Automatic Changeover Switch for Generator / ATS for Single phase Wiring / ATS System for generator
ฝัง
- เผยแพร่เมื่อ 7 ก.พ. 2025
- In this video I hope to explain the circuit diagrams required to Automatic Changeover Switch for Generator, ATS for Single phase Wiring, ATS System for generator.
*Generator turns on automatically when the main supply fails.
*The generator will automatically turn off when the supply is restored.
*There are two AC powered and DC powered timers.
*The circuit is configured to interlock the two contactors, thus providing greater protection.
*This is a very important circuit for a home that uses a generator.
*** Red colour wire - Live wire(L)
*** Black colour wire - Neutral wire(N)
***Main supply contactor auxiliary point 2 should be N / C (normally closed).
***You can buy such a contactor in the market or you can use auxiliary contact block. Thanks.
****Thanks for watching video please subscribe my channel.
Watch out: **electrical wiring is very dangerous**you could be shocked or killed. If you are not trained and familiar with proper, safe electrical wiring practices don't try it.
My Other Video..
Ring Circuit Wiring Diagram | Socket Outlet Ring Circuit Wiring Diagram
• Ring Circuit Wiring Di...
Transistor How to Work Animation | Bipolar Transistor (NPN/PNP) | NPN Transistor | PNP Transistor
• Transistor How to Work...
generator auto start stop circuit diagram sinhala
Security Lamp Circuit | Security Light Wiring Connection
• Security Lamp Circuit ...
Forward Reverse Starter Power and Control Circuit | 3p Motor Forward and Reverse Control Wiring
• Forward Reverse 3 Phas...
Forward Reverse Starter Power and Control Wiring | 3p Motor Forward and Reverse Control Circuit
• Forward Reverse Starte...
Direct Online Starter(DOL) | 3 phase Motor Connection | Contactor Working | DOL Starter
• DOL starter control ci...
Electrical House Wiring Diagram/Single Phase House Wiring
• Electrical House Wirin...
Water Pump Automatic and Manual Control | Float Switch Wiring Diagram | Water Motor Float Wiring
• Water Pump Automatic a...
One Light On/Off Two Places /Two Way Circuit (method 1)
• Two way switch connect...
5V DC Power Supply | How to Make USB Port | 7805 Regulator IC | 5V DC
• 5V DC Power Supply | 7...
Emergency Light Wiring for Home | Home Emergency Light Wiring with Solar Power
• Emergency Light Wiring...
Water Pump Motor Automatic and Manual Control | Float Switch Wiring Diagram
• Water Pump Motor Auto ...
Solar Panel system for home/Solar Power system with inverter
• Solar Panel Wiring | S...
Generator Connect to the Home Distribution Board | Distribution Board Wiring with portable Generator
• Video
ats panel, ats automatic transfer switch, ats control circuit diagram, ats changeover switch, Automatic Changeover Switch, ATS System, ATS Wiring Diagram, ats switch for generator, ats panel for generator, generator ats panel wiring, generator ats wiring diagram, generator ats panel, generator ats controller, generator ats connection, ats for generator, ats auto start generator, ats connection to generator, ATS Automatic transmission system.
***Main supply contactor auxiliary point 2 should be N / C (normally closed). You can buy such a contactor in the market or you can use auxiliary contact block. Thanks.
Help me
Thanks for the video it's good but the generator contactor won't be energized since it doesn't receive the neutral
Thanks your best comment my friend.I'm made a small mistake.Sorry
Watch this one for beter understand it.
th-cam.com/video/rHpZEmuHknQ/w-d-xo.html
Very Useful video no doubt, thank you for your work and your time. but how could Bobin of the Power contactors and relays 230 V be ON (Energised), wen A2 terminal is connected from outlet terminals of the Contactors, or I misunderstud the Circuit?
Thank you very much for your comment. Please watch this for better understanding.
th-cam.com/video/rHpZEmuHknQ/w-d-xo.html&feature=share&EJGixIgBCJiu2KjB4oSJEQ
This very good
Thanks.keep watching my videos.
Good stuff
Thanks friend..
Great video
Thank you..
Thank you brother
Thanks friend
Sir light ane se genrator off hoga fir or DG contactor off hoga fir timer chalega last may Main contactor on hoga kya
Thanks friend ..
Please watch this video
th-cam.com/video/rHpZEmuHknQ/w-d-xo.html
Sir this very informative video God bless u but I can not understand why you use comman neutral plz explain me thanks
Thank you...In one case only one contactor is turned on (interlock system is used) so it is not common neutral.
