@@tejasshirke1267 Brother the values which i get from soil report is in ohm.meter for example 87 ogm.meter, how i will convert it to Kelvin.meter/watt?
Great vedio sir, I have'nt seen this type of content on this particular topic in which any industry can actually calculate their cable size and will no longer be dependent on assumptions.
Hi, thank you for this video. I have a quick question for you, instead of using 95sqmm size cable, can we route two run of 70sqmm cable or not??? Please tell me the reason. Once again thank you.
Ok Thank you for detail video Kindly requesting to provide details for Multiple cables running in ground Multiple cables running in air through cable tray
this is very good but i have a small doubt let's consider the 80kw load is inductive so the starting current will be more don't we have to consider that in it ??
@@solarfacts4242 Thanks for your videos. Brother the values which i get from soil report is in ohm.meter for example 87 ogm.meter, how i will convert it to Kelvin.meter/watt?
Hey bro! Did you got any reference book or standard? If yes can you share it to me and if you are experienced in this field can you tell I should go by this video?
Hi sir, Kindly guide I have to take connection from electric pole which is 500 meters away for bunglow Existing cable which i am using voltage dropps from 220 to 170 while starting motor, Meter connection i have got for 2kw. This is overhead connection, Without any other wire. Kindly advice the wire to choose
Dear Raman ji this is for aluminium cable or copper cable ? For both these same formula will be applicable or different if different formula then please tell
i have a comments against your subject , final calculation which your apply instead of 1000 u r putting 100 , please clarified this , and over all v.good
Hi sir,fantastic explanation,kindly make video for current carrying capacity of particular armoured cables size(without knowing power) ,like 4 core 240 sqmm armoured cable.
Sir could you please help me our load ism1500kw so how many cables of 300mm aluminium would we need from transformer to load , cable length approximately 50m
As depth of cable ur selecting from chart 1050 Meter and that sqmm of cable how can we decide that 70 sqmm. after correction factor calculation only we can decide sqmm of cable on wht basis or consideration we are taking 70 sqmm before calculating correction factor
One question I have is that for calculating full load current will the current be divided by k factor value or will it be multiplied by k factor value beacuse k factor is correction factor means it is derating the cable current depending on certain parameters so full load current should reduce and for that we should multiply the current by k factor. This is my assumption, please correct if I am wrong.
Thank you for the good information. I would like to know regarding the K ratings.. On which basis we should we take the K ratings.. I mean do we have any BIS Or ISI to prove.. If ask someone..
Right. My mistake. In star mode, phase current equals line current.But here we are calculating voltage drop making use of current. Is it still required to be multiplied by root three?
Sir mujhe 1.5ton non inverter technology 4 AC chalana he mcb box se electricity pole Tak main line 25 mtr Lambi Ho Jayegi to bataiye 2 core aluminium wire kitne mm ka lagaen
There are different type of gauge of wire available in market in same category like 2.5mm wire different companies has different gauge you don't even mention a single time about gauge i want some information about it how can i contact you
Some industry is maintaining a power factor of 0.95 and if we are to choose wire size then we take solar load into consideration. e.g. if we have a 50 kw solar project then Solar load will be at a max not more than 50kw and power factor will be maintained. So can we chose the wire size on that basis or we will have to consider PF as 0.8 for all cases. Plz clear.
I can't understand value of jsinφ because you take R = 0.6 and sinφ=0.6 both reading value are same so I confused. which parameter value putting in the place of sinφ
@Solar Facts : Dear sir i think you mis calculated current in voltage drop equation. Value for current should be 142.28 Amp as per my thinking. Please correct me if i am wrong.
