  • An #automatic_transfer_switch (#ATS) or an #automatic_changeover_switch transfers power supply from its primary source to a backup #generator automatically, when it senses partly failure or a total failure in the primary source.
    When a failure occurs in the primary power system the ATS invokes the backup source which is a three phase diesel powered #automatic_generator here, to run electric equipment until utility power is restored.
    This ATS is capable of automatic starting and stopping of the generator too, in addition to the automatic transferring of power to the load.
    ATS needs to be properly designed and wired to the primary and backup power sources, as it must communicate effectively with both power sources to switch power and connect the equipment to the proper power source with a minimum delay period.
    If the video is useful, please subscribe to the channel.
    Thank you.
    #changeoverswitch #changeover #self_start_generator #3phase #ac_generator
    #3phase_generator #changeoverswitch #auto_changeover_switch #ATS_panel_wiring #electrical_wiring #electrical_safety #Generator_for_home
    #Generac_generator #Generator_automatic_start #Automatic_generator_start_and_stop #contactor_wiring #how_to_start_generator #generator_start
    More videos for you 👇
    Surge Protection Device (SPD): Operation and Installation on a Single phase or 3phase DB, explained.
    • Surge Protection Devic...
    Safety Relay: Operation and installation explained.
    • Working principle of S...
    Automatic Start-Stop of generator with ATS / Automatic transfer switch / Automatic changeover switch
    • How to design an ATS f...
    Phase Failure Relay (PFR): Operation and Installation.
    • Phase Failure Relay (P...
    Emergency Stop Push button switch - Operation and Wiring Explained.
    • Emergency stop push bu...
    Single phase Induction Motor operation with Start Run Capacitors.
    • Single phase Induction...
    Star Delta Starter Power circuit wiring for 3Phase Induction Motor- Operation explained.
    • Star Delta Starter pow...
    VFD (Variable Frequency Drive) and Inverter Operation Explained.
    • How Variable Frequency...
    3 Phase Electricity operation: How it works and Power Calculations.
    • What is 3 Phase Electr...
    Motor speed (RPM) calculation: Synchronous speed & Fractional slip explained.
    • Single phase Induction...

ความคิดเห็น • 163

  • @ElectroAcademyEA
    @ElectroAcademyEA  ปีที่แล้ว +9

    Hi everyone,
    Just a kind request to the viewers and professionals who can afford to sponsor or fund this channel, mainly for the benefit of the viewers all over the world.🌎🗺✈
    It will also definitely be a motivation for me, to continue this channel with good explanatory educational videos for all of you.
    You can contribute by being a Sponsor of this channel using the following link, patreon.com/ElectroAcademy
    I made this request few months ago, and now we have one Patron who has come forward to help this channel.💪💪
    I love it from the bottom of my heart.❤❤❤
    I know, many have become patrons of entertainment channels mainly, but look forward to seeing some more supporters who understand the value of an educational channel like this.
    Your kind gesture will be most welcome..!❤👍
    Thank you and Best regards.
    Sudarshan,
    Creator of Electro Academy Channel.

  • @abdiismael6138
    @abdiismael6138 11 หลายเดือนก่อน +1

    this is absolutely comprehensive videos that need to be supported in every means

  • @faridahmedrana2688
    @faridahmedrana2688 10 หลายเดือนก่อน +1

    Sir, You are the great teacher for electrician. May Allah bless you. Thanks.

  • @pattersonbogar6380
    @pattersonbogar6380 ปีที่แล้ว +1

    A well explained information supported with clear pictorial diagram. Thank you for dedicating your time and effort to share your knowledge on this particular topic. Thank you...much appreciated

  • @polyfaruk190
    @polyfaruk190 2 ปีที่แล้ว +2

    Very good.thank you sir

  • @GAMINGYT-eg6xj
    @GAMINGYT-eg6xj 2 ปีที่แล้ว +2

    very good video sir thanks

  • @venanciojpena1669
    @venanciojpena1669 ปีที่แล้ว +1

    Very interesting & really appreciated

  • @cabs79
    @cabs79 ปีที่แล้ว +1

    Is this diagram can be in actual wiring of the ats panel?

    • @ElectroAcademyEA
      @ElectroAcademyEA  ปีที่แล้ว

      Yes. Basic arrangement is this.
      Changes are there according to the different models and brands.

