  • How to select cable size? // AC Cable size & Voltage drop calculation. // AC cable design for load.
    Principles of Cable Sizing :-
    current carrying capacity, voltage drop, short circuit.
    Cables are often the last component considered during system design even if in many situations cables are the true system’s lifeline: if a cable fails, the entire system may stop. Cable reliability is therefore extremely important, then a cable system should be engineered to last the life of the system in the installation environment for the required application. Environments in which cable systems are being used are often challenging, as extreme temperatures, chemicals, abrasion, and extensive flexing. These variables have a direct impact on the materials used for cable insulation and jacketing as well as the construction of the cable. Using a systematic approach will help ensure that designer select the best cable for the required application in the installation environment. This lessons will provide students main guidelines for perform this approach.
    Solar
    Safest
    Smarter
    Saur urja
    Biljli Kaise bachaye
    Solar se Bijli Kaise Bachaye
    Benefits of Installing solar
    Profitable solar
    Solar k Fayede
    Solar Lagane k Fayade
    MCB
    MCCB
    ACB
    AJB
    ACDB
    DCDB
    Lighting Arrester
    walkway
    cable Tray
    Solar Panel
    Solar Inverter
    Solar Cable
    AC Cable
    Follow me on -
    Telegram- t.me/+uVOzUWjDk0tiNTBl
    LinkedIn- / raman-kumar-666436141
    Facebook - / solarfacts-37057195372...
    solar structures
    Solar panel mounting structure
    Solar mounting structure
    acdb and dcdb for solar system
    acdb box price
    dcdb box for solar system
    dcdb box price
    long rail solar structure
    mini rail for solar panels
    mini rail solar structure
    solar mounting structures
    solar panel structure
    solar structure
    solar structure types
    types of mounting structures for solar panels
    types of solar mounting structure
    types of solar structure
    mounting structure for solar panels
    mono rail solar structure
    solar acdb box
    solar acdb dcdb box
    solar dcdb box
    solar mini rail
    standing seam solar structure
    tilted solar structure
    acdb box for solar
    dcdb box for solar
    Video link -
    1. How solar zero export works.- lnkd.in/evPgfuj2
    2. What is Enphase microinverter ? // Microinverter & it’s step wise installation explanation. - lnkd.in/e3mr7HjF
    3. Concept of Solar Inverter Overloading //Solar inveter overloading is right or wrong !!!! - lnkd.in/eDNXTc2z
    4. What is Reactive Power ? // Why Industries Power Factory become poor after installing Solar! - lnkd.in/ei8S_d_m
    5. What is CT? What is CT Ratio? How to select CT? - lnkd.in/eCkNRTtZ
    6. How to check Current Transformers? - lnkd.in/eT5gc99e
    7. Why Solar Systems are not Success with Zero Export device. // Precautionary Majors for Zero Export. - • Why Solar Systems are ...
    8. How to design SolarEdge string // How to use SolarEdge string designing tool. - • How to design SolarEdg...
    9. How to install solar panel // What is the right way to install solar panel. - • How to install solar p...
    10. How to calculate string design for solar Inverter? -- lnkd.in/ekujjSpm
    11. How to design stand alone solar system & Battery bank capacity - lnkd.in/exEYzYdD
    12. What is surge protection device? // How to protect our system from surge? - • What is Surge Protecti...
    13. What is Armoured cable? // what is the benefits of Armoured cable?- • What is Armoured cable...
    14. Why Single Core Cable Comes with AL Armoured not with Steel? -- • Why Single Core Cable ...
    15. How To Calculate Neutral Current? 3 Phase Neutral Current Calculation! Unbalance current calculation! - • How To Calculate Neutr...
    16. What is Neutral Floating? // Why voltage increase // what happen if neutral breaks in a transformer. - • Video
    17. Solar Power Plant Shadow Analysis ! // Shadow Calculations for Row Spacing.
    • Solar Power Plant Shad...
    18. What is 1000VDC and 1500VDC solar system.// Advantage and Disadvantage of 1500VDC Solar System - • What is 1000VDC and 15...
    19. What is Netmetering and What is Gross metering. // Netmetering and Gross metering billing method. -- • What is Netmetering an...
    20. What is PID (Potential Induced Degradation) ? Why PID Occurs in Solar Panel ? / How to check PID ? -- • What is PID (Potential...
    21. How to select solar panel on technical basis ? // Best solar panel selection as per project. -- • How to select solar pa...
    22. What Is Solar PERC Technology? // Mono PERC // Poly PERC. // Passivated Emitter and Rear Contact -- • What Is Solar PERC Tec...
    For more information contact us 😊.
    Name - Raman Kumar
    Contact No- 9871073342

