Reliable level measurement with steam boiler approval

แชร์
ฝัง
  • เผยแพร่เมื่อ 27 ม.ค. 2025

ความคิดเห็น • 2

  • @AirForceVet76
    @AirForceVet76 4 ปีที่แล้ว +1

    Do you need to put a propagation velocity correction in on the flex86?

    • @VEGA_Level_Pressure
      @VEGA_Level_Pressure  4 ปีที่แล้ว +2

      Thanks for your question. The VEGAFLEX 86 steam probe which is shown in this video has a runtime correction which uses a known reference target inside the coax probe to compensate automatically for changing propagation velocities due to the steam atmosphere. This means, you don’t need to correct anything manually.