  • @thesportsbar7
    @thesportsbar7 2 ปีที่แล้ว +1

    Very clear and understanding

  • @ousmanfadera8310
    @ousmanfadera8310 ปีที่แล้ว +1

    great lectures credible and amazing. any chance of scholarships on electrical and electronic engineering into your reputable and renowned Electro Academy..

    • @ElectroAcademyEA
      @ElectroAcademyEA  ปีที่แล้ว

      We currently teach only through TH-cam media.
      We may consider this when we start our learning center soon.

  • @agustinussonoto7794
    @agustinussonoto7794 2 ปีที่แล้ว +1

    The best tutorial..

  • @ibekwechidithompson4853
    @ibekwechidithompson4853 ปีที่แล้ว +1

    Thanks for the lessons, please can I apply this to a single Phase? And can I have the circuit diagram for this video, thanks

  • @ibekwechidithompson4853
    @ibekwechidithompson4853 ปีที่แล้ว +1

    Thanks for the video, but please can I see its physical build-up

    • @ElectroAcademyEA
      @ElectroAcademyEA  ปีที่แล้ว

      Thank you.
      Standard arrangement is shown here with current flow animation, mainly for the ones who need to understand the automatic starting of the generator easily.

  • @michaelisongekwere1402
    @michaelisongekwere1402 2 ปีที่แล้ว +1

    Please if am to design this ATS for a load wattage of 25,000watts in facility what is the the size of panel by millimeters I should request to buy? That would contain these components

    • @ElectroAcademyEA
      @ElectroAcademyEA  2 ปีที่แล้ว

      Actually the size of the panel is to be decided according to the component sizes and the relevant wiring work too. Some component sizes might be different according to their brands also.
      If you are not an Electrician, better to get help from one to get good idea on sizing of the panel board.

  • @sarmadali1991
    @sarmadali1991 2 ปีที่แล้ว +1

    Can you explain how connect swich of generator to run and stop generator auto. Please draw wiring diagram for connections

    • @earthenergyhex
      @earthenergyhex 2 ปีที่แล้ว +1

      yes I would like to see the same

    • @ElectroAcademyEA
      @ElectroAcademyEA  2 ปีที่แล้ว

      Generator manual start button wires need to be connected to the two green points marked as start connection on the diagram for automatic starting.
      Generator stop button wires need to be connected to the two red dots marked as stop connection for auto stopping of the generator.
      If you need an auto - manual switch for generator, connection from the battery can be provided through a 2 pole breaker.
      This breaker OFF position will act as generator on manual starting only, still the power will automatically change over after you start the generator manually.

    • @sarmadali1991
      @sarmadali1991 2 ปีที่แล้ว

      @@ElectroAcademyEA
      I didn't understand you can you draw wiring diagram to explain that
      Thank you ❣️❣️❣️

  • @marounabimoussa4374
    @marounabimoussa4374 2 ปีที่แล้ว +1

    Excellent explanation! Just one question though: contactors have 3 main poles and 2 accessory poles?? The ones I usually see have just one accessory...

    • @ElectroAcademyEA
      @ElectroAcademyEA  2 ปีที่แล้ว +1

      Normally contactors have 2 auxiliary contact points, NO and NC.
      But, according to the requirement, you can purchase heavy duty contactors with 4 auxiliary contact points, two NO and two NC points.
      There are contactors where you can add more auxiliary contact points on to it also.
      Additional contact points can be slide on to the contactor top and lock it.
      It should be done according to the manufacturer recommendations only.

    • @michaelisongekwere1402
      @michaelisongekwere1402 2 ปีที่แล้ว +1

      @@ElectroAcademyEA good please should I use stop push and start push buttons to manually switch off and on generator?

    • @ElectroAcademyEA
      @ElectroAcademyEA  2 ปีที่แล้ว

      @@michaelisongekwere1402 Yes.
      Further, you can use a 2 pole breaker when wiring 12 volt power from the battery to this system.
      Breaker "ON" position is your generator automatic start/stop operating position.
      Similarly, breaker "OFF" position will act as generator manual start/stop position.
      In both these positions power transferring will be fully automatic, although you have to start the generator manually, in breaker "OFF" position.

