TIA Portal: High speed counter with TM Count 2x24V

แชร์
ฝัง
  • เผยแพร่เมื่อ 28 ก.ย. 2024

ความคิดเห็น • 15

  • @hemadeepan644
    @hemadeepan644 3 หลายเดือนก่อน

    Hi,Thanks for the video, can we apply this to PLC SIM also? I followed same steps, but it showing error "Missing module or power supply".

  • @JohnsView
    @JohnsView 3 ปีที่แล้ว

    Great upload keep em coming cheers

  • @vorapobautomation9760
    @vorapobautomation9760 2 ปีที่แล้ว

    How to use motor encoder with TM Count 2x24V in order to read motor speed ?

    • @softwarewizard9027
      @softwarewizard9027  2 ปีที่แล้ว +1

      If you have connected the encoder of the motor to the tm count:
      -on the modules "Measured value" tab, you have to select velocity
      -you can leave the update time on 10ms
      -if you want to get the speed in RPM leave the time base on 60s (1minute)
      -and for last you have to enter your encoders increment in 1 total turn (it is written on the encoder)
      -when these things are downloaded, you can see it on the measured value input double word.
      Hope it helps, if you need more clarification just tell me.

    • @vorapobautomation9760
      @vorapobautomation9760 2 ปีที่แล้ว

      Can you show in next video please ?
      Thank you.

    • @vorapobautomation9760
      @vorapobautomation9760 2 ปีที่แล้ว

      How to wiring encoder cable to TM module ?
      Can you show all in next video please ?

    • @softwarewizard9027
      @softwarewizard9027  2 ปีที่แล้ว +1

      @@vorapobautomation9760 Yes, I will make it soon then. :)

    • @softwarewizard9027
      @softwarewizard9027  2 ปีที่แล้ว +1

      @@vorapobautomation9760 yes, but you have to know which wire is which on your encoder. If you know which ones are the A (and B is optional, also the N) then you only need to power it from the modules encoder supply and then you are good to go. :)

  • @betelgeuse369
    @betelgeuse369 13 ชั่วโมงที่ผ่านมา

    Nice. THX for video

  • @dipsr3104
    @dipsr3104 2 ปีที่แล้ว

    Good one! Struggling with implementing synchronization part, Is the input DI0 hard wired to encoder signal N? And how are you setting DO0 as you have chosen setting "use by user program "

  • @juanreeves3128
    @juanreeves3128 3 ปีที่แล้ว

    Interesting

  • @streetcurb2451
    @streetcurb2451 3 ปีที่แล้ว

    Nice one