Sir apne resistance, reactance ka value galt le liya he . Apne Resistance liya he 0.6 jabki multi core aluminum cable ka Resistance he 0.568 ohm he . Reactance apne 0.1ohm liya he jabki aluminum multi core cable ka Reactance 0.07 he. Please explain if I am wrong
Can u please explain why u choose 70 sqmm directly and started selectin gparameters as per that , u didn't give any contex or explanation over there , 9.47 minutes
This was random selection just to check whether it is ok or not I will also share one video where you can find the calculation for the cross section of wire
Sir 4 core cable me nutral current kitna flow karega or agr humara system pura sirf unbalance ho 3phase and nutral ko hum sirf single phase and nutral use karrahe ho to kya nutral wire 3 phase wire ka sum hoga
Thankyou bhaiya
I’m a working professional nd I’m really suffering alot in corporate world because no one is ready to tell me
😊
Can feel you... seniors do tell but bcoz of work pressure, most of the times they're rude🙃 but that's how we learn.
@@tejasshirke1267 Brother the values which i get from soil report is in ohm.meter for example 87 ogm.meter, how i will convert it to Kelvin.meter/watt?
Great vedio sir, I have'nt seen this type of content on this particular topic in which any industry can actually calculate their cable size and will no longer be dependent on assumptions.
Thanks 🙏
Ap bht acha prhate ho aisi videos bnate rhee... Respect from pakistan
Thanks
@@solarfacts4242 Brother the values which i get from soil report is in ohm.meter for example 87 ogm.meter, how i will convert it to Kelvin.meter/watt?
Helpful videos for Industrial projects
Thank you
You are welcome
This video is very important every electrical field.
Thank you sir.
Many many thanks
Hi, thank you for this video. I have a quick question for you, instead of using 95sqmm size cable, can we route two run of 70sqmm cable or not??? Please tell me the reason. Once again thank you.
well done sir,from long time need for such a good explanation..I LIKED UR VDO
Thank you so much 🙏🏻
Thank you for the good information i think need to some more calculation like Derating Factor of Cable ?
Ok Thank you for detail video
Kindly requesting to provide details for Multiple cables running in ground
Multiple cables running in air through cable tray
ok i will make video on it
this is very good but i have a small doubt let's consider the 80kw load is inductive so the starting current will be more don't we have to consider that in it ??
Informative sir ❤
Thank you 🙏🏻
Proper explanation ; thank you for such good video.
Thanks 🙏
@@solarfacts4242 Thanks for your videos. Brother the values which i get from soil report is in ohm.meter for example 87 ogm.meter, how i will convert it to Kelvin.meter/watt?
Very nice Sir . keep up the good work Sir :)
Thanks 🙏🏻
Superb bro u r awesome keep it up n thank u soo much ❤
Very helpful video sir.... thanks
Most welcome
very good sir
Very very nice video Sirji
Thank you
Sir sorry, I have question in cable sizing.
What is the meaning of no of runs?
Example:
5R/3.5C/240sqm/XLPE and
1R/3.5C/25sqm/XLPE
Thank you Sir
Sir thanks. Very useful 😇😇
👍
Excellent information
Source ? Reference Book or any National Indian Standard ?
Hey bro! Did you got any reference book or standard? If yes can you share it to me and if you are experienced in this field can you tell I should go by this video?
@solar Facts thanks a lot for this video. can u share the book name about k factors table u have used in this calculation???
K factors are given by manufacturing company. You can follow them
That you can get from the manufacturer whose cable you are going to use
Sir 3/3.5/4 core cable ke liye kis size ka gland or holesaw cutter use hota iski info share kariye
I will make one video on it
Regarding voltage drop calculation Are you sure about considering current value 139.12 amps . Why not used current rating 142.28 ?
Let me check
Hi sir,
Kindly guide
I have to take connection from electric pole which is 500 meters away for bunglow
Existing cable which i am using voltage dropps from 220 to 170 while starting motor,
Meter connection i have got for 2kw.
This is overhead connection,
Without any other wire.
Kindly advice the wire to choose
Dear Raman ji this is for aluminium cable or copper cable ? For both these same formula will be applicable or different if different formula then please tell
Same formula only values will change
i have a comments against your subject , final calculation which your apply instead of 1000 u r putting 100 , please clarified this , and over all v.good
That is 1000 there is written error
Hi sir,fantastic explanation,kindly make video for current carrying capacity of particular armoured cables size(without knowing power) ,like 4 core 240 sqmm armoured cable.