  • @SivaKumar-zi3dd
    @SivaKumar-zi3dd 8 หลายเดือนก่อน +1

    ❤❤

  • @CR7FanBoyy
    @CR7FanBoyy ปีที่แล้ว +1

    On the grid side you used two timer relays
    Can’t one timer relay do the job

    • @ElectroAcademyEA
      @ElectroAcademyEA  ปีที่แล้ว

      Timer 1 is there to make generator to run on load for 2 to 3 minutes even after grid power is available.
      If grid power goes off again within this period, generator is on load and power supply will not be interupted.
      Although recommended, you can omit this timer if intermittent power disturbances are minimal.

  • @geraldrice3423
    @geraldrice3423 ปีที่แล้ว +1

    Too difficult to follow . Need to slow down a bit !

  • @OsmanyellaKargbo
    @OsmanyellaKargbo 6 หลายเดือนก่อน

    Any Whatsapp group pls I want to join

  • @davidshirindzi4653
    @davidshirindzi4653 2 วันที่ผ่านมา +2

    I have been looking for these , too long.

  • @ibekwechidithompson4853
    @ibekwechidithompson4853 ปีที่แล้ว +1

    Thanks for the lessons, please can I apply this to a single Phase? And can I have the circuit diagram for this video, thanks
    Thanks in anticipation

    • @ElectroAcademyEA
      @ElectroAcademyEA  ปีที่แล้ว

      Thank you.
      You can use this for single phase generator wiring too.
      Instead of 3 phase 3 wires on power side of two contactors, use live wire and neutral wire on L1 and L3 terminals.
      Keep L2 terminal empty.
      Control wiring is the same as shown in this video.

  • @alkararali3548
    @alkararali3548 ปีที่แล้ว +2

    شكرا لك أخي الكريم على هذا الفيديو المهم استمر بالعطاء
    يا حبذا لو تعمل لنا فيديو اخر عن كيفيه اداره ATS ثلاث مراحل كهرباء الدولة الحكومية وكذالك كهرباء الاشتراك في الحارة وكهرباء مولد البيت في الداخل كيف الىبط بينهما

  • @Ayx12114
    @Ayx12114 6 หลายเดือนก่อน +1

    Sir can you provide schematic diagram for this system

  • @ibekwechidithompson4853
    @ibekwechidithompson4853 ปีที่แล้ว +1

    Thanks sir, please can i see how the start and stop connection is done physically, with stop and start button.
    I will be grateful if granted.
    Thanks

    • @ElectroAcademyEA
      @ElectroAcademyEA  ปีที่แล้ว

      Please try the video on below link.
      th-cam.com/video/_6WhieL50GI/w-d-xo.html&feature=share9

  • @michaelisongekwere1402
    @michaelisongekwere1402 2 ปีที่แล้ว +2

    This was an explanation thank you Sir please what are components that make up this design and connection? I know 2 magnetic contactor, 1 phase failure relay, 3 Double pole double throw 8 relay, 2 AC double pole breaker, 5 Timers
    Secondly on the battery relays you connected port 1 and 3 of start and port 1 and 3 of stop to what components is it 1 and 2 start- push and 3 and 4 stop-push components?

  • @ElectroAcademyEA
    @ElectroAcademyEA  2 ปีที่แล้ว +3

    Dear All,
    DPDT relay means Double Pole Double Throw Relay.
    Double pole is mispronounced here as Double port @ 1:32.
    Kindly take a note on this, when viewing/listening to the video.
    Regards,
    EA.

    • @gombanirorichard9759
      @gombanirorichard9759 2 ปีที่แล้ว +1

      The start connection is the one from AUTOMATIC button on generator screen?how to connect it on that relay?thank u

    • @ElectroAcademyEA
      @ElectroAcademyEA  2 ปีที่แล้ว

      Best way is to check with the generator supplier.
      Then its easy with relative brands.

  • @selimmahmud1616
    @selimmahmud1616 ปีที่แล้ว +1

    all ok.
    When my grid off then 3 hours Later generator start.
    How to set the time

    • @ElectroAcademyEA
      @ElectroAcademyEA  ปีที่แล้ว

      Hope you can get help from an electrician to correct this fault.
      Necessary timer settings are described in the video.