ความคิดเห็น • 188

  • @gallwailaydi3976
    @gallwailaydi3976 4 วันที่ผ่านมา

    Excellent information

  • @sourabhsharma9985
    @sourabhsharma9985 2 ปีที่แล้ว +4

    Great vedio sir, I have'nt seen this type of content on this particular topic in which any industry can actually calculate their cable size and will no longer be dependent on assumptions.

  • @khaledshaikh4972
    @khaledshaikh4972 2 ปีที่แล้ว +2

    Helpful videos for Industrial projects
    Thank you

  • @shoaibahmed8947
    @shoaibahmed8947 7 หลายเดือนก่อน

    Superb bro u r awesome keep it up n thank u soo much ❤

  • @shikshasolanki8903
    @shikshasolanki8903 ปีที่แล้ว +5

    Thankyou bhaiya
    I’m a working professional nd I’m really suffering alot in corporate world because no one is ready to tell me

    • @solarfacts4242
      @solarfacts4242  ปีที่แล้ว

      😊

    • @tejasshirke1267
      @tejasshirke1267 ปีที่แล้ว

      Can feel you... seniors do tell but bcoz of work pressure, most of the times they're rude🙃 but that's how we learn.

    • @user-uj4ms9zf3d
      @user-uj4ms9zf3d 3 หลายเดือนก่อน

      @@tejasshirke1267 Brother the values which i get from soil report is in ohm.meter for example 87 ogm.meter, how i will convert it to Kelvin.meter/watt?

  • @SONUSAINI-lz6qs
    @SONUSAINI-lz6qs ปีที่แล้ว

    This video is very important every electrical field.
    Thank you sir.

  • @mohammadumer37
    @mohammadumer37 ปีที่แล้ว +2

    Informative sir ❤

  • @sumitjambhulkar8875
    @sumitjambhulkar8875 ปีที่แล้ว

    Very helpful video sir.... thanks

  • @Shailendra_singh_81
    @Shailendra_singh_81 8 หลายเดือนก่อน

    Thank you for the good information i think need to some more calculation like Derating Factor of Cable ?

  • @nisark.v6010
    @nisark.v6010 7 หลายเดือนก่อน

    Great❤❤

  • @rajkandari5069
    @rajkandari5069 2 หลายเดือนก่อน

    Gajab video

  • @sohampise260
    @sohampise260 2 ปีที่แล้ว +1

    Proper explanation ; thank you for such good video.

    • @solarfacts4242
      @solarfacts4242  2 ปีที่แล้ว

      Thanks 🙏

    • @user-uj4ms9zf3d
      @user-uj4ms9zf3d 3 หลายเดือนก่อน

      @@solarfacts4242 Thanks for your videos. Brother the values which i get from soil report is in ohm.meter for example 87 ogm.meter, how i will convert it to Kelvin.meter/watt?

  • @Jsr735
    @Jsr735 ปีที่แล้ว +1

    well done sir,from long time need for such a good explanation..I LIKED UR VDO

  • @chandrakantchaudhari7679
    @chandrakantchaudhari7679 ปีที่แล้ว +1

    Very very nice video Sirji

  • @surajbk1020
    @surajbk1020 2 ปีที่แล้ว +1

    Sir thanks. Very useful 😇😇

  • @abusalehAbir
    @abusalehAbir ปีที่แล้ว +1

    Very nice Sir . keep up the good work Sir :)

  • @useer-eo3tn
    @useer-eo3tn 10 หลายเดือนก่อน +3

    Ap bht acha prhate ho aisi videos bnate rhee... Respect from pakistan

    • @solarfacts4242
      @solarfacts4242  10 หลายเดือนก่อน

      Thanks

    • @user-uj4ms9zf3d
      @user-uj4ms9zf3d 3 หลายเดือนก่อน

      @@solarfacts4242 Brother the values which i get from soil report is in ohm.meter for example 87 ogm.meter, how i will convert it to Kelvin.meter/watt?

