When Mov not Operated from local and remote and showing below massage on display what can do pls help. INIT-ok Modul : LCB FLASH : Intern 512K Start : downloadmanager Funct : Slave Only showing this mags no change
It's in the 'Display' Menu. See 'Operation' section of the Operating Instructions which can be downloaded from www.auma.com/en/documents/ and select 'Operating Instructions' and 'Actuator with controls'
Hello, I see your video is very helpful but what if I need to set my limit for opening to 90 and my limit to close to 65 (so in my system I want this motorized valve to operate between those settings. can you please support me?
im facing an issue in auma actuator sa10.2-f10 when operate from dcs on remote mode, on small percentage of closing command valve does not stop there and keep on closing untill 0%. Please share your expertise
@@mattewen1424 Thanks for replying. But 7 months ago i tried everything in the parameters. Than magger results of motor showed fault, got the motor rewinded but valve was still not functioning as required, temperature switch of winding was damaged on overheat and after replacing that everything is fine.
@@Yasirbacha118 Great to hear, I didn't expect you to still be figuring this out after 7 months, I hope this might help someone else troubleshooting their actuator. I'll have to think about how a thermal switch would cause the issues you mentioned.
Thank you 🙏
Do you have a video for the torque switching settings?
Thanks 😊
Need Maintenance videos.
Is there any chance to get problem if valves are open and close frequently
How to change range or span.
I problem, same time zero position but still have distance ± 30mm
I need saexc 14.1 pin diagram where to find
my position feedback showing mm unit?? can you pls tell me how can I change the percentage value
How to solve this problem position undefined
When Mov not Operated from local and remote and showing below massage on display what can do pls help.
INIT-ok
Modul : LCB
FLASH : Intern 512K
Start : downloadmanager
Funct : Slave
Only showing this mags no change
how do i connect to the bluetooth?
how do we can change the language, please ?
It's in the 'Display' Menu. See 'Operation' section of the Operating Instructions which can be downloaded from www.auma.com/en/documents/ and select 'Operating Instructions' and 'Actuator with controls'
Hello, I see your video is very helpful but what if I need to set my limit for opening to 90 and my limit to close to 65 (so in my system I want this motorized valve to operate between those settings. can you please support me?
It's helping
Looks like biffi program.
im facing an issue in auma actuator sa10.2-f10
when operate from dcs on remote mode, on small percentage of closing command valve does not stop there and keep on closing untill 0%.
Please share your expertise
There's a feature called self-retaining remote that you want to disable. It should then follow a push to run style of control.
@@mattewen1424 Thanks for replying. But 7 months ago i tried everything in the parameters. Than magger results of motor showed fault, got the motor rewinded but valve was still not functioning as required, temperature switch of winding was damaged on overheat and after replacing that everything is fine.
@@Yasirbacha118 Great to hear, I didn't expect you to still be figuring this out after 7 months, I hope this might help someone else troubleshooting their actuator. I'll have to think about how a thermal switch would cause the issues you mentioned.
Traducirlo a Español,me interesa