***Main supply contactor auxiliary point 2 should be N / C (normally closed). You can buy such a contactor in the market or you can use auxiliary contact block. Thanks.
Very Useful video no doubt, thank you for your work and your time. but how could Bobin of the Power contactors and relays 230 V be ON (Energised), wen A2 terminal is connected from outlet terminals of the Contactors, or I misunderstud the Circuit?
Thank you very much for your comment. Please watch this for better understanding. th-cam.com/video/rHpZEmuHknQ/w-d-xo.html&feature=share&EJGixIgBCJiu2KjB4oSJEQ
Great video....One question though, why did u connect the generator relay-contactor's A2 coil terminal to main power neutral line, shouldn't the A2 for the generator be connected to line two of the generator power wire
Both contactors in this circuit do not turn on at the same time .interlock is used for this circuit.Therefore it is correct to connect the neutral terminals together and assign them to the A2 terminals.
I think u're wrong here. Y do you pick neutral from the output of the contactor to supply the terminal A2 of your coils? You Even linked both the utility and generator together?. Thought the generator would've gotten it's neutral from the input terminal of Gen contactor to feed its coils separately. My observation though, i stand to be corrected please
Hi, I have a Schneider conext 4024 system with a 24V Battery System. I have a WEN 4750 Generator like in your video above. With that said, I have a relay setup, that when I lose the AC, which basically means, that her home is dead from the AC side of the Solar system, it will signal the relay to switch to the generator. The problem with that, is that I still have to manually go out and start the generator. So, what I’m Looking for is a switch that will sense the battery voltage and the loss of AC, in case of loss of Solar power, and a low voltage of the Battery system, to signal the Generator to start. Do you have any video's like that?
merci pour le montage, comment la bobine du premier contacteur sera exciter or pour l'exciter , il faut que le timer soit fermé or il n'a pas encore son neutre pour basculer vers le contactes fermés ( 8 et 6), avec le relais aussi (8 et 6 est ouvert), il est alimenté par le neutre de la sortie or les contacteurs sont tous ouverts car leurs bobines ne sont excitées, ... le montage n'a pas encore fonctionné
bahi jaan mujhy ji batain ky genrator ki jo start ke wire ja stop karny wali wire kaisy lagy gin ap ke meherbani ho gi janab ager numbr mil jaye to sab say best ha thanks
With due respect sir, u're very wrong. U really don't understand ur diagram. It's incorrect sir. With this ur diagram, non of the contactors can ever turn on cos the supply of their A2 is coming from wrong side
How its working with out Neutral U can not connect Neutral from the main power or Generator and how to stop Generator self starter wy U not use to NC point of contactor and it can run to b two timer 12vol and 220vol
it will not work because A2 (-) taking from output (after contactor), should be from input (before contactor). and generator continue start, never stop.
***Main supply contactor auxiliary point 2 should be N / C (normally closed). You can buy such a contactor in the market or you can use auxiliary contact block. Thanks.
Help me
Thanks for the video it's good but the generator contactor won't be energized since it doesn't receive the neutral
Thanks your best comment my friend.I'm made a small mistake.Sorry
Watch this one for beter understand it.
th-cam.com/video/rHpZEmuHknQ/w-d-xo.html
Very Useful video no doubt, thank you for your work and your time. but how could Bobin of the Power contactors and relays 230 V be ON (Energised), wen A2 terminal is connected from outlet terminals of the Contactors, or I misunderstud the Circuit?
Thank you very much for your comment. Please watch this for better understanding.
th-cam.com/video/rHpZEmuHknQ/w-d-xo.html&feature=share&EJGixIgBCJiu2KjB4oSJEQ
Sir this very informative video God bless u but I can not understand why you use comman neutral plz explain me thanks
Thank you...In one case only one contactor is turned on (interlock system is used) so it is not common neutral.
Great video....One question though, why did u connect the generator relay-contactor's A2 coil terminal to main power neutral line, shouldn't the A2 for the generator be connected to line two of the generator power wire
Both contactors in this circuit do not turn on at the same time .interlock is used for this circuit.Therefore it is correct to connect the neutral terminals together and assign them to the A2 terminals.
Thank you very much your comment
I think u're wrong here. Y do you pick neutral from the output of the contactor to supply the terminal A2 of your coils? You Even linked both the utility and generator together?. Thought the generator would've gotten it's neutral from the input terminal of Gen contactor to feed its coils separately. My observation though, i stand to be corrected please
good video but question is what if you wanted to simply run generator manually?