  • @Amazingsolar7753
    @Amazingsolar7753 2 ปีที่แล้ว +2

    Nice video

  • @skmgamer8214
    @skmgamer8214 9 หลายเดือนก่อน

    Would the calculation be the same for the cable from Inverter to the LT panel?

  • @mohamadsafwan4575
    @mohamadsafwan4575 ปีที่แล้ว

    Lot of thanks.....

  • @kavinraj6388
    @kavinraj6388 2 ปีที่แล้ว +1

    Hi sir,fantastic explanation,kindly make video for current carrying capacity of particular armoured cables size(without knowing power) ,like 4 core 240 sqmm armoured cable.

    • @solarfacts4242
      @solarfacts4242  2 ปีที่แล้ว

      Ok Good Topic thanks 🙏

    • @fahadmukhtar1124
      @fahadmukhtar1124 ปีที่แล้ว

      @@solarfacts4242 bahi jaan 1000 & 100 kider sey aya?

  • @vinayff2461
    @vinayff2461 2 ปีที่แล้ว

    Excellent video

  • @sayedmustaffa2296
    @sayedmustaffa2296 2 ปีที่แล้ว +1

    Ok Thank you for detail video
    Kindly requesting to provide details for Multiple cables running in ground
    Multiple cables running in air through cable tray

  • @akm4590
    @akm4590 ปีที่แล้ว +1

    great video

  • @kv848
    @kv848 2 ปีที่แล้ว +1

    Good brother,.But to finalize cable, you must check the short circuit capacity of cable also...

  • @anmol_ashu1822
    @anmol_ashu1822 ปีที่แล้ว +1

    Good 😊❤

  • @electricalengineer-ey4fe
    @electricalengineer-ey4fe ปีที่แล้ว +1

    Good work

  • @singhdevendra802
    @singhdevendra802 หลายเดือนก่อน

    One question I have is that for calculating full load current will the current be divided by k factor value or will it be multiplied by k factor value beacuse k factor is correction factor means it is derating the cable current depending on certain parameters so full load current should reduce and for that we should multiply the current by k factor. This is my assumption, please correct if I am wrong.

  • @prakashmathad5563
    @prakashmathad5563 ปีที่แล้ว

    Thank you for the good information. I would like to know regarding the K ratings.. On which basis we should we take the K ratings.. I mean do we have any BIS Or ISI to prove.. If ask someone..

    • @swapnilshiyaniya5306
      @swapnilshiyaniya5306 ปีที่แล้ว

      K ratings are given in evry company's Wire catelogue. You can find K rating as per your need

    • @solarfacts4242
      @solarfacts4242  10 หลายเดือนก่อน

      You can get this from manufacturer or for normal calculation I will share the link in the description

  • @vaibhaodnyaneshwarkelzarka6153
    @vaibhaodnyaneshwarkelzarka6153 4 หลายเดือนก่อน

    Thank you

  • @adnansafi2332
    @adnansafi2332 14 วันที่ผ่านมา

    As depth of cable ur selecting from chart 1050 Meter and that sqmm of cable how can we decide that 70 sqmm. after correction factor calculation only we can decide sqmm of cable on wht basis or consideration we are taking 70 sqmm before calculating correction factor

  • @amolgaikwad7146
    @amolgaikwad7146 5 หลายเดือนก่อน

    Hi bro in last while calculation of voltage drop you write 139 amp but while adding "k" factor this is 142 so what is correct ?

