hai wo mismatch hai ....
Sir NFPA k hisab se fire alarm panel smoke detector heat detector beem detector se mutaliq tafseeli video bnayen
Hi, pls check my this video
th-cam.com/video/grKPupj1tEw/w-d-xo.html
Meri sub videos dhekhiye apka concept clear hojayega.or pls video ko share zaroor kary apny company k group m
Thank you
So wish that you have English version. I don’t understood your language. 😊
I will try to add subtitles
Sir common fault kya hota hai kisi panel mein mahine din mein fault aata hai reset karne per theek ho jata hai FIR 20 25 dinon mein a jata hai. Please reply sir
Common fault bohot type ka ho sakta hai .. detector faulty, Detector missing, cable open... depends karta hai....aysa fault sirf conventional panel m hi show hota hai... because addressable m exact fault show hota h
Sir, please prepare laptop ke through configure kaise kare
Mai koshish karta hoo uska bhi video banany ki
I am phasing a problem in NSC solution F-1 fire alarm panel thats the touch pad buttons are not working , if you have a solution kindly suggest me.
Pls Contact OEM, they will provide spare parts
Sir simplex fire alarm system ka installation and programming ka video banvo na..
Ok Manish, I will try to make video on it
Thanks for your comment 😊