Repairing Daikin E3 Error

แชร์
ฝัง
  • เผยแพร่เมื่อ 26 ธ.ค. 2024

ความคิดเห็น •

  • @eastcoast186
    @eastcoast186 2 ปีที่แล้ว +2

    Hey mate we’re the nitrogen purge to braze and micron gauge for vacuum

  • @johnhenderson4335
    @johnhenderson4335 ปีที่แล้ว +1

    How did u manage to get the last of the gas in? I though the last would go in the suction when on?... I'm trying to learn ac, just incase iv missing something..

    • @johnhenderson4335
      @johnhenderson4335 ปีที่แล้ว +1

      This comment was for previous video mate.. Same HP video /fault

    • @maracservices
      @maracservices  ปีที่แล้ว +2

      So after evacuating the system, I weigh in the refrigerant. In the perfect case, there is enough pressure in the bottle to add all the gas in. If not, then I run the system and add it slowly through the suction line.
      I hope that helps mate.

  • @brocwilliams7186
    @brocwilliams7186 23 วันที่ผ่านมา

    Why did you not put the old gas back in the unit?

  • @vladimirnik7260
    @vladimirnik7260 2 ปีที่แล้ว +1

    Hi, soldering was without nitrogen?

  • @ushant29
    @ushant29 ปีที่แล้ว +1

    Hi Mitch,
    DAIKIN AIR WATER HIGH TEMPERATURE 16K installed in 2019
    I have an error code that remains displayed:
    Unit 0
    E3 12
    160 L32
    006 F5E
    Do you have any information regarding this recurring error code?
    Unit 0 concerns the outer group?
    Best Regards ;)

    • @maracservices
      @maracservices  ปีที่แล้ว

      Sorry mate I don’t really understand what your talking about. Daikin E3 is a high pressure switch. Something is causing the system to have high head pressure OR the pressure switch is faulty.

  • @chocman77
    @chocman77 3 ปีที่แล้ว +1

    Good job man, nice and tight in that condenser lol, keep the videos coming 👏👏

    • @maracservices
      @maracservices  3 ปีที่แล้ว

      Thanks mate. Yeah they’re so tight aye, so much stuff to burn lol.

  • @rdenir
    @rdenir 2 ปีที่แล้ว +1

    Thanks for pointing out just how stupid the HP switch is on the Daikin units,, I have replaced so many and every time I just shake my head in disbelief as to why they designed it that way where it requires a gas removal process..Yet the HP sensor switch can be removed in minutes by screwing off and screwing back on..

    • @maracservices
      @maracservices  2 ปีที่แล้ว +1

      It makes no sense to me either. So stupid!

    • @rdenir
      @rdenir 2 ปีที่แล้ว +1

      @@maracservices what’s even more unbelievable is that this has just happened to me again today on a VRV unit!!

    • @maracservices
      @maracservices  2 ปีที่แล้ว

      @@rdenir oh wow.. I’ve come across this twice now. They definitely fail. Once again, why it is soldered in is beyond me..

  • @sotirigouna8195
    @sotirigouna8195 3 ปีที่แล้ว +1

    Hey bud
    I have the same error coming up but mine stays on for about 40mins and the top fan doesn’t kick in either

    • @maracservices
      @maracservices  3 ปีที่แล้ว

      It’s a high pressure switch so unfortunately the only way to diagnose this is to reset the system, and run it with some gauges on the unit. If the pressure is indeed getting to high then it could be caused by the top fan not running (if on cooling mode). However if it is coming up with this error when the pressures are fine then I’d put my money on the HPS being faulty.

  • @hamdani5502
    @hamdani5502 2 ปีที่แล้ว +2

    Thanks Mr ....

  • @shamimdhaka4424
    @shamimdhaka4424 2 ปีที่แล้ว +2

    Good video very tanks

  • @deepastephenson6422
    @deepastephenson6422 ปีที่แล้ว

    Nice and great way to understand and find the daily and solve it

  • @santiagoyaguesegura5765
    @santiagoyaguesegura5765 4 หลายเดือนก่อน

    Buen vídeo 👍

  • @hanshvide8935
    @hanshvide8935 หลายเดือนก่อน

    why does not this video explain what daikin system he is talking about?

  • @suldaancooling4207
    @suldaancooling4207 3 ปีที่แล้ว

    Thanks you so much bro👍👍♥️♥️

  • @richardmalewski953
    @richardmalewski953 2 ปีที่แล้ว +1

    No Schrader core on switch? Crazy

    • @maracservices
      @maracservices  2 ปีที่แล้ว

      No Schrader. You have to reclaim all the refrigerant to change it over. Crazy is correct haha.

  • @ILMANHAFIDZ09
    @ILMANHAFIDZ09 3 หลายเดือนก่อน

    tinggal cuci , bikin rusak ac itu namanya

  • @petevelasco6877
    @petevelasco6877 4 หลายเดือนก่อน

    W we

  • @bmiadmin5784
    @bmiadmin5784 ปีที่แล้ว

    The worst brand ever come across. So many faculties and problems!!!