  • @vinodmenariya3471
    @vinodmenariya3471 2 ปีที่แล้ว +1

    Sir it great please made single phase wire size selection

  • @Mikku7Vlog
    @Mikku7Vlog 11 หลายเดือนก่อน +1

    Dear Raman ji this is for aluminium cable or copper cable ? For both these same formula will be applicable or different if different formula then please tell

    • @solarfacts4242
      @solarfacts4242  10 หลายเดือนก่อน

      Same formula only values will change

  • @kanagarajayyappan7690
    @kanagarajayyappan7690 ปีที่แล้ว +3

    i have a comments against your subject , final calculation which your apply instead of 1000 u r putting 100 , please clarified this , and over all v.good

    • @solarfacts4242
      @solarfacts4242  ปีที่แล้ว +1

      That is 1000 there is written error

  • @SONUSAINI-lz6qs
    @SONUSAINI-lz6qs ปีที่แล้ว

    Very helpful videos sir

  • @mehadimonjurkhan8506
    @mehadimonjurkhan8506 ปีที่แล้ว +1

    @solar Facts thanks a lot for this video. can u share the book name about k factors table u have used in this calculation???

    • @swapnilshiyaniya5306
      @swapnilshiyaniya5306 ปีที่แล้ว

      K factors are given by manufacturing company. You can follow them

    • @solarfacts4242
      @solarfacts4242  10 หลายเดือนก่อน

      That you can get from the manufacturer whose cable you are going to use

  • @aalamraza3213
    @aalamraza3213 2 ปีที่แล้ว

    Good explain

  • @deepakkyadav2381
    @deepakkyadav2381 6 หลายเดือนก่อน +4

    Source ? Reference Book or any National Indian Standard ?

    • @asispuri8580
      @asispuri8580 3 หลายเดือนก่อน

      Hey bro! Did you got any reference book or standard? If yes can you share it to me and if you are experienced in this field can you tell I should go by this video?

  • @neutral6778
    @neutral6778 ปีที่แล้ว +1

    Sir kindly make a video of wire size calculation for normal house wiring and what point need to keep in mind whenever we will go for solar in future

  • @minujha8214
    @minujha8214 2 ปีที่แล้ว +1

    👍👍👍👍

  • @engrasad2965
    @engrasad2965 6 หลายเดือนก่อน

    Aoa dear your video is very helpful... Kindly give just one answer...
    If I use the 4 core 70mmsq then it's means that number of cable run = 1...or 4

  • @umaid-nungshatpa
    @umaid-nungshatpa 9 หลายเดือนก่อน

    Voltage drop me system full load current lena tha ya nahi?

  • @sherrydreaming5987
    @sherrydreaming5987 2 ปีที่แล้ว

    Some industry is maintaining a power factor of 0.95 and if we are to choose wire size then we take solar load into consideration. e.g. if we have a 50 kw solar project then Solar load will be at a max not more than 50kw and power factor will be maintained. So can we chose the wire size on that basis or we will have to consider PF as 0.8 for all cases. Plz clear.

    • @solarfacts4242
      @solarfacts4242  2 ปีที่แล้ว

      generally we consider power factor 0.80 for the wire calculation

  • @mohdanjum267
    @mohdanjum267 2 ปีที่แล้ว +2

    Regarding voltage drop calculation Are you sure about considering current value 139.12 amps . Why not used current rating 142.28 ?

  • @sanketbhangeofficial2531
    @sanketbhangeofficial2531 ปีที่แล้ว +1

    Great vedio sir. How can we put values of k factor like air temp.

    • @solarfacts4242
      @solarfacts4242  ปีที่แล้ว

      There is a sheet from where you can find out the values of K

  • @pushpendrakumar2736
    @pushpendrakumar2736 ปีที่แล้ว +1

    Sir 3/3.5/4 core cable ke liye kis size ka gland or holesaw cutter use hota iski info share kariye

  • @syedahsanahmad7806
    @syedahsanahmad7806 6 หลายเดือนก่อน

    how did you select 70sqmm=164Amp

  • @sapnatripathi6658
    @sapnatripathi6658 7 หลายเดือนก่อน

    There are different type of gauge of wire available in market in same category like 2.5mm wire different companies has different gauge you don't even mention a single time about gauge i want some information about it how can i contact you

  • @skmgamer8214
    @skmgamer8214 9 หลายเดือนก่อน

    sir voltage drop me 100/1000 kiss chiz k liye hai?