I will submit a video with a suitable solution for it.
Thank for your comment 😊
Sir light ane se genrator off hoga fir or DG contactor off hoga fir timer chalega last may Main contactor on hoga kya
Thanks friend ..
Please watch this video
th-cam.com/video/rHpZEmuHknQ/w-d-xo.html
Sir dg automatic on off hoga kya
Thank you friend your comment..
Please watch this video
th-cam.com/video/rHpZEmuHknQ/w-d-xo.html
Stop aur start push bottn hai kya ya
I don’t know how to stop machine?when main supply coming?🙏
Thanks your comment.please watch my ATS video..
th-cam.com/video/rHpZEmuHknQ/w-d-xo.html
This very good
Thanks.keep watching my videos.
Sir very good
But more explain by morally with practical bcs eas to understand
Thank you so much .. Ask if there is anything you do not understand
Single phase ATS explain
th-cam.com/video/rHpZEmuHknQ/w-d-xo.html
You take neutral kontrol after main contactor, how it will be activated
Neutral wire should be connect to contactor coil ..
❤❤❤❤❤❤❤❤❤❤❤❤❤❤❤❤❤❤❤❤❤❤❤❤❤❤❤❤
❤️❤️❤️🙏🙏🙏.Thanks
Pardon me, Shouldn't the Stop of the gen be connected to the N/O of the relay? In that way, it the completes the STOP circuit when the power returns
Thanks your comment. 😍
Depending on the type of start stop switch on the generator we can select N / O, N / C on the relay.
Please watch other video..
th-cam.com/video/rHpZEmuHknQ/w-d-xo.html
@@ELTronic3 my
sir please make 3phase ATS & auto generator diagram video
I will create this video immediatly.Thanks👍👍
For how many seconds we should set ac and dc timer
Give example
Good Expalaination, Please send me 3phase ATS wiring diagram.
Thanks...i will create a 3 phase ats systerm
Good stuff
Thanks friend..
Thank you brother
Thanks friend
❤❤❤❤
Thanks friend..
Hi, I have a Schneider conext 4024 system with a 24V Battery System. I have a WEN 4750 Generator like in your video above. With that said, I have a relay setup, that when I lose the AC, which basically means, that her home is dead from the AC side of the Solar system, it will signal the relay to switch to the generator. The problem with that, is that I still have to manually go out and start the generator.
So, what I’m Looking for is a switch that will sense the battery voltage and the loss of AC, in case of loss of Solar power, and a low voltage of the Battery system, to signal the Generator to start. Do you have any video's like that?
Thanks your comment.
There is currently no video created. I will create it.
Great video
Thank you..
Merci
Ok friend
Thank you sir
Thank you friend..😍😍
I want to see the 240 volts wiring diagram
The timer contactor used should be 240V.Diagram same
Watch this one..to better understand .
th-cam.com/video/rHpZEmuHknQ/w-d-xo.html
Sir video thoda jaldi banate to Accha hota
Thank you..next video create fast
Gen stop piont how to work with N/C point in relay of contector
Gen stop and start function is same, hiw to work this function?
Sir please this doubt.
Watching care full my friend
th-cam.com/video/rHpZEmuHknQ/w-d-xo.htmlsi=DY91VePcfBL_pQGZ
Thanks.
And another why you use relay for generator stoping use n/c point
You can also use the N / O point depending on the stop switch used on the generator
Please sir is video main main & gen indicator & auto manual rotary switch connection Karke dikhyo
I will create this method video
សុំសួរមួយលោកគ្រូតើប្រព័ន្ធនេះវាដេរម៉ាស៊ីនភ្លើង auto មែន
Thanks your comment ..😍😍
merci pour le montage, comment la bobine du premier contacteur sera exciter or pour l'exciter , il faut que le timer soit fermé or il n'a pas encore son neutre pour basculer vers le contactes fermés ( 8 et 6), avec le relais aussi (8 et 6 est ouvert), il est alimenté par le neutre de la sortie or les contacteurs sont tous ouverts car leurs bobines ne sont excitées, ... le montage n'a pas encore fonctionné
Thanks your best comment...please watch this video for better idea
th-cam.com/video/rHpZEmuHknQ/w-d-xo.htmlsi=k732LE3WC3bwCwbz
Thanks..❤️❤️
bahi jaan mujhy ji batain ky genrator ki jo start ke wire ja stop karny wali wire kaisy lagy gin ap ke meherbani ho gi janab ager numbr mil jaye to sab say best ha thanks
Thanks your comment..