  • @ibekwechidithompson4853
    @ibekwechidithompson4853 ปีที่แล้ว +1

    Please sir, the relays and timers for the gen auto start are they DC or AC?

    • @ElectroAcademyEA
      @ElectroAcademyEA  ปีที่แล้ว

      Battery connected relays and timers are DC.
      All others are AC.

  • @rolandtoophanie5185
    @rolandtoophanie5185 2 ปีที่แล้ว +1

    Hey sir what type of timer relay used. Is all the timer relay ON DELAY?

    • @ElectroAcademyEA
      @ElectroAcademyEA  2 ปีที่แล้ว +1

      All the timer relays used here are ON DELAY type.
      Actually we can use ON DELAY timer relays for average OFF DELAY functions also, by using NO and NC contacts properly.

    • @rolandtoophanie5185
      @rolandtoophanie5185 2 ปีที่แล้ว

      Ok thank you. I'm going to build a system exactly like this soon for backup system

    • @rolandtoophanie5185
      @rolandtoophanie5185 2 ปีที่แล้ว

      Is there any other way I can get in contact with you to get some more information about the parts to be purchased?

  • @ayojoseph4571
    @ayojoseph4571 2 หลายเดือนก่อน +1

    This is very clear, thanks

  • @IsraelKero
    @IsraelKero 5 หลายเดือนก่อน +1

    Very helpful thanks man

  • @adammangal8530
    @adammangal8530 ปีที่แล้ว +1

    Hello, where do we get the neutral for the load from? How do we ensure there is always a neutral cable from both supplies without them interconnecting?

    • @ElectroAcademyEA
      @ElectroAcademyEA  ปีที่แล้ว

      From the generator supply, you get separate neutral cable.
      So, the two neutral cables need to be connected separately, as shown on the video.

    • @adammangal8530
      @adammangal8530 ปีที่แล้ว +1

      @@ElectroAcademyEA It only shows the 3 active wires going to the load, how does the neutral wire connect to the load?

    • @ElectroAcademyEA
      @ElectroAcademyEA  ปีที่แล้ว +1

      Sorry for that I have not shown it in the video.
      As done for the 3 power lines, you need to get two neutral lines separately from the grid and from the generator to the junction box, and connect it.
      From the junction box, only one neutral line to the load.
      3 pole contactors on grid side and generator side, need to be changed with 4 pole contactors to provide neutral wire through it.

    • @adammangal8530
      @adammangal8530 ปีที่แล้ว

      @@ElectroAcademyEA 4 pole contactor! okay thank you very much

  • @JimmyHorope-fq5zx
    @JimmyHorope-fq5zx 4 หลายเดือนก่อน +1

    That was helpful.

  • @josebravo6642
    @josebravo6642 2 ปีที่แล้ว +1

    No entiendo el inglés.

    • @ElectroAcademyEA
      @ElectroAcademyEA  2 ปีที่แล้ว

      Por favor, consulte el canal en el siguiente enlace.
      Más videos serán agregados aquí pronto.
      th-cam.com/users/Academiaelectrónica

  • @renebangura8138
    @renebangura8138 ปีที่แล้ว +1

    OK but I have a question how would this design change if you you wanted to build an ATS that changes between 3 sources. An example would be if you had grid, solar backup and generator in that priority order. Would be great to know as there's almost no info available on this specific topic

    • @JOSE-tt8tb
      @JOSE-tt8tb 10 หลายเดือนก่อน

      Bro, it’s simple, just make another same set of panel and it’s out considered as second prior after the grid, for example just do this circuit with solar and generator and it’s out again do with grid supply, in this way you can make infinite number of power sources 💪😉

  • @sandyfortuno3194
    @sandyfortuno3194 ปีที่แล้ว +1

    nice

  • @manojmule8624
    @manojmule8624 ปีที่แล้ว +1

    Thank you sir

  • @GAMINGYT-eg6xj
    @GAMINGYT-eg6xj 2 ปีที่แล้ว +2

    thanks sir,thank you so much

  • @abudaoud1310
    @abudaoud1310 2 ปีที่แล้ว +2

    Thanks for made the video🌹

  • @peterloulee8845
    @peterloulee8845 ปีที่แล้ว

    Are you doing relay switch for video

  • @seiduafataw9821
    @seiduafataw9821 ปีที่แล้ว +1

    After that how does the generator start if the grid is out.

