Como resetar o conversor de frequência para as configurações de fábrica utilizando o LCP 102

แชร์
ฝัง
  • เผยแพร่เมื่อ 25 ต.ค. 2024

ความคิดเห็น • 40

  • @LeandroSilva-dt2zc
    @LeandroSilva-dt2zc 3 ปีที่แล้ว +2

    Parabéns pelo feedback, ótima explicação

  • @josemirrocha6355
    @josemirrocha6355 4 ปีที่แล้ว +5

    Parabéns, bem didático ! Excelente explicação 👏🏽👏🏽👏🏽👏🏽

    • @DanfossBrasilOficial
      @DanfossBrasilOficial  4 ปีที่แล้ว

      Obrigado, Josemir!!

    • @sebastianmontanez3782
      @sebastianmontanez3782 3 ปีที่แล้ว

      @@DanfossBrasilOficial Hi! How are you? i found this device danfoss graphical local control panel (keypad) - lcp 102 i would like to use something like 3 d printer is it possible ?? thanks for the reply

  • @maxsuelalves1376
    @maxsuelalves1376 3 ปีที่แล้ว +1

    Muito objetivo nas suas explicações !
    Parabéns.

  • @maxwillian2120
    @maxwillian2120 3 ปีที่แล้ว +1

    Muito obrigado.

  • @luangrandi6159
    @luangrandi6159 4 ปีที่แล้ว +2

    Como sugestão, façam um vídeo mostrando o setup nos terminais e configuração no grupo de parâmetros 14-22 (opção 1), para realizar o teste da placa de controle do drive. Este teste ajuda bastante em um diagnóstico de falha.

    • @DanfossBrasilOficial
      @DanfossBrasilOficial  3 ปีที่แล้ว

      Obrigado a sua sugestão, Luan. Agradecemos a sua participação.

  • @JERRYAES
    @JERRYAES 9 หลายเดือนก่อน +1

    Seria muito top essa IHM como um aplicativo para smartphone.

    • @DanfossBrasilOficial
      @DanfossBrasilOficial  8 หลายเดือนก่อน +1

      Olá, Jerry. Realmente seria uma otima opção, mas por enquanto utilizamos apenas pelo nosso software MCT-10.

  • @Ju-zs9zb
    @Ju-zs9zb 2 ปีที่แล้ว +1

    Uma dúvida.
    O alarme A13 sobrecorrente
    É possível reset pelos parâmetros 14-20 (3 ou mais vezes) e 14-21 tempo de reset.
    Só consigo esse reset manualmente, gostaria ele de forma automática conforme o tempo definido em 14-21

    • @DanfossBrasilOficial
      @DanfossBrasilOficial  10 หลายเดือนก่อน

      Olá! O alarme A13 seria uma opção "trip lock", nesse caso ele limita o conversor ao reset manual, sendo assim, temos uma opção para o reset automático 14-90.7 --> [2] Trip, desta forma se torna possível fazer o reset automático.

  • @juliosilva9532
    @juliosilva9532 3 ปีที่แล้ว +1

    Bom dia como ,baixar esse display para simular. Desde já eu agradeço

    • @DanfossBrasilOficial
      @DanfossBrasilOficial  10 หลายเดือนก่อน

      Olá, Julio. Esse display é uma opção de simulação do nosso software MCT-10, disponível em nosso site: www.danfoss.com/pt-br.

  • @VictorHFVitor
    @VictorHFVitor 10 หลายเดือนก่อน +1

    Boa tarde.
    Estou com a seguinte mensagem no display: Clear logs S: 28 [M26].
    Como resetar essa mensagem?

    • @DanfossBrasilOficial
      @DanfossBrasilOficial  10 หลายเดือนก่อน

      Olá, Vitor. Nesse caso, depende do modelo de seu inversor, portanto pedimos que verifique o manual de operação onde estaria listado todos os alarme e como resolvê-los.

  • @lucianotavares349
    @lucianotavares349 4 ปีที่แล้ว +2

    Boa tarde! Como eu faço para pular uma frequência ex: o compressor chegar a frequência 45 ate 49 a tubulação fica vibrando tem como pular essa frequência.

    • @DanfossBrasilOficial
      @DanfossBrasilOficial  10 หลายเดือนก่อน

      Olá, Luciano! Nesse caso, o conversor vai fazer sua rampa normalmente. Para chegar em 49, é necessário passar por uma frequência abaixo.

  • @andersonrodrigo2216
    @andersonrodrigo2216 ปีที่แล้ว +1

    Como faço para baixar esse simulador da IHM ??