Ok Good Topic thanks 🙏
@@solarfacts4242 bahi jaan 1000 & 100 kider sey aya?
Sir kindly make a video of wire size calculation for normal house wiring and what point need to keep in mind whenever we will go for solar in future
ok sure thank you
Gajab video
Sir could you please help me
our load ism1500kw so how many cables of 300mm aluminium would we need from transformer to load , cable length approximately 50m
Aoa dear your video is very helpful... Kindly give just one answer...
If I use the 4 core 70mmsq then it's means that number of cable run = 1...or 4
1 run 4 core
Could you pls do videos also in English? So it will be accessible for much bigger audience. thnx
As depth of cable ur selecting from chart 1050 Meter and that sqmm of cable how can we decide that 70 sqmm. after correction factor calculation only we can decide sqmm of cable on wht basis or consideration we are taking 70 sqmm before calculating correction factor
Good brother,.But to finalize cable, you must check the short circuit capacity of cable also...
yes
Nice video
Thanks 🙏
Sir it great please made single phase wire size selection
Ok sure I will
One question I have is that for calculating full load current will the current be divided by k factor value or will it be multiplied by k factor value beacuse k factor is correction factor means it is derating the cable current depending on certain parameters so full load current should reduce and for that we should multiply the current by k factor. This is my assumption, please correct if I am wrong.
great video
Thanks for the visit
Thank you for the good information. I would like to know regarding the K ratings.. On which basis we should we take the K ratings.. I mean do we have any BIS Or ISI to prove.. If ask someone..
K ratings are given in evry company's Wire catelogue. You can find K rating as per your need
You can get this from manufacturer or for normal calculation I will share the link in the description
Where can I find K factor tables? and why sin(fi) 0.6?
Good endeavor. But, to calculate voltage drop, why current be multiplied by root three? In star mode, phase voltage equals line voltage.
No
Sir in delta phase voltage is equal to line voltage
Right. My mistake. In star mode, phase current equals line current.But here we are calculating voltage drop making use of current. Is it still required to be multiplied by root three?
Why you taken current as 139 while calculating voltage drop ???
Correction : for voltage drop
It is( 1.732*I*R*L*100) / V3ph * NO.of Run * 1000
Hi bro in last while calculation of voltage drop you write 139 amp but while adding "k" factor this is 142 so what is correct ?
Would the calculation be the same for the cable from Inverter to the LT panel?
But sir i have 1 confusion is this for almunium cabels or for copper
Good 😊❤
Thank you 🙏🏻
Great❤❤
Very helpful videos sir
Thanks and welcome
100 kider sey aya?
Good work
Thank you
Voltage drop me system full load current lena tha ya nahi?
Sir in this video you didn't calculate power loss.
So can you tell or describe the power loss finding according to this calculation?
That will be a separate video
Excellent video
thanks
Sir mujhe 1.5ton non inverter technology 4 AC chalana he mcb box se electricity pole Tak main line 25 mtr Lambi Ho Jayegi to bataiye 2 core aluminium wire kitne mm ka lagaen
Replied on phone 😊
For Home wiring we also find voltage drop?
Yes you can find the voltage drop for home also
Same method?
Sir, Inverter always work on unity factor, so why you. Have consider .8 PF
Can you explain ?
Inverter power factor is unity but as per my consideration power factor always depends on load that why I have take 0.8
Can we use simple polycab 4sqmm ac wire in 3kw solar ongrid system?
Yes
But you have to check cable length
@@solarfacts4242 90 ft. Approximately
Lot of thanks.....
thanks
wher u apply value in formula there please clarified mean where divided the value u r put 415 x1 x100 instead of 1000
That is 1000 there is written error
how did you select 70sqmm=164Amp
Great vedio sir. How can we put values of k factor like air temp.
There is a sheet from where you can find out the values of K
Hello sir....generator voltage too low ... inverters main issue hai ..?