  • @SK-iv2fc
    @SK-iv2fc 7 หลายเดือนก่อน

    Plz sir relay setting calculation per video banaye

  • @nimeshmandal7606
    @nimeshmandal7606 2 ปีที่แล้ว +1

    Sir, Inverter always work on unity factor, so why you. Have consider .8 PF
    Can you explain ?

    • @solarfacts4242
      @solarfacts4242  2 ปีที่แล้ว +1

      Inverter power factor is unity but as per my consideration power factor always depends on load that why I have take 0.8

  • @pradeeppoojari2786
    @pradeeppoojari2786 6 หลายเดือนก่อน

    How derating factor to be devided instead of multiplying..can you clarify..

  • @trilochanpanigrahi3681
    @trilochanpanigrahi3681 2 ปีที่แล้ว +1

    I can't understand value of jsinφ because you take R = 0.6 and sinφ=0.6 both reading value are same so I confused. which parameter value putting in the place of sinφ

    • @solarfacts4242
      @solarfacts4242  2 ปีที่แล้ว +1

      Cos @ = 0.8
      You can calculate @
      Then when you will do sin @ you will get value = 0.6

  • @ankushpatil3451
    @ankushpatil3451 ปีที่แล้ว

    Why you taken current as 139 while calculating voltage drop ???

  • @looserregrets3623
    @looserregrets3623 2 ปีที่แล้ว +1

    Can we use simple polycab 4sqmm ac wire in 3kw solar ongrid system?

    • @solarfacts4242
      @solarfacts4242  2 ปีที่แล้ว

      Yes
      But you have to check cable length

    • @looserregrets3623
      @looserregrets3623 2 ปีที่แล้ว

      @@solarfacts4242 90 ft. Approximately

  • @shrikantvaze2837
    @shrikantvaze2837 ปีที่แล้ว +1

    Sir, cable selection me short circuit current nahi consider karte hai kya ?

  • @amarnathmishra1461
    @amarnathmishra1461 ปีที่แล้ว

    Good endeavor. But, to calculate voltage drop, why current be multiplied by root three? In star mode, phase voltage equals line voltage.

    • @solarfacts4242
      @solarfacts4242  ปีที่แล้ว

      No
      Sir in delta phase voltage is equal to line voltage

    • @amarnathmishra1461
      @amarnathmishra1461 ปีที่แล้ว

      Right. My mistake. In star mode, phase current equals line current.But here we are calculating voltage drop making use of current. Is it still required to be multiplied by root three?

  • @soorajsharma4694
    @soorajsharma4694 ปีที่แล้ว +1

    Sir mujhe 1.5ton non inverter technology 4 AC chalana he mcb box se electricity pole Tak main line 25 mtr Lambi Ho Jayegi to bataiye 2 core aluminium wire kitne mm ka lagaen

  • @kanagarajayyappan7690
    @kanagarajayyappan7690 ปีที่แล้ว +1

    wher u apply value in formula there please clarified mean where divided the value u r put 415 x1 x100 instead of 1000

    • @solarfacts4242
      @solarfacts4242  ปีที่แล้ว

      That is 1000 there is written error

  • @ayushshortvlogs3499
    @ayushshortvlogs3499 11 หลายเดือนก่อน +1

    Hello sir....generator voltage too low ... inverters main issue hai ..?

    • @solarfacts4242
      @solarfacts4242  11 หลายเดือนก่อน

      You have to keep the voltage In range of inverter

  • @RaganiG
    @RaganiG ปีที่แล้ว +1

    Sir fault level pr cable size pr kya effect h please elaborate the fualt level effect

    • @solarfacts4242
      @solarfacts4242  10 หลายเดือนก่อน

      Yes will make a separate video on it

  • @Mikku7Vlog
    @Mikku7Vlog 11 หลายเดือนก่อน +1

    Sir in this video you didn't calculate power loss.
    So can you tell or describe the power loss finding according to this calculation?

    • @solarfacts4242
      @solarfacts4242  10 หลายเดือนก่อน

      That will be a separate video

  • @raman5409
    @raman5409 8 หลายเดือนก่อน

    please explain cable size of 300kw load

  • @Jehangir.e
    @Jehangir.e ปีที่แล้ว +1

    For Home wiring we also find voltage drop?