    • @ElectroAcademyEA
      @ElectroAcademyEA  ปีที่แล้ว

      Through battery power

    • @seiduafataw9821
      @seiduafataw9821 ปีที่แล้ว

      And what? Meaning the the battery have to be charge right?

    • @ElectroAcademyEA
      @ElectroAcademyEA  ปีที่แล้ว

      Yes. You need to have a battery charger (powered by grid side) to keep the battery fully charged, in order to start the generator during a power outage.

  • @GAMINGYT-eg6xj
    @GAMINGYT-eg6xj 2 ปีที่แล้ว +1

    make the video two pump controlled by latching relay plz

  • @sheriffdeen175
    @sheriffdeen175 ปีที่แล้ว +1

    Thanks sir

  • @marcelogallelli5548
    @marcelogallelli5548 2 ปีที่แล้ว +1

    Que buen tutorial ... Lo malo es que no se hablar ingles 🤦‍♂️...

    • @ElectroAcademyEA
      @ElectroAcademyEA  2 ปีที่แล้ว

      Gracias.
      Puede ver este video en español usando el siguiente enlace.
      th-cam.com/video/rgtEnNUYTto/w-d-xo.html

  • @kyawzin2639
    @kyawzin2639 5 หลายเดือนก่อน +1

    thank

  • @SlaviTerziev
    @SlaviTerziev 10 หลายเดือนก่อน +1

    great

  • @ildarhamrayev
    @ildarhamrayev 2 ปีที่แล้ว +2

    Very nice and vivid current flow is illustrated. Makes everything clear how does it work. And explained simple. Much of thanks to u !

    • @ElectroAcademyEA
      @ElectroAcademyEA  2 ปีที่แล้ว +1

      Thank you👍

    • @ildarhamrayev
      @ildarhamrayev 2 ปีที่แล้ว +1

      @@ElectroAcademyEA waiting for more videos like that. if u can make industrial machines

  • @AliShan-lv9pf
    @AliShan-lv9pf ปีที่แล้ว +1

    I love you 😘 great work and very helpful diagram video sooo thanks.............

  • @enochmeshullam2814
    @enochmeshullam2814 9 หลายเดือนก่อน +1

    I am very thankful to you Sir for this very informative video you have shared with those of us who are in a real need for knowledge of ATS control phenomenon. I love the video. Much thanks and great appreciation. Cheers

  • @Akolkar2
    @Akolkar2 ปีที่แล้ว +1

    Pl show timer s T1 T2 in video with colour animation. Thanks again for video,👌👌👌👌👌

  • @lappyajay1
    @lappyajay1 2 ปีที่แล้ว +1

    Can we common all the neutral...??

    • @ElectroAcademyEA
      @ElectroAcademyEA  2 ปีที่แล้ว +2

      No.
      Grid and generator side neutral lines need to be kept separated, to enable safety features like RCDs to work correctly.

  • @heartperson4987
    @heartperson4987 2 ปีที่แล้ว +1

    So excellent video about automation..
    Thanks for like this video from Bangladesh

  • @kamaphilemon2089
    @kamaphilemon2089 5 หลายเดือนก่อน +1

    Thank you Sir. You effort is much appreciated.
    Best ATS video ever

  • @tettehphilipkwei3905
    @tettehphilipkwei3905 8 หลายเดือนก่อน +1

    Sir you where my teacher you are the best 👍🔥

  • @faryazch
    @faryazch 2 ปีที่แล้ว +1

    This design is suitable for Single Phase Gride and Single Phase Generator?
    and how many self start attempt?

    • @ElectroAcademyEA
      @ElectroAcademyEA  2 ปีที่แล้ว

      Yes. You can use it on single phase grid with single phase generator.
      Normally, generator should start with one start attempt.
      If there are dificulties with starting, we need to check and correct it first.

  • @adamsoladipupo3390
    @adamsoladipupo3390 ปีที่แล้ว +1

    Well done sir, pls how will one connect the ats for single phase generator to auto start/stop

    • @ElectroAcademyEA
      @ElectroAcademyEA  ปีที่แล้ว

      For single phase generator, same two magnetic contactors can be used.
      Instead of three phase lines, live wire and the neutral wire can be taken through it. One terminal on both contactors will be empty.

