Sir Is there any reason for apply voltage from secondary side?? When we injecting voltage from secondary it will generate 1660V at primary its not quite measurable While it's comes for 400/11kv trafo it's generating voltages in KV at primary side.. It's very unsafe & dangerous Sir Am I right or wrong??
You are most welcome. You are absolutely right in all respects. The video explains only on high-voltage step-down transformer and up to 33/11 KV Transformer. For testing 11/0.4 KV Tr. You have commented rightly. Make the process of testing which is suitable in this regard. Thank you.
Thank you very much
Welcome. Thank you❤.
Very informative.Will be helpful.
Thank you.
Can it be done with multimeter??
Ammeter is connected in series with a circuit. Therefore it is not easy to measure current by Multimeter.Thank you.
Salam
Nomoste.
Sir
Is there any reason for apply voltage from secondary side??
When we injecting voltage from secondary it will generate 1660V at primary its not quite measurable
While it's comes for 400/11kv trafo it's generating voltages in KV at primary side..
It's very unsafe & dangerous
Sir Am I right or wrong??
You are most welcome. You are absolutely right in all respects. The video explains only on high-voltage step-down transformer and up to 33/11 KV Transformer.
For testing 11/0.4 KV Tr. You have commented rightly. Make the process of testing which is suitable in this regard. Thank you.
@@electricalpassionate lv side you apply 440v that 3times in hv side 1200v this is huge