    • @solarfacts4242
      @solarfacts4242  ปีที่แล้ว +1

      Yes you can find the voltage drop for home also

    • @Jehangir.e
      @Jehangir.e ปีที่แล้ว

      Same method?

  • @mehadimonjurkhan8506
    @mehadimonjurkhan8506 ปีที่แล้ว +1

    bhai iska internation rules reference de sakte ho kya?? ye rules kaha se liya apne please send us reference

  • @sapnatripathi6658
    @sapnatripathi6658 7 หลายเดือนก่อน

    How can i contact you

  • @digvijaybarge
    @digvijaybarge 2 ปีที่แล้ว +1

    Which cable Cu or Al for 95 sq.mm ?

  • @faizuddin7489
    @faizuddin7489 2 ปีที่แล้ว

    Respected sir,
    Jo apne 6% ka loss calculate kiya end me wo kitni length par jakay hoga or length ko formula me kese put krengy pls sir help

    • @solarfacts4242
      @solarfacts4242  ปีที่แล้ว

      this will happen at 200 Meter
      already mention in Video

  • @gulsherahmad6198
    @gulsherahmad6198 ปีที่แล้ว +1

    Plz share the link of the Tables which you are used .

  • @user-ik3py5wb3h
    @user-ik3py5wb3h 5 หลายเดือนก่อน

    Why you consider current valve 139 intead of 142.12 amp ? I think there is some mistakes?

    • @shahidhassan786
      @shahidhassan786 4 หลายเดือนก่อน

      It is because the full.load current flow is 139 amp not 142amp.

  • @avradeepdas1606
    @avradeepdas1606 ปีที่แล้ว

    Sir, why Value of k1,k4,k6,k7 are not considered ??

  • @Abdulghaffar-hw8nu
    @Abdulghaffar-hw8nu 9 หลายเดือนก่อน

    Sir end mea jo ap nay calculation keya hy 6.26" ye answer nai ah rah kindly explain me

    • @Abdulghaffar-hw8nu
      @Abdulghaffar-hw8nu 9 หลายเดือนก่อน

      Ya kisi Bhai ko pata ho kindly tell me

  • @danishalam1061
    @danishalam1061 2 ปีที่แล้ว +1

    Ye aluminium cable ka hai ya copper cable ka

  • @Jehangir.e
    @Jehangir.e ปีที่แล้ว +1

    Please share data sheet of current carrying capacity of cable

    • @solarfacts4242
      @solarfacts4242  ปีที่แล้ว

      You can download for google it is easily available

  • @ranjan1436
    @ranjan1436 2 ปีที่แล้ว +1

    why have you taken 139 A in the voltage drop calculation whereas the current after the K factor is 142A?

  • @sanaparveen9642
    @sanaparveen9642 2 ปีที่แล้ว +1

    Sir 4 core cable ya sirf single core cable

    • @solarfacts4242
      @solarfacts4242  2 ปีที่แล้ว +1

      You can calculate for both

    • @sanaparveen9642
      @sanaparveen9642 2 ปีที่แล้ว

      Sir 4 core cable me nutral current kitna flow karega or agr humara system pura sirf unbalance ho 3phase and nutral ko hum sirf single phase and nutral use karrahe ho to kya nutral wire 3 phase wire ka sum hoga

  • @niteshgiri4650
    @niteshgiri4650 ปีที่แล้ว

    In ac cable voltage drop formula you did you divide it by 1000 as per formula. Bcs you wrote 415x100

  • @kousikchatterjee7490
    @kousikchatterjee7490 3 หลายเดือนก่อน

    How to find K1= cable in Air.

  • @Anjalidas1999
    @Anjalidas1999 11 หลายเดือนก่อน +1

    Fault current consideration?

    • @solarfacts4242
      @solarfacts4242  10 หลายเดือนก่อน

      Yes should do we will make a video where we will do that also

  • @avlog2600
    @avlog2600 3 หลายเดือนก่อน

    In voltage drop what us sin fai and explain and in formula 1000 but in numerical 100 please share original formula

  • @asfaquealam9086
    @asfaquealam9086 ปีที่แล้ว +1

    K6 ka value aapne consider ni kiya hai. What about that?