  • @ashokshah7388
    @ashokshah7388 2 ปีที่แล้ว +1

    wow nice very very usefull video thank you

  • @zenebehagos3537
    @zenebehagos3537 ปีที่แล้ว +1

    10q so much for taking time do this lecture and took time to upload it

  • @WilliamsBright-z2c
    @WilliamsBright-z2c ปีที่แล้ว +1

    Very clear and understanding,thanks for this information

  • @okonkwoandrew5880
    @okonkwoandrew5880 6 หลายเดือนก่อน +1

    you are a teacher with teaching qualities I keep to your videos.

  • @anaskarim7033
    @anaskarim7033 10 หลายเดือนก่อน +1

    what a wonderful explanation it was . thanks a lot to the channel

  • @NickTheHunter
    @NickTheHunter ปีที่แล้ว +1

    Thank you so much, sir! A very good quality video! Much appreciated!

  • @hassanhussein3703
    @hassanhussein3703 2 ปีที่แล้ว +1

    Thank you

  • @sersiobordios
    @sersiobordios ปีที่แล้ว

    your sub-title covers the timer socket wiring configuration, it's bad video.

    • @ElectroAcademyEA
      @ElectroAcademyEA  ปีที่แล้ว

      You can stop subtitles by clicking the "CC" icon on the screen.

  • @lenardfritz1020
    @lenardfritz1020 2 ปีที่แล้ว +1

    Very Nice . Can we have a ladder diagram of the ATS explained above?

    • @ElectroAcademyEA
      @ElectroAcademyEA  2 ปีที่แล้ว +1

      Thank you.
      Will try to do when time permits

  • @irshadumerfarooq7901
    @irshadumerfarooq7901 2 ปีที่แล้ว +1

    Great Sir, Do you have 3 power source ATS model

    • @ElectroAcademyEA
      @ElectroAcademyEA  ปีที่แล้ว

      Generally, control circuit needs only a single phase supply or direct current supplied through a battery, to operate magnetic contactors.

  • @said_words
    @said_words ปีที่แล้ว +1

    great work ,which software have you used

    • @ElectroAcademyEA
      @ElectroAcademyEA  ปีที่แล้ว

      For animation work, Microsoft power point.
      Thank you.

  • @GAMINGYT-eg6xj
    @GAMINGYT-eg6xj 2 ปีที่แล้ว +1

    sir please make next video on latching relay plz.

  • @princeukomatthew5544
    @princeukomatthew5544 2 หลายเดือนก่อน +1

    Insightful and educative ❤

  • @sahanshrestha738
    @sahanshrestha738 2 ปีที่แล้ว +1

    Please explain how Manual and Auto mode is achieved in ATS

    • @ElectroAcademyEA
      @ElectroAcademyEA  2 ปีที่แล้ว +1

      Introduce a two pole Isolator or a breaker and take battery wires to the auto start and stop connections through it.
      Isolator "ON" position will act as "AUTO" mode.
      Isolator "OFF" position will be the "MANUAL" position.
      When Isolator is at OFF position, you need to start the generator manually when grid power is not there.
      It will supply power to the contactor top and generator side control line breaker, allowing power to transfer automatically to the load.

    • @sahanshrestha738
      @sahanshrestha738 2 ปีที่แล้ว +1

      @@ElectroAcademyEA thanks for your prompt response

  • @DS-it3xd
    @DS-it3xd 2 ปีที่แล้ว +1

    How to emergence stop button. Sir..

    • @ElectroAcademyEA
      @ElectroAcademyEA  2 ปีที่แล้ว

      Emergency stop button should come with the generator itself.

  • @anhtuannguyen2248
    @anhtuannguyen2248 11 หลายเดือนก่อน +1

    Very good, thanks.

  • @kingsleymakoi3343
    @kingsleymakoi3343 ปีที่แล้ว +1

    Good.. nice thank you

  • @kamikazeray4866
    @kamikazeray4866 2 ปีที่แล้ว +1

    Thanks a lot
    It's very useful 👍💕

  • @bijusenthil
    @bijusenthil 2 ปีที่แล้ว +1

    Good explanation

  • @amissahjoojo7961
    @amissahjoojo7961 2 ปีที่แล้ว +1

    A very good tutorial 👌