Great video....One question though, why did u connect the generator relay-contactor's A2 coil terminal to main power neutral line, shouldn't the A2 for the generator be connected to line two of the generator power wire
Both contactors in this circuit do not turn on at the same time .interlock is used for this circuit.Therefore it is correct to connect the neutral terminals together and assign them to the A2 terminals.
Thank you very much your comment
I think u're wrong here. Y do you pick neutral from the output of the contactor to supply the terminal A2 of your coils? You Even linked both the utility and generator together?. Thought the generator would've gotten it's neutral from the input terminal of Gen contactor to feed its coils separately. My observation though, i stand to be corrected please
Thank you sir
Thank you friend..😍😍
Sir very good
But more explain by morally with practical bcs eas to understand
Thank you so much .. Ask if there is anything you do not understand
Single phase ATS explain
th-cam.com/video/rHpZEmuHknQ/w-d-xo.html
Pardon me, Shouldn't the Stop of the gen be connected to the N/O of the relay? In that way, it the completes the STOP circuit when the power returns
Thanks your comment. 😍
Depending on the type of start stop switch on the generator we can select N / O, N / C on the relay.
Please watch other video..
th-cam.com/video/rHpZEmuHknQ/w-d-xo.html
@@ELTronic3 my
I don’t know how to stop machine?when main supply coming?🙏
Thanks your comment.please watch my ATS video..
th-cam.com/video/rHpZEmuHknQ/w-d-xo.html
You take neutral kontrol after main contactor, how it will be activated
Neutral wire should be connect to contactor coil ..
Sir dg automatic on off hoga kya
Thank you friend your comment..
Please watch this video
th-cam.com/video/rHpZEmuHknQ/w-d-xo.html
Stop aur start push bottn hai kya ya
Gen stop piont how to work with N/C point in relay of contector
Gen stop and start function is same, hiw to work this function?
Sir please this doubt.
Watching care full my friend
th-cam.com/video/rHpZEmuHknQ/w-d-xo.htmlsi=DY91VePcfBL_pQGZ
Thanks.
good video but question is what if you wanted to simply run generator manually?
I will submit a video with a suitable solution for it.
Thank for your comment 😊
I want to see the 240 volts wiring diagram
The timer contactor used should be 240V.Diagram same
Watch this one..to better understand .
th-cam.com/video/rHpZEmuHknQ/w-d-xo.html
bahi jaan mujhy ji batain ky genrator ki jo start ke wire ja stop karny wali wire kaisy lagy gin ap ke meherbani ho gi janab ager numbr mil jaye to sab say best ha thanks
Thanks your comment..
th-cam.com/video/rHpZEmuHknQ/w-d-xo.html
❤❤❤❤
Thanks friend..
❤❤❤❤❤❤❤❤❤❤❤❤❤❤❤❤❤❤❤❤❤❤❤❤❤❤❤❤
❤️❤️❤️🙏🙏🙏.Thanks
merci pour le montage, comment la bobine du premier contacteur sera exciter or pour l'exciter , il faut que le timer soit fermé or il n'a pas encore son neutre pour basculer vers le contactes fermés ( 8 et 6), avec le relais aussi (8 et 6 est ouvert), il est alimenté par le neutre de la sortie or les contacteurs sont tous ouverts car leurs bobines ne sont excitées, ... le montage n'a pas encore fonctionné
Thanks your best comment...please watch this video for better idea
th-cam.com/video/rHpZEmuHknQ/w-d-xo.htmlsi=k732LE3WC3bwCwbz
Thanks..❤️❤️
Merci
Ok friend
sir please make 3phase ATS & auto generator diagram video
I will create this video immediatly.Thanks👍👍
For how many seconds we should set ac and dc timer
Give example
Sir video thoda jaldi banate to Accha hota
Thank you..next video create fast
Good Expalaination, Please send me 3phase ATS wiring diagram.
Thanks...i will create a 3 phase ats systerm
Hi, I have a Schneider conext 4024 system with a 24V Battery System. I have a WEN 4750 Generator like in your video above. With that said, I have a relay setup, that when I lose the AC, which basically means, that her home is dead from the AC side of the Solar system, it will signal the relay to switch to the generator. The problem with that, is that I still have to manually go out and start the generator.
So, what I’m Looking for is a switch that will sense the battery voltage and the loss of AC, in case of loss of Solar power, and a low voltage of the Battery system, to signal the Generator to start. Do you have any video's like that?