You have to keep the voltage In range of inverter
There are different type of gauge of wire available in market in same category like 2.5mm wire different companies has different gauge you don't even mention a single time about gauge i want some information about it how can i contact you
👍👍👍
bhai iska internation rules reference de sakte ho kya?? ye rules kaha se liya apne please send us reference
Ok
Ye 👍 baat Hui na sir
Some industry is maintaining a power factor of 0.95 and if we are to choose wire size then we take solar load into consideration. e.g. if we have a 50 kw solar project then Solar load will be at a max not more than 50kw and power factor will be maintained. So can we chose the wire size on that basis or we will have to consider PF as 0.8 for all cases. Plz clear.
generally we consider power factor 0.80 for the wire calculation
From where did u get k value as .9
Plz share the link of the Tables which you are used .
Sure
Thank you
How derating factor to be devided instead of multiplying..can you clarify..
Why you consider current valve 139 intead of 142.12 amp ? I think there is some mistakes?
It is because the full.load current flow is 139 amp not 142amp.
Single phase ke liye yehi formula chalega kya voltage drop ka
Sir fault level pr cable size pr kya effect h please elaborate the fualt level effect
Yes will make a separate video on it
I can't understand value of jsinφ because you take R = 0.6 and sinφ=0.6 both reading value are same so I confused. which parameter value putting in the place of sinφ
Cos @ = 0.8
You can calculate @
Then when you will do sin @ you will get value = 0.6
Good explain
thank you
@Solar Facts : Dear sir i think you mis calculated current in voltage drop equation. Value for current should be 142.28 Amp as per my thinking. Please correct me if i am wrong.
Yes there is a calculation error at the last
please explain cable size of 300kw load
Sir, cable selection me short circuit current nahi consider karte hai kya ?
Karte hai
Will make a separate video
Plz sir relay setting calculation per video banaye
Sir can u send selection chart of cable
Sure
Please share data sheet of current carrying capacity of cable
You can download for google it is easily available
why have you taken 139 A in the voltage drop calculation whereas the current after the K factor is 142A?
That is typo mistake
Sorry
sir voltage drop me 100/1000 kiss chiz k liye hai?
K6 ka value aapne consider ni kiya hai. What about that?
By default it is 1
Sir apne resistance, reactance ka value galt le liya he . Apne Resistance liya he 0.6 jabki multi core aluminum cable ka Resistance he 0.568 ohm he .
Reactance apne 0.1ohm liya he jabki aluminum multi core cable ka Reactance 0.07 he.
Please explain if I am wrong
Ye aluminium cable ka hai ya copper cable ka
Al
Sir, why Value of k1,k4,k6,k7 are not considered ??
i have considered 1
Fault current consideration?
Yes should do we will make a video where we will do that also
How to find K1= cable in Air.
In voltage drop what us sin fai and explain and in formula 1000 but in numerical 100 please share original formula
In ac cable voltage drop formula you did you divide it by 1000 as per formula. Bcs you wrote 415x100
you can check the calculation
Respected sir,
Jo apne 6% ka loss calculate kiya end me wo kitni length par jakay hoga or length ko formula me kese put krengy pls sir help
this will happen at 200 Meter
already mention in Video
Which cable Cu or Al for 95 sq.mm ?
Al
You took sin& =0.6 Can you pls explain how
We know cos @ = 0.8 from here you can get @ value then you can calculate sin @
@@solarfacts4242
Didn't get calculation
Cos(@) suppose we put 0.8 then value get 0.99
Sin(0.99)=0.0172
Can u please explain why u choose 70 sqmm directly and started selectin gparameters as per that , u didn't give any contex or explanation over there , 9.47 minutes
This was random selection just to check whether it is ok or not
I will also share one video where you can find the calculation for the cross section of wire
👍👍👍👍
Thanks 😊
Sir 4 core cable ya sirf single core cable
You can calculate for both
Sir 4 core cable me nutral current kitna flow karega or agr humara system pura sirf unbalance ho 3phase and nutral ko hum sirf single phase and nutral use karrahe ho to kya nutral wire 3 phase wire ka sum hoga
Why using 1.732x somexcable length x 100...in this why multiple with 100 ??
This is the formula
I have check from where 100 is coming in formula