    • @DanfossBrasilOficial
      @DanfossBrasilOficial  ปีที่แล้ว

      Olá! Como indicado ao @filomenolima6713, este simulador da IHM fica disponível no nosso software do MCT-10, onde é possivel parametrizar o drive com conexão via USB-B por um computador.
      O simulador fica disponivel ao abrir um projeto ou simular um drive, pode ser baixado gratuitamente em nosso site abaixo usando a CD 12314500:
      www.danfoss.com/pt-br/service-and-support/downloads/dds/vlt-motion-control-tool-mct-10/

  • @FlavioPereiraSalesflaviosales
    @FlavioPereiraSalesflaviosales ปีที่แล้ว +1

    oLÁ BOM DIA mATEUS! COMO FAÇO PARA RESOLVER FALHA: ERRO AL8

    • @DanfossBrasilOficial
      @DanfossBrasilOficial  ปีที่แล้ว

      Olá, Flavio! O alarme 8 é de subtensão no barramento CC - Você deve verificar a tensão do Drive e fazer um teste na alimentação. Se persistir, por favor envie um e-mail para a nossa equipe de atendimento ao cliente: sac.brasil@danfoss.com

  • @jorjiosapigao5417
    @jorjiosapigao5417 4 ปีที่แล้ว

    sir..hvac volt drive its possible to input dc volts.

  • @supertecmt3611
    @supertecmt3611 2 ปีที่แล้ว +1

    E quando o inversor já tem uma pré senha cadastrada e não consigo acessar o main menu

    • @DanfossBrasilOficial
      @DanfossBrasilOficial  10 หลายเดือนก่อน

      Olá! Nesse caso, a única opção seria realizar um reset de fábrica via botões, sendo assim, você pode utilizar o reset de botões:
      1° Desligar conversor (Sem alimentação)
      2° Pressionar simultaneamente teclas [STATUS] + [OK] + [MAIN MENU]
      3° Ligar o conversor com as teclas pressionadas
      4° Após 10 segundos, soltar as teclas
      5° Alarme 80 indicará a conclusão do processo
      6° Resetar o alarme pressionando o botão [RESET]
      7° Iniciar parametrização

  • @daniel.847
    @daniel.847 10 หลายเดือนก่อน +1

    1-3* Avan. Dados do Motor
    1-30 Resistência do Estator (Rs)
    [Ohm] * Dep. dos dados do
    motor
    1-33 Reatância de Fuga do
    Estator (X1)
    [Ohm] * Dep. dos dados do
    motor
    1-35 Reatância Principal (Xh)
    [Ohm] * Dep. dos dados do
    motor .
    Procurei mas não achei esses dados na placa do motor.

    • @DanfossBrasilOficial
      @DanfossBrasilOficial  10 หลายเดือนก่อน +1

      Olá, Daniel. Esses itens são medidos pelo parametro 1-29 - AMA.

  • @francisconeves5499
    @francisconeves5499 3 ปีที่แล้ว

    Ola boa tarde!
    Quando no painel aparece o nome perda de fase, o que significa e como se faz para resolver?

    • @DanfossBrasilOficial
      @DanfossBrasilOficial  3 ปีที่แล้ว

      Olá, Francisco. Para esta dúvida, nosso departamento técnico está a disposição através dos canais de e-mail: sac.brasil@danfoss.com e SAC.: 0800 87 87 847 para assim solucionar o que esta aparecendo no painel. Agradecemos sua participação

  • @SritaAdiLz
    @SritaAdiLz 4 ปีที่แล้ว +1

    Hola, podrias apoyarme con los parametros para arrancar el variador en auto que suba hasta 55HZ y se mantenga ahi? gracias

    • @DanfossBrasilOficial
      @DanfossBrasilOficial  10 หลายเดือนก่อน

      Hola! Para hacer esto, puedes configurar el parámetro 3-02 a 55 Hz para que se quede bloqueado en esa frecuencia.

  • @otonielbarros4110
    @otonielbarros4110 ปีที่แล้ว

    Meu variador deu alarme 21 erro de configuracao como fasso para volta denovo

    • @DanfossBrasilOficial
      @DanfossBrasilOficial  ปีที่แล้ว

      Olá, Otoniel! Por favor, entre em contato com o nosso SAC pelo e-mail: sac.brasil@danfoss.com 👍

  • @VandersonCastelhano
    @VandersonCastelhano ปีที่แล้ว

    Falha na partida , será que algum parâmetro errado?

    • @DanfossBrasilOficial
      @DanfossBrasilOficial  ปีที่แล้ว

      Olá! Podem ser parâmetros do motor com algum desvio, mas pode depender da aplicação que esta sendo colocado.

  • @alexandremonteiro4326
    @alexandremonteiro4326 4 ปีที่แล้ว

    O modelo que eu tenho não tem essa tecla

    • @DanfossBrasilOficial
      @DanfossBrasilOficial  3 ปีที่แล้ว

      Olá, Alexandre. Para essa dúvida nosso departamento técnico está a disposição para identificar qual e seu modelo e as teclas corretas.
      O departamento técnico atende através dos canais de e-mail: sac.brasil@danfoss.com e SAC.:0800 87 87 847 para assim solucionar o que esta aparecendo no painel. Agradecemos sua participação.