  • Hi, I'm Paul Whiffin from at ATSPACE and today, we're answering a question: "what is a vent test?" or what is a ventilation flow rate test? Ventilation is part F of the building regulations, and today we're going to show you how we perform one, and this is for an intermittent fan, which is system one. Right. Well, I'm going to show you is the equipment we use these are the two hoods that we get the reasons for different sort of style hood is to fit over certain circumference of fans and to get into those tricky areas. And basically what hooks on the back, this gadget here straight in there is the anemometer. And this measures the flow rate of extraction. So, I'm going to show you what it looks like when we stick it over a fan.
    So in here, we got utility. A small utility room. They got to achieve 30 litres a second in these small rooms due to all the appliances in them. Got to make sure the door has a gap underneath it so I can draw air in between 10and 12 mm. And the door should be shut when you're testing. So, Anyway, let's put it over the fan. Make sure it's a nice fit. You got to give it a bit of time for it to pick up things so we can measure it. Make sure the fan is working well. We got 31.4. So this complies with the building regulations. Were going into the bathroom next. Each wet room. Whether its is a bathroom, WC, kitchen has different extraction rates. So bathrooms have 15 litres a second WC, which stands for water closet which tends to be sinks and toilets they have a extraction rate of 6. Kitchen extraction rate of 30. If the hob is adjacent to the fan is got to achieve 60 so got to be a bit careful with what size of fans you actually instal right again, the fan is on. Sounds like it's working fine. Stick the hood over. This has to achieve 15 litres a second in the bathroom. And as you can see, and you can see that there we are achieving 15.4. This drops a little bit, due to the camera underneath it, there we go 15. So again, this complies with part F.What we do is we make a note of this, and we issue a certificate for building regulations to meet part F. And that you can submit your building control to get sign off. Thanks for watching the video if you like what you've seen, please like or subscribe and if you have any comments or questions, please put them below so I can help you further.

ความคิดเห็น • 11

  • @AngusAbbott-qf8xm
    @AngusAbbott-qf8xm 4 หลายเดือนก่อน +1

    Never heard about this Part F before, guess I’ll be getting someone else in to do this one

    • @atspaceltd654
      @atspaceltd654  4 หลายเดือนก่อน

      Hey, thanks for your comment. Yes, part F ventilation is super important, especially with all the houses becoming more airtight. ATSPACE will be happy to assist, welcome to speak to one of our relationship managers 0345 6465 454

  • @midaxng
    @midaxng หลายเดือนก่อน

    Thanks 👍

  • @stevenslin131
    @stevenslin131 2 ปีที่แล้ว +2

    Thank you Paul

  • @abuhadis2790
    @abuhadis2790 3 หลายเดือนก่อน

    Can you make vent axia advance sentinel kinetic ventilator extract and supply full flow rate test??

    • @atspaceltd654
      @atspaceltd654  3 หลายเดือนก่อน +1

      Yes, you can perform a full flow rate test on a Vent-Axia Advance Sentinel Kinetic ventilator for both extract and supply. To conduct this test, follow these general steps:
      Preparation:
      Ensure the ventilator is properly installed and all connections are secure.
      Verify that the unit is clean and any filters are in good condition.
      Equipment:
      Use an anemometer or airflow meter suitable for measuring the air volume and velocity.
      Test Setup:
      Access the control panel of the Sentinel Kinetic unit.
      Set the unit to maximum speed for both extract and supply modes. This may involve overriding normal operation settings.
      Measuring Extract Flow Rate:
      Measure the airflow at each extract point (vents) using the anemometer.
      Ensure the measurements are taken at the point where the airflow is most consistent.
      Record the airflow rates from all extract points.
      Measuring Supply Flow Rate:
      Measure the airflow at each supply point using the anemometer.
      Ensure the measurements are taken at the point where the airflow is most consistent.
      Record the airflow rates from all supply points.
      Calculation:
      Sum the recorded airflow rates to determine the total extract and supply flow rates.
      Verification:
      Compare the measured flow rates against the manufacturer's specifications to ensure the unit is performing correctly.
      Adjustment (if necessary):
      If the measured flow rates are outside the expected range, adjust the fan speeds or check for blockages and repeat the measurements.
      By following these steps, you can effectively test the full flow rate of both the extract and supply functions of the Vent-Axia Advance Sentinel Kinetic ventilator.
      If struggling, give ATSPACE a call to carry this out for you: T. 0345 6465 454 sales@atspaceltd.com

  • @paullittle2757
    @paullittle2757 ปีที่แล้ว

    How do you test cooker hoods?

    • @paulwhiffin6248
      @paulwhiffin6248 ปีที่แล้ว +1

      Hi cookers are tricky, best practice is to hold the hood over the exhaust outside of the building from the kitchen extractor, this will give you your flow rate.

  • @Dear-John..
    @Dear-John.. ปีที่แล้ว

    Hi guys, where can I purchase the hood and or the meter??

    • @paulwhiffin6248
      @paulwhiffin6248 ปีที่แล้ว +1

      I believe BSRIA can sell you the kit

  • @ahmedshosho7194
    @ahmedshosho7194 23 วันที่ผ่านมา

    Testo is the worst company in the world