i love your video because i understand what i didnot about generator issue. plased, Could u share Rectifier slot issue how to slove? How to fail dg auto start and how to solve? Telcom power cabinet system?
Thanks for your complements. 1. Rectifier slot issue: If you're facing rectifier's slot issue, just dismantle backplane and replace faulty slot with new one, mostly slot melt due to surge issue, make sure your earthing should be fine enough (less than 3 Ohm). 2. Auto remote start: For auto start, you have to use 1 pair of cable (better to use LAN cable), Genset end: give positive through battery and negative through module remote point (e.g in DSE704 12#) and rectifier's end use rectifier's remote point + & - Telecom Power Cabinet (Power Cube): Power Cube is a power box (in case of Huawei), having rectifier as well as battery bank cabinet.
i love your video because i understand what i didnot about generator issue.
plased, Could u share Rectifier slot issue how to slove? How to fail dg auto start and how to solve? Telcom power cabinet system?
Thanks for your complements.
1. Rectifier slot issue:
If you're facing rectifier's slot issue, just dismantle backplane and replace faulty slot with new one, mostly slot melt due to surge issue, make sure your earthing should be fine enough (less than 3 Ohm).
2. Auto remote start:
For auto start, you have to use 1 pair of cable (better to use LAN cable), Genset end: give positive through battery and negative through module remote point (e.g in DSE704 12#) and rectifier's end use rectifier's remote point + & -
Telecom Power Cabinet (Power Cube):
Power Cube is a power box (in case of Huawei), having rectifier as well as battery bank cabinet.