Thanks your comment.
There is currently no video created. I will create it.
Please sir is video main main & gen indicator & auto manual rotary switch connection Karke dikhyo
I will create this method video
If you use this comman neutral I think circuit not working plz clear this
In one case only one contactor is turned on (interlock system is used) so it is not common neutral.
How can i identity the stop and start wires of a generator?
Remove the wire from the start switch and off switch from the control box of the generator.
Connect the wire as in this video.
Pls how can i contact you to send you the images of the generator am talking about. Thanks?
@@christophernwafor9779 thank you.. your comment.
eltronic3@gmail.com
Ok bro
How its working with out Neutral U can not connect Neutral from the main power or Generator and how to stop Generator self starter wy U not use to NC point of contactor and it can run to b two timer 12vol and 220vol
Thank your comment..I always use contactor n/c point.interrlock system very important.
Please watch this video..
th-cam.com/video/rHpZEmuHknQ/w-d-xo.html
Please brief in audio how this circuit works
Thank you friend.I will create your video.😊
Check this out for now.
th-cam.com/video/rHpZEmuHknQ/w-d-xo.html
Thanks
Ok friend .Stay with me.🤗
And another why you use relay for generator stoping use n/c point
You can also use the N / O point depending on the stop switch used on the generator
oi vai aita koi pabo piz bolben
what are you saying dude....
សុំសួរមួយលោកគ្រូតើប្រព័ន្ធនេះវាដេរម៉ាស៊ីនភ្លើង auto មែន
Thanks your comment ..😍😍
Wiring on A2 is wrong it will not automatically turn to normal when the mains power returns.
Thanks your comment 😊..please watch this video.
th-cam.com/video/rHpZEmuHknQ/w-d-xo.html
Software name pls
Poor explanation, when ur sharing knowledge always try to explain not to play music
Stop too much music playing 2:43
এইখানে তিনটা রিলে দরকার নেই,,, একটাই এনাপ,, যদি জানলে,,,,,,
Thanks friend your comment..
Salut je peux avoir son schéma
No poblem.thanks
Hello
Hello friend ..
Every Time i look but i dont undasting i want
Sir
Yes...🙂
Use manual change over switch
This circuit is automation circuit..you like manual switch..
How to get neutral to main contactor coil for operation.
Without neutral contactor not hold
Thanks your comment.please watch this video..th-cam.com/video/rHpZEmuHknQ/w-d-xo.html
Hi, should A2 be coming from either 6/L3 Main Supply or Generator? In your diagram, its coming from 5/L3? How will contactor ever be turned on?
a2 must be neutral for the contactor to be on.
With due respect sir, u're very wrong. U really don't understand ur diagram. It's incorrect sir. With this ur diagram, non of the contactors can ever turn on cos the supply of their A2 is coming from wrong side
Thank you so much i am glad. please can you make this circuit a PDF so i can get it printed? if i can send my mail address. thanks
Thank you I do not currently have the circuit diagram here. I will create it and give it to you.
Sorry for being late to reply😊😊
eltronic3@gmail.com
my email..
it will not work because A2 (-) taking from output (after contactor), should be from input (before contactor). and generator continue start, never stop.
Thanks you for your comment.
Please watch this video.(Single Phase ATS with explain)
th-cam.com/video/rHpZEmuHknQ/w-d-xo.html
මට මේකෙ ඩයිග්රම් එකක් ගන්න පුලුවන්ද..
Mekat balanna..th-cam.com/video/rHpZEmuHknQ/w-d-xo.html
Digaram eka adapu ekak ne ne.adala tamai denna wenne..
good send me 3phase
Thanks friend..i will create 3phase ats system 🤗
Give me the model no. Of that contractor
A contactor with a current of 40A should be selected between the main contact points.
Both auxiliary points of the first contactor should be N / C.
Hlo
Helloo friend. watch my videos always.
This is Wair (N) poroblam for bobin s condactor s
Thanks friend your comment. please watch this video
th-cam.com/video/rHpZEmuHknQ/w-d-xo.html
@@ELTronic3 Thanks i see
You are right
Stop too much music playing
Ok friend
Poor Explanation
Ok friend.
th-cam.com/video/rHpZEmuHknQ/w-d-xo.html
Stop too much music playing 2:43
Sorry friend..volume down and re watch
Stop too much music playing
Stop too much music playing 2:43
Sorry friend..volume down and re watch thanka...