  • @allinonewithshyamjeedwived4606
    @allinonewithshyamjeedwived4606 ปีที่แล้ว +1

    Sir can u send selection chart of cable

  • @whydoyouwannaknowmyname6510
    @whydoyouwannaknowmyname6510 5 หลายเดือนก่อน

    Correction : for voltage drop
    It is( 1.732*I*R*L*100) / V3ph * NO.of Run * 1000

  • @rishikeshsali4753
    @rishikeshsali4753 ปีที่แล้ว +1

    Can u please explain why u choose 70 sqmm directly and started selectin gparameters as per that , u didn't give any contex or explanation over there , 9.47 minutes

    • @solarfacts4242
      @solarfacts4242  ปีที่แล้ว

      This was random selection just to check whether it is ok or not
      I will also share one video where you can find the calculation for the cross section of wire

  • @swapnilshiyaniya5306
    @swapnilshiyaniya5306 ปีที่แล้ว +1

    @Solar Facts : Dear sir i think you mis calculated current in voltage drop equation. Value for current should be 142.28 Amp as per my thinking. Please correct me if i am wrong.

    • @solarfacts4242
      @solarfacts4242  ปีที่แล้ว

      Yes there is a calculation error at the last

  • @vnmbnaidutvnmbnaidut1969
    @vnmbnaidutvnmbnaidut1969 ปีที่แล้ว

    Why using 1.732x somexcable length x 100...in this why multiple with 100 ??

  • @anilrsinhindi3311
    @anilrsinhindi3311 ปีที่แล้ว

    Tnx ji n I have gifted you check plz

  • @theemperor__
    @theemperor__ ปีที่แล้ว +1

    You took sin& =0.6 Can you pls explain how

    • @solarfacts4242
      @solarfacts4242  ปีที่แล้ว

      We know cos @ = 0.8 from here you can get @ value then you can calculate sin @

    • @surekhapise8978
      @surekhapise8978 6 หลายเดือนก่อน +1

      ​@@solarfacts4242
      Didn't get calculation
      Cos(@) suppose we put 0.8 then value get 0.99
      Sin(0.99)=0.0172

  • @ranaahmadkaleem
    @ranaahmadkaleem 5 หลายเดือนก่อน

    LAST Calculation m 100 likha 1000 ki jgah,, baki thek h

    • @solarfacts4242
      @solarfacts4242  5 หลายเดือนก่อน

      That written by mistake

  • @thesocialpursuit
    @thesocialpursuit ปีที่แล้ว +1

    At 9:48. Jb hme cable size malum hi ni.. to apne 70 sqmm cable q consider ki...y to champu bna rhe h ap

    • @solarfacts4242
      @solarfacts4242  ปีที่แล้ว

      That I have consider just to calculate you can put other cable data then you will find whether you need to increase to increase the cross-section or decrease the cross-section of cable as per answer

  • @viralparmar9889
    @viralparmar9889 2 ปีที่แล้ว

    Why u used 139 A insted of 142 A .
    U have not mentioned cable size in formula so how I know 70 sq mm is wrong

    • @solarfacts4242
      @solarfacts4242  2 ปีที่แล้ว

      We have use 142 amp considering K- Factor - 0.9667

    • @solarfacts4242
      @solarfacts4242  2 ปีที่แล้ว

      Now you have to match the current with cable data sheet which cable is able to handle this current accordingly we select the cable

  • @Engr-vy3in
    @Engr-vy3in ปีที่แล้ว

    ANY ENGLISH TRANSALTION ?

  • @SKDYOUTUBE
    @SKDYOUTUBE 2 หลายเดือนก่อน

    70 sqmm cable size kahan se aa gya 😂

  • @satyaranjanprusty9074
    @satyaranjanprusty9074 ปีที่แล้ว

    I think below calculator is wrong

  • @ramishahmed6436
    @ramishahmed6436 11 หลายเดือนก่อน +1

    Samaj ni aya k factor tu bilkul ni

  • @nabeelasghar6883
    @nabeelasghar6883 6 หลายเดือนก่อน

    Electrical Engineering portal 😂😂😂😂 Dont just copy stuff