th-cam.com/video/rHpZEmuHknQ/w-d-xo.html
Please brief in audio how this circuit works
Thank you friend.I will create your video.😊
Check this out for now.
th-cam.com/video/rHpZEmuHknQ/w-d-xo.html
Thanks
Ok friend .Stay with me.🤗
If you use this comman neutral I think circuit not working plz clear this
In one case only one contactor is turned on (interlock system is used) so it is not common neutral.
Use manual change over switch
This circuit is automation circuit..you like manual switch..
How can i identity the stop and start wires of a generator?
Remove the wire from the start switch and off switch from the control box of the generator.
Connect the wire as in this video.
Pls how can i contact you to send you the images of the generator am talking about. Thanks?
@@christophernwafor9779 thank you.. your comment.
eltronic3@gmail.com
Ok bro
oi vai aita koi pabo piz bolben
what are you saying dude....
Hi, should A2 be coming from either 6/L3 Main Supply or Generator? In your diagram, its coming from 5/L3? How will contactor ever be turned on?
a2 must be neutral for the contactor to be on.
With due respect sir, u're very wrong. U really don't understand ur diagram. It's incorrect sir. With this ur diagram, non of the contactors can ever turn on cos the supply of their A2 is coming from wrong side
How its working with out Neutral U can not connect Neutral from the main power or Generator and how to stop Generator self starter wy U not use to NC point of contactor and it can run to b two timer 12vol and 220vol
Thank your comment..I always use contactor n/c point.interrlock system very important.
Please watch this video..
th-cam.com/video/rHpZEmuHknQ/w-d-xo.html
Wiring on A2 is wrong it will not automatically turn to normal when the mains power returns.
Thanks your comment 😊..please watch this video.
th-cam.com/video/rHpZEmuHknQ/w-d-xo.html
Software name pls
Salut je peux avoir son schéma
No poblem.thanks
it will not work because A2 (-) taking from output (after contactor), should be from input (before contactor). and generator continue start, never stop.
Thanks you for your comment.
Please watch this video.(Single Phase ATS with explain)
th-cam.com/video/rHpZEmuHknQ/w-d-xo.html
Hello
Hello friend ..
Every Time i look but i dont undasting i want
Poor explanation, when ur sharing knowledge always try to explain not to play music
এইখানে তিনটা রিলে দরকার নেই,,, একটাই এনাপ,, যদি জানলে,,,,,,
Thanks friend your comment..
How to get neutral to main contactor coil for operation.
Without neutral contactor not hold
Thanks your comment.please watch this video..th-cam.com/video/rHpZEmuHknQ/w-d-xo.html
Stop too much music playing 2:43
මට මේකෙ ඩයිග්රම් එකක් ගන්න පුලුවන්ද..
Mekat balanna..th-cam.com/video/rHpZEmuHknQ/w-d-xo.html
Digaram eka adapu ekak ne ne.adala tamai denna wenne..
Thank you so much i am glad. please can you make this circuit a PDF so i can get it printed? if i can send my mail address. thanks
Thank you I do not currently have the circuit diagram here. I will create it and give it to you.
Sorry for being late to reply😊😊
eltronic3@gmail.com
my email..
Sir
Yes...🙂
good send me 3phase
Thanks friend..i will create 3phase ats system 🤗
Stop too much music playing
Ok friend
Give me the model no. Of that contractor
A contactor with a current of 40A should be selected between the main contact points.
Both auxiliary points of the first contactor should be N / C.
This is Wair (N) poroblam for bobin s condactor s
Thanks friend your comment. please watch this video
th-cam.com/video/rHpZEmuHknQ/w-d-xo.html
@@ELTronic3 Thanks i see
You are right
Hlo
Helloo friend. watch my videos always.
Poor Explanation
Ok friend.
th-cam.com/video/rHpZEmuHknQ/w-d-xo.html
Stop too much music playing
Stop too much music playing 2:43
Sorry friend..volume down and re watch
Stop too much music playing 2:43
Sorry friend..volume